Plan Review Details - Permit 15060561
Plan Review Stops For Permit 15060561
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time   Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time   Sent To  
Notes
2016-05-13 15:20:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060561 SFOG ATTENDANT BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RDREVIEW
 DATE: FRI. MAY 13/ 2016
 ACTION: BUILDING PROVISO
  
 1A) BUILDING PROVISO/ DEFERRED SUBMITTAL. PLANS ARE
 MISSING 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS .
 (B) WINDOW
 (C), WALL LOUVERS, EFIS SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP
  
 1B) BUILDING PROVISO 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By jwitmer Date 2016-03-29 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2016-03-29 Time 16:03 Sent To  
Notes
2016-03-29 16:28:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060561 SFOG ATTENDANT BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. MARCH 29/ 2016
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID.
  
 1-3) COMPLIED.
  
 4) SEMI -COMPLIED. THE SHEET 0423-A-FOG-01 SEPTAGE FOG
 ATENDANT BUILDING SHOWS WALL INSULATION BUT THE SHEET
 0425-A-FOG-03 V2 SHOWS A CUT SECTION THROUGH THE
 BUILDING ROOF THE TYPE OF INSULATION, THICKNESSNOR
 R-VALUE ARE NOT GIVEN.
 MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY 103.2
 ENERGY REPORTING FORMS. INFORMATION ON CONSTRUCTION
 DOCUMENTS. 103.2.1 CODE DEMONSTRATION FORMS. SEE TABLE
 103.2.1.
  
 5) SEMI-COMPLIED. THE SHEET 0423-A-FOG-01 SEPTAGE FOG
 ATENDANT BUILDING SHOWS WALL INSULATION BUT THE SHEET
 0425-A-FOG-03 V2 SHOWS A CUT SECTION THROUGH THE
 BUILDING ROOF THE TYPE OF INSULATION, THICKNESS ARE NOT
 GIVEN. PLANS ARE MISSING THE REQUIRED INSULATION BY THE
 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR
 506 TOTAL BUILDING PERFORMANCE.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTAL. PLANS ARE
 MISSING 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS .
 (B) WINDOW
 (C), WALL LOUVERS, EFIS SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP
  
 7) BUILDING PROVISO 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 09:24 Sent To  
Notes
2015-07-27 09:25:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060561 SFOG ATTENDANT BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JULY 27/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID.
  
 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02
 THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO
 USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS
 DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING
 TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE
 G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS,
 THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE
 CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION.
  
 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR.
 PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS
 SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS E-MAILED TO: [email protected] THURS.
 JULY 02/2015 07:25 AM.
  
 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected] OR [email protected]
  
 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected] OR [email protected]
  
 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST
 PALM BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED
 IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT
 ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT
 THAT POINT.
  
 4) 0423-A-FOG-01 SEPTAGE FOG ATENDANT BUILDING
 48) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY
 103.2 ENERGY REPORTING FORMS. INFORMATION ON
 CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION
 FORMS. SEE TABLE 103.2.1.
  
 5) PLANS ARE MISSING THE REQUIRED INSULATION BY THE
 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR
 506 TOTAL BUILDING PERFORMANCE.
  
 6) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS .
 (B) WINDOW
 (C), WALL LOUVERS, EFIS SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET 0331-S-FOG-05 PRESSURES FOR COMPONENTS AND
 CLADDING EXPOSURE "C" @ 180 MPH, 17 FT ABOVE GRADE,ARE
 LOW FOR BOTH THE ROOF ZONES AND WALL ZONES. MULTIPLIER
 OF 1.29 FOR HEIGHT.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-08 Cont ID  
Sent By dharvey Date 2015-12-08 Time 08:36 Rev Time 0.00
Received By dharvey Date 2015-12-08 Time 08:16 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By cranford Date 2015-07-24 Time 09:41 Rev Time 0.00
Received By cranford Date 2015-07-24 Time 09:41 Sent To  
Notes
2015-07-24 09:41:31JOHN ROACH VERIFIED APPLICATION WAS CONSISTENT WITH
 APPROVED SITE PLAN. SITE PLAN APPROVAL LETTER NOT YET
 DRAFTED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By cranford Date 2015-06-30 Time 08:37 Rev Time 0.00
Received By cranford Date 2015-06-30 Time 08:36 Sent To  
Notes
2015-06-30 08:37:31FOR SFOR ATTENDANT BLDG
  
 1. PLEASE SUBMIT A COPY OF THE APPROVED SITE PLAN
 (Z14080026). WHEN SITE PLAN REVIEW IS REQUIRED, REVIEW
 AND APPROVAL ARE NECESSARY PRIOR TO ISSUANCE OF A
 BUILDING PERMIT. [SECTION 94-35(G) OF THE CITY'S CODE
 OF ORDINANCES]
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-23 Cont ID  
Sent By wjolin Date 2015-06-23 Time 16:06 Rev Time 0.00
Received By wjolin Date 2015-06-23 Time 15:13 Sent To  
Notes
2015-06-23 16:06:204395 EASLEY DRIVE - SFOG ATTENDANT BUILDING
 PERMIT #15060561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE
 BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE
 STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3)
 PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON
 CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200
 A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING
 DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A
 PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS
 FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE
 NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL
 OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH
 PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE
 NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE.
 CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT
 IS NOT RATED 1200 A OR MORE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 08:26 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2016-04-25 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-04 Cont ID  
Sent By lmarchan Date 2016-04-04 Time 11:22 Rev Time 0.00
Received By lmarchan Date 2016-03-22 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-08 Cont ID  
Sent By dharvey Date 2015-12-08 Time 08:36 Rev Time 0.00
Received By dharvey Date 2015-06-17 Time 14:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-06-06 Cont ID  
Sent By skennedy Date 2016-06-06 Time 15:37 Rev Time 0.00
Received By skennedy Date 2016-06-06 Time 15:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 09:19 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 09:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 08:26 Rev Time 0.00
Received By ccole Date 2016-05-24 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-05-06 Cont ID  
Sent By ccole Date 2016-05-06 Time 13:39 Rev Time 0.00
Received By ccole Date 2016-05-06 Time 12:55 Sent To  
Notes
2016-05-06 13:47:353RD REVIEW: FBC 2014 MECHANICAL
 BIO-SOLIDS PERMIT #15060561
 5/6/16
  
 1) THE ENGINEER'S RESPONSE REFERENCES SHEET H-SEQ-01
 FOR REVIEW OF AC AND O/A CONTROL SEQUENCES, HOWEVER THE
 SHEET IS NOT INCLUDED IN THE PLAN SETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-31 Cont ID  
Sent By ccole Date 2016-03-31 Time 11:01 Rev Time 0.00
Received By ccole Date 2016-03-31 Time 11:01 Sent To  
Notes
2016-03-31 11:10:012ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060561
 3/31/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 OFFICE AND STORAGE ROOMS PER TABLE 403.3 FBC-10
 MECHANICAL, AND INDICATE HOW THE O/A SUPPLY WILL BE
 CONTROLLED IN ACCORDANCE WITH SECTION 503.2.5.4 FBC-10
 ENERGY CONSERVATION.
 2) PROVIDE A DS (DUCT SMOKE DETECTOR) SYMBOL IN THE
 MAIN SUPPLY PLENUM OF AC-2
 3) PROVIDE WIND-LOAD TIE DOWN ENGINEERING FOR FOR THE
 ROOFTOP AC-2, EF-1, AND THE GROUND-MOUNTED ACCU-1: SEE
 SECTION 301.12 FBC-10 MECHANICAL.
 4) PROVIDE AN INSTALLATION DETAIL FOR THE
 CEILING-MOUNTED AC-1 UNIT IN THE ELECTRICAL ROOM
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-05 Cont ID  
Sent By ccole Date 2015-08-05 Time 07:39 Rev Time 0.00
Received By ccole Date 2015-08-05 Time 07:39 Sent To  
Notes
2015-08-05 07:42:371ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060561 SFOG ATTENDANT BUILDING
 8/5/15
  
 1) THE HVAC PLANS FOR THE BUILDING WERE NOT UPLOADED
 FOR REVIEW: PLEASE PROVIDE THE PLANS.
 2) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 3) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 4) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 10:40 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By tklarge Date 2015-07-27 Time 06:51 Rev Time 0.00
Received By tklarge Date 2015-07-27 Time 06:05 Sent To  
Notes
2015-07-27 06:22:281) SUBMIT A SCUPPER & OVERFLOW SCUPPER DETAIL WITH
 THESE PLANS. THE SCUPPER SHALL BE INSTALLED AND LOCATED
 IN ACCORDANCE WITH 2010 FBC SEC.1503.4.2 AND THE
 OVERFLOW SHALL BE INSTALLED AND LOCATED PER
 SEC.1503.4.2.1. SHT.0424-A-FOG-2 NOTE # 2 INDICATES THE
 OVERFLOW SCUPPER TO BE LOCATED 3" ABOVE PRIMARY
 SCUPPER.
 2) THE DRAINAGE CALCULATIONS FOR THE SIZING OF THE
 SCUPPERRS SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALL THAT DIVERTS RAINWATER TO THE ROOF PER 2010 FPC
 SEC.1106.4. INDICATE THIS SQUARE FOOTAGE IN THE ROOF
 DRAINAGE CALCULATION.
 3) SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH TABLE
 1106.7.
 4) SUBMIT A SANITARY AND WATER RISER FOR REVIEW. WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 5) SUBMIT ALL DRAWINGS APPLICABLE FOR THIS PORTION OF
 THE PROJECT. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) INDICATE THE HEIGHT OF THE SCUPPER HEAD DESIGN PER
 TABLE 1106.7 OF 2010 FPC.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-06-06 Cont ID  
Sent By skennedy Date 2016-06-06 Time 15:27 Rev Time 0.00
Received By skennedy Date 2016-06-06 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-09-08 Cont ID  
Sent By jroach Date 2015-09-08 Time 13:46 Rev Time 0.00
Received By jroach Date 2015-09-08 Time 13:46 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved