| 2015-06-20 15:33:52 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| | PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. |
| | |
| | 2) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | |
| | 3) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL |
| | (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| | SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | (1) BATHROOMS |
| | |
| | 4) INSTALL OR VERIFY EXISTING SMOKE AS REQUIRED FOR NEW |
| | CONSTRUCTION. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |