Plan Review Details - Permit 15060652
Plan Review Stops For Permit 15060652
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-01 Cont ID  
Sent By albarran Date 2015-10-01 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By jwitmer Date 2015-08-31 Time 12:02 Rev Time 0.00
Received By jwitmer Date 2015-08-31 Time 10:13 Sent To FIRE
Notes
2015-08-31 11:12:26BUILDING PLAN REVIEW
 W. P. B. PERMIT:15060652
 ADD: 222 LAKEVIEW AVENUE/ GROUND FLOOR
 CONT: HOLT LEE
 TEL: ( 954)725-4881
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 31/ 2015
 ACTION: DENIED
  
 1) NEW COMMENT: THE PLAN REVIEW RE-SUBMITTAL SHEET
 INDICATES A CHANGE OF CONTRACTOR WITH CREF ESPERANTE AS
 THE CONTRACTOR WHERE AS THE CONTRACTOR ON THE PERMIT
 APPLICATION IS HOLT LEE. FOR A CHANGE OF CONTRACTOR A
 NEW APPLICATION WITH THE NEW QUALIFIER TO BE SIGNED ON.
 FLORIDA STATUTE 489.
  
 2) THE SHEET A1.2 HAS BEEN UPDATED TO SHOW A MERCANTILE
 OCCUPANCY TO THE LEFT OF THE COMMON AREA RESTROOMS AND
 A ASSEMBLY OCCUPANCY TO THE RIGHT OF THE COMMON
 RESTROOMS. THE DOOR SWINGS ARE CORRECT FOR THE OCCUPANT
 LOADS. WHAT IS THE CONCERN IS THE DOOR LEADING BETWEEN
 THE MERCANTILE OCCUPANCY AND THE COMMON RESTROOMS SHOWS
 A EXIT LIGHT ON THE RESTROOM SIDE OF THE DOOR. THE 2010
 FBC-B SECTION 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. 1014.2.1. EGRESS FROM A ROOM OR SPACE
 SHALL NOT PASS THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS
 AND THE AREA SERVED ARE ACCESSORY TO ONE OR THE OTHER,
 ARE NOT A GROUP H OCCUPANCY AND PROVIDE A DISCERNIBLE
 PATH OF EGRESS TRAVEL TO AN EXIT.
  
 WITH THE CONFIGURATION AS SHOWN THE MERCANTILE MAY BE
 CLOSED BUT WITH THE EXIT LIGHT AS SHOWN OCCUPANTS FROM
 THE ASSEMBLY OCCUPANCY WOULD BELIEVE THIS IS A EXIT
 THEY COULD USE AND IF THE MERCANTILE OCCUPANCY WERE
 CLOSED AND THE DOOR LOCKED, THERE COULD WELL BE A
 PANIC.
 AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT CAN
 BE LOCKED TO PREVENT EGRESS.
  
 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2015-06-24 Time 14:25 Sent To  
Notes
2015-06-24 15:28:15 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT:15060652
 ADD: 222 LAKEVIEW AVENUE/ GROUND FLOOR
 CONT: HOLT LEE
 TEL: ( 954)725-4881
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24/ 2015
 ACTION: DENIED
  
 1) THE PLANS ARE DENIED, THE SMALL AREA OF DETAIL (AREA
 OF WORK) PROVIDED ON THE COVERSHEET AND SHEET A1.1 DOES
 NOT LINE UP WITH GIVEN POINTS AS STAIRWELLS AND
 ELEVATOR SHAFTS. A THOROUGH REVIEW CANNOT BE MADE AT
 THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By albarran Date 2015-10-01 Time 16:04 Rev Time 0.00
Received By albarran Date 2015-10-01 Time 15:52 Sent To I
Notes
2015-10-01 16:04:3910/1/15 APPROVED WITH EXCEPTIONS AS MENTIONED BELOW:
 FAILURE TO CORRECT THESE ISSUES PRIOR TO INSPECTION
 WILL RESULT IN FAILED INSPECTION AND ASSESSMENT OF
 REINSPECTION FEES.
 1. ELECTRIC WATER COOLER SHALL BE ON A GFI PROTECTED
 CIRCUIT PER NEC 422.52
 2. THE OTHER END OF THE CORRIDOR MAY REQUIRE AN EXIT
 LIGHT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-17 Cont ID  
Sent By dhayes Date 2015-06-17 Time 14:25 Rev Time 0.00
Received By dhayes Date 2015-06-17 Time 14:25 Sent To  
Notes
2015-06-17 14:27:00APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-02 Cont ID  
Sent By pleduc Date 2015-09-02 Time   Rev Time 0.00
Received By pleduc Date 2015-09-02 Time 08:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-08-21 Cont ID  
Sent By pleduc Date 2015-08-21 Time   Rev Time 0.00
Received By pleduc Date 2015-08-21 Time 11:53 Sent To  
Notes
2015-08-21 12:02:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS SUBMITTAL ONLY CONTAINED TWO - 1 SHEET DRAWINGS
 AND DID NOT ADDRESS THE NOTED CONCERNS ON THE 1ST
 SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By pleduc Date 2015-06-23 Time   Rev Time 0.00
Received By pleduc Date 2015-06-23 Time 09:10 Sent To  
Notes
2015-06-23 10:06:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A1.1 ON THE A1 DEMOLITION PLAN INDICATES A
 DOOR BEING REMOVED. PLEASE PROVIDE THE OCCUPANCY OF THE
 SPACE THAT THE DOOR LEADS TO AND A NOTE JUSTIFYING THAT
 THIS DOOR IS NOT REQUIRED FOR THAT SPACE.
  
 2) SHEET A1.1 ON THE ON THE A1 DEMOLITION PLAN
 INDICATES A DOUBLE DOOR BEING REMOVED; G8 FLOOR PALN
 INDICATES A NEW SINGLE DOOR BEING INSTALLED. PLEASE
 PROVIDE THE OCCUPANY AND OCCUPANCY LOAD OF THE SPACE
 THAT THIS DOOR LEADS TO.
  
 3) PROVIDE COMPLETE LIFE SAFETY PLANS FOR EACH
 OCCUPANCY THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON REVIEW OF THE
 ABOVE RESUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-01 Cont ID  
Sent By albarran Date 2015-10-01 Time 16:08 Rev Time 0.00
Received By albarran Date 2015-10-01 Time 12:54 Sent To B
Notes
2015-10-01 16:10:2110/1/15 PASSED REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL.
 SENT TO LARGE READY BIN "H". MA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-18 Cont ID  
Sent By pleduc Date 2015-09-02 Time 13:14 Rev Time 0.00
Received By skennedy Date 2015-08-28 Time 12:48 Sent To  
Notes
2015-08-28 12:48:32JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 15:26 Rev Time 0.00
Received By skennedy Date 2015-08-19 Time 13:10 Sent To  
Notes
2015-08-19 13:10:53ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-16 Cont ID  
Sent By tklarge Date 2015-07-16 Time 11:33 Rev Time  
Received By tklarge Date 2015-06-15 Time   Sent To  
Notes
2015-06-17 14:32:06B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2015-06-24 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-09 Cont ID  
Sent By ccole Date 2015-07-09 Time 15:52 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-16 Cont ID  
Sent By tklarge Date 2015-07-16 Time 11:33 Rev Time 0.00
Received By tklarge Date 2015-07-16 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-07-14 Cont ID  
Sent By aaponte Date 2015-07-14 Time 15:55 Rev Time 0.00
Received By aaponte Date 2015-07-14 Time 15:55 Sent To  
Notes
***NONE***