Plan Review Details - Permit 15060656
Plan Review Stops For Permit 15060656
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-19 Cont ID  
Sent By ccole Date 2015-06-19 Time 14:11 Rev Time 0.00
Received By ccole Date 2015-06-19 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-18 Cont ID  
Sent By albarran Date 2015-06-18 Time 15:28 Rev Time 0.00
Received By albarran Date 2015-06-18 Time 14:46 Sent To M
Notes
2015-06-18 16:38:12ELECTRICAL PROVISO
 IN AN ATTEMPT TO EXPEDITE THE ISSUANCE OF THIS PERMIT,
 THE FOLLOWING WILL BE REQUIRED PRIOR TO THE FIRST
 ELECTRICAL INSPECTION.
 THE SCOPE OF THE MECHANICAL LICENSE AND SUBSEQUENT
 PERMIT ALLOW THE ELECTRICAL DISCONNECTION AND
 RECONNECTION OF THE EQUIPMENT FROM THE FIRST POINT OF
 DISCONNECTION. ANY WORK BEYOND THAT SHALL BE CONDUCTED
 BY A LICENSED ELECTRICAL CONTRACTOR UNDER THE BENEFIT
 OF AN ELECTRICAL SUB-PERMIT. THEREFORE, PRIOR TO THE
 FIRST ELECTRICAL INSPECTION, AN ELECTRICAL SUB-PERMIT
 SHALL BE OBTAINED. THE APPLICATION SHALL DEFINE THE
 ELECTRICAL WORK BEING PERFORMED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-19 Cont ID  
Sent By mech bin Date 2015-06-19 Time 14:12 Rev Time 0.00
Received By ccole Date 2015-06-19 Time 14:11 Sent To M
Notes
2015-06-18 10:56:066/18/15: ADDED ELECTRICAL, BUIDING, FIRE STOPS-
 ELECTRICAL NOTES AND DETAILS ON PLANS, CONCRETE PAD
 EXTENSION IN SCOPE OF WORK SUBMITTAL, REFRIGERANT
 DETECTOR AND ALARM/CC
2015-06-17 14:46:41"EXPEDITED"
 ROUTED TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By ccole Date 2015-06-19 Time 14:12 Rev Time 0.00
Received By ccole Date 2015-06-19 Time 07:16 Sent To  
Notes
2015-06-19 07:18:46MECHANICAL PROVISO 6/19/15:
  
 A REVISION TO THE PERMIT AND ISPECTIONS ARE REQUIRED
 FOR UPGRADES TO THE REFRIGERANT LEAK DETECTION/ALARM
 AND VENTILATION SYSTEMS- NORMAL AND EMERGENCY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-18 Cont ID  
Sent By ccole Date 2015-06-18 Time 14:59 Rev Time 0.00
Received By ccole Date 2015-06-17 Time 14:59 Sent To  
Notes
2015-06-18 09:32:251ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060656 6/18/15
  
 1) ADDITIONAL DETAILS REGARDING THE REFRIGERANT LEAK
 DETECTION SYSTEM, AND THE NORMAL AND EMERGENCY
 VENTILATION SYSTEMS ARE REQUIRED DUE TO THE CHILLER
 UPGRADES- SEE SHEET ME-1 ASHRAE 15-2010 SUMMARY. PER
 NOTE 1 IN THE SUMMARY I HAVE RESEARCHED PERMIT RECORDS
 BUT HAVE NOT FOUND ANY 2014 PERMITS TO UPGRADE THE
 SYSTEMS.
 PLEASE PROVIDE THE FOLLOWING INFORMATION IN ACCORDANCE
 WITH ASHRAE 15, 34, AND FMC-2010:
 A) INDICATE THE REFRIGERANT CHARGE IN LBS FOR CH-1 IN
 THE SCHEDULE ON THE SCHEDULE.
 B) REFERENCE SECTIONS 1105.6.3 FMC-10- NORMAL
 VENTILATION PROCEDURE, AND 1105.6.4 EMERGENCY
 CONDITIONS: PROVIDE DATA INCLUDING VENTILATION
 CALCULATIONS, EXHAUST FAN SCHEDULES, MAKEUP AIR LOUVER
 SIZES ETC. TO VERIFY COMPLIANCE FOR BOTH SYSTEMS.
 C) REFERENCE SECTION 8.11.2.1 ASHRAE 15, AND SECTION
 8.6 ASHRAE 34: SHOW THE EXACT LOCATIONS OF THE REQUIRED
 REFRIGERANT LEAK DETECTORS INCLUDING MOUNTING HEIGHTS
 AND SPACINGS.
 D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LEAK
 DETECTORS REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD. THE SPECS SHALL INDICATE THE DETECTORS WILL
 ACTUATE THE ALARM SYSTEM AT THE LOWEST LEVEL OF
 TOXICITY MEASURE. PLEASE INCLUDE WHAT THE LEVEL IS
 BASED ON EVIDENCE FROM QUALIFIED TEST REPORT SOURCES.
 E) PROVIDE A SEQUENCE OF OPERATION DIAGRAM FOR THE LEAK
 DETECTION/ ALARM SYSTEM. SHOW THE LOCATIONS OF ALL
 ALARM DEVICES- INSIDE AND OUTSIDE THE MACHINERY ROOM,
 AND AT THE ROOM ENTRANCE, PLEASE NOTE THE DEVICES SHALL
 BE BOTH VISUAL AND AUDIBLE. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR ANY NEW DEVICES REVIEWED AND
 APPROVED BY THE ENGINEER OF RECORD.
 2) PROVIDE STRUCTURAL DETAILS FOR EXTENSION OF THE
 CHILLER PAD AS NOTED IN THE SUBMITTED 8-1/2 X11" SCOPE
 OF WORK OUTLINE.
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW CHILLER
  
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  