Plan Review Details - Permit 15060658
Plan Review Stops For Permit 15060658
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By aclange Date 2015-06-22 Time 08:58 Rev Time 0.00
Received By aclange Date 2015-06-22 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-16 Cont ID  
Sent By dhayes Date 2015-07-16 Time 15:40 Rev Time 0.00
Received By dhayes Date 2015-07-16 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By dhayes Date 2015-06-17 Time 12:56 Rev Time 0.00
Received By dhayes Date 2015-06-17 Time 12:56 Sent To Z
Notes
2015-06-17 12:56:066/17/2015
 PROJECT: PV SYSTEM
 PERMIT#: 15060658
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A DETAIL INDICATING HOW THE 60 AMP CIRCUIT
 ORIGINATES AT THE UTILITY. THE RISER DIAGRAM
 ILLUSTRATES 4, #6 WIRES ORIGINATING AT THE UTILITY BUT
 DO NOT ILLLUSTRATE HOW THAT IS IS TO BE ACCOMPLISHED OR
 WHAT TYPE OF WIRING METHOD IS UTILIZED FOR THE
 INSTALLATION OF THE #6 WIRE TO THE NEW PV PANEL. NEC
 408.4
  
 2) PROVIDE A DETAIL FOR THE INSTALLATION OF THE PVC
 CONDUIT WITH THE A/C CIRCUTRY FROM THE PV SYSTEM TO THE
 NEW PV PANEL. IS IT INSTALLED INSIDE OR OUTSIDE OF THE
 DWELLING.
  
 3) PROVIDE A GROUNDING DETAIL ILLUSTRATING THE
 CONNECTION OF THE ARRAY GROUNDING ELECTRODE CONDUCTOR
 TO THE GROUNDING ELECTRODE SYSTEM.
  
 4) INDICATE THE INSTALLATION AND USE OF THE REQUIRED
 GFI PROTECTION FOR THE ARRAY. NEC 690.5
  
 5) PROVIDE AND INDICATE ALL REQUIRED LABELING FOR PHOTO
 VOLTAIC SYSTEMS IN COMPLIANVCE WITH NEC 690.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-16 Cont ID  
Sent By dhayes Date 2015-07-16 Time 15:40 Rev Time 0.00
Received By dhayes Date 2015-07-13 Time 06:45 Sent To  
Notes
2015-07-14 06:45:33DHAYES DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-22 Cont ID  
Sent By aclange Date 2015-06-22 Time 08:58 Rev Time  
Received By aclange Date 2015-06-15 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***