| 2015-07-06 09:23:52 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060563 CENTRIFUGE DEWATERING |
| | BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY06/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID. |
| | |
| | 1) THE SUBMITTED PLANS FOR THE CENTRIFUGE DEWATERING |
| | BUILDING ARE MISSING PLANS ACCORDING TO THE INDEX. |
| | MISSING FROM THIS REVIEW ARE SHEETS: |
| | A-DEW-29 |
| | |
| | PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02 |
| | THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO |
| | USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS |
| | DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING |
| | TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | |
| | 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE |
| | G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS, |
| | THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE |
| | CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION. |
| | |
| | 3) THIS BUILDING WILL REQUIRE A THRESHOLD INSPECTOR, |
| | OVER 50 FEET IN HEIGHT. |
| | THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 3F) NOTICE! NO ACTION REQUIRED FOR PLAN REVIEW. FOR |
| | DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE |
| | PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT |
| | LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS |
| | OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE.. |
| | |
| | 3G) NOTICE NO ACTION IS REQUIRED FOR PLAN REVIEW. |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3H) NOTICE NO ACTION IS REQUIRED FOR PLAN REVIEW. |
| | 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | 4) SHEET 0394-A-DEW-01: |
| | 4A) CONSTRUCTION TYPE- TYPE I-B -UNPROTECTED, PLEASE |
| | NOTE TABLE 601 DOES REQUIRE 1,2, OR 3 HOUR FIRE |
| | PROTECTION OF STRUCTURAL MEMBERS ALSO SEE FOOTNOTES |
| | |
| | 4B) CONSTRUCTION TYPE- TYPE I-B SPRINKLERED PER FBC-B |
| | 602.2 - 602.2 HAS NOTHING TO DO WITH FIRE SPRINKLERS, |
| | IT DEALS WITH BUILDING ELEMENTS OF NON-COMBUSTIBLE |
| | MATERIALS AND ALLOWABLE USE OF FIRE-RETARDANT TREATED |
| | WOOD FRAMING. |
| | |
| | 5) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| | 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| | FORMS. SEE TABLE 103.2.1. PLANS ARE MISSING THE |
| | REQUIRED INSULATION BY THE 2010 FBC-ENERGY 502 BUILDING |
| | ENVELOPE REQUIREMENTS OR 506 TOTAL BUILDING |
| | PERFORMANCE. |
| | |
| | 6) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS & ROOF HATCH. |
| | (B) WINDOW |
| | (C), WALL LOUVERS, EFIS SYSTEMS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) SHEET 0312- S-DEW-06 PRESSURES FOR COMPONENTS AND |
| | CLADDING EXPOSURE "C" @ 180 MPH, 60 FT. ABOVE GRADE, |
| | ARE LOW FOR BOTH THE ROOF ZONES AND WALL ZONES. |
| | MULTIPLIER OF 1.62 FOR HEIGH FOR VULT PRESSURES. PLEASE |
| | ALSO SUPPLY PRESSURES IN VASD SINCE ALL PRODUCT |
| | APPROVALS ARE IN VASD. |
| | |
| | 9) SHEET 365-A-GEN-02 WAS INCLUDED IN THIS PERMIT |
| | PACKAGE DOOR SCHEDULES BUT NOT FOR THE CENTRIFUGE |
| | DEWATERING BUILDING, NOT ON ANY OF THE BUILDING |
| | SCEDULES. |
| | 107.3.5.1.1 (4 & 7) DOOR SCHEDULE- PROTECTION OF |
| | OPENINGS, MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. |
| | |
| | 10) SHEET 0364-A-DEW-01 DOES NOT PROVIDE A WALL LEGEND |
| | INDICATING THE RATING OF THE INTERIOR WALLS. |
| | 107.3.5.1.1 (4) MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS. FIRE-RESISTANT CONSTRUCTION |
| | REQUIREMENTS SHALL INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE RATING OF INTERIOR WALLS |
| | |
| | 11) SHEET 0364-A-DEW-01. THE CODE SHEET SHOWS THE 3 |
| | FLOORS OF THE BUILDING WITH VARIOUS WALLS IDENTIFIED AS |
| | RATED WALLS BUT THERE ARE NO WALL TAGS IDENTIFYING THE |
| | WALL TYPES FOR FIRE RESISTANCE RATING AND TYPE OF |
| | MATERIALS THEY WILL BE CONSTRUCTED. 107.3.5.1.1 (4) |
| | MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: FIRE RATING OF |
| | INTERIOR WALLS, |
| | |
| | INTERIOR VERTICAL EXIT ENCLOSURE FBC-B 1022.1. |
| | |
| | ELEVATOR MACHINE ROOM FBC-B 3006.4 |
| | |
| | THIRD FLOOR EXTERIOR WALL AT EXTERIOR STAIR FBC-B |
| | 1026.6 PROTECTION OF EXTERIOR STAIR PROTECTION. |
| | |
| | 12) ) PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B 713.6 |
| | FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | |
| | 13) SHEET 0410-A-DEW- 17 SHOWS FLOOR OPENINGS ON THE |
| | 2ND & 3RD FLOOR THAT ALLOW THE 3 FLOORS TO COMMUNICATE |
| | WITHOUT AND WITHOUT A SHAFT ENCLOSURE, PLEASE SHOW |
| | COMPLIANCE WITH 2010FBC-B 708.2 OR AN EXCEPTION. |
| | |
| | 1) SHEET 0419-A-DEW-26. DETAIL # 1 1ST FLOOR ACCESSIBLE |
| | BATHROOM. |
| | 14A) PLEASE PROVIDE THE DIMENSION FROM THE CENTERLINE |
| | OF THE WATERCLOSET TO THE FINISH OF THE CLOSEST |
| | INTERIOR WALL NOT THE CENTERLINE OF THE WALL, SHOW |
| | COMPLIANCE WITH 2010 FBC-ACCESIBLITY CODE 604.2 |
| | |
| | 14B) PLEASE PROVIDE DIMENSIONS SHOWING COMPLIANCE WITH |
| | 2010 FBC-ACCESSIBLITY CODE FIGURE 604.3.1. |
| | |
| | 14C) SHEET 0394-A-DEW-01 ONLY SHOWS AN ACCESSIBLE |
| | BATHROOM ON THE 1ST FLOOR. NEITHER THE 2ND FLOOR OR 3RD |
| | FLOOR INDICACATE COMPLIANCE WITH THE 2010 FL PLUMBING |
| | CODE DOES ALLOW TRAVEL DISTANCE OF ONE FLOOR TO REACH A |
| | RESTROOM AND OR BATHROOMS. 2010 FL ACCESS. 213.2 |
| | TOILET. |
| | |
| | 15) SHEET 0396- A-DEW- 03/05 OR 06 DO NOT PROVIDE A |
| | DRINKING AN ACCESSIBLE DRINKING FOUNTAIN. 2010 |
| | FBC-ACCESS. 211.2 MINIMUM NUMBER.NO FEWER THAN TWO |
| | DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | |
| | 16) SHEET 0409-A-DEW-16. NOTES THAT THE PRE-FABRICATED |
| | METAL CANOPY WILL BE DESIGNED BY A DELEGATE ENGINEER. |
| | PLEASE PROVIDE THE WIND DESIGN CRITERIA THAT THE CANOPY |
| | HAS TO BE DESIGNED TO. ASCE 7-10/ FBC-B 3105.5.1 LOADS. |
| | |
| | 17) SHEET 0409-A-DEW-16. SHOWS A EXTERIOR STAIR, |
| | GUARDRAI / HANDRAIL SYSTEM THERE IS A NOTE INDICATING |
| | SEE 4/ A-DEW-29, THIS IS A MISSING SHEET. NO PLAN |
| | REVIEW OF THE EXTERIOR STAIR CAN BE COMPLETED. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 18) SHEET 0409-A-DEW-16 SHOWS WINDOWS, DOORS AND WALL |
| | LOUVERS WITHIN 10 FT. OF THE STAIRS AND LANDINGS. |
| | PLEASE PROVIDE CODE COMPLIANCE WITH 1026.6. EXTERIOR |
| | STAIR PROTECTION. |
| | |
| | 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |