Plan Review Details - Permit 15060641
Plan Review Stops For Permit 15060641
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2015-07-22 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By albarran Date 2015-07-21 Time 18:59 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 18:34 Sent To B
Notes
2015-07-06 19:03:40THE FOLLOWING ITEMS NEED TO BE PROVIDED FOR A
 SUCCESSFUL ELECTRICAL PLAN REVIEW:
 1. YOU WILL NEED TO PROVIDE SUPPLEMENTAL INFORMATION
 INDICATING THE LOCATION OF THE OCPD FOR THESE LIGHTS.
 2. THE SPEC SHEET FOR THE BOLLARD PATH LIGHT OR THE
 POLE LIGHT DIDN'T UPLOAD CLEARLY TO VIEW THE LOAD OF
 THESE LUMINARIES.
 3. COMPLIANCE W/FBC-ENERGY CONSERVATION CODE IS
 REQUIRED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-26 Cont ID  
Sent By cpuell Date 2015-08-26 Time 12:16 Rev Time 0.00
Received By cpuell Date 2015-06-15 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-06-15 Cont ID  
Sent By cpuell Date 2015-06-15 Time 10:45 Rev Time 0.00
Received By cpuell Date 2015-06-15 Time 10:45 Sent To  
Notes
2015-06-15 10:45:56APPROVED UNDER 15060641

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-19 Cont ID  
Sent By avann Date 2015-08-19 Time 11:32 Rev Time 0.00
Received By ajones Date 2015-08-19 Time 11:32 Sent To  
Notes
***NONE***