Plan Review Details - Permit 15060554
Plan Review Stops For Permit 15060554
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-25 Cont ID  
Sent By jwitmer Date 2016-03-25 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2016-03-25 Time 12:15 Sent To  
Notes
2016-03-25 12:41:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060554 WASTE GAS BURNER
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: FRI. MARCH 25/ 2016
 ACTION: BUILDING PROVISO
  
 1) SHEET 0298 M-ADF-39 WHEN MEASURED SCALES ABOUT 12.4
 FEET ABOVE THE FLANGE #150. PLEASE PROVIDE ADDITIONAL
 INFORMATION IF THE SCHEDULE 5S SST PIPE WILL REQUIRE
 LATERAL RESISTING SYSTEM FOR THE HEIGHT OF THE PIPE AS
 WELL FOR THE WIND DESIGN OF 180 MPH.
  
 LATERAL FORCE-RESISTING SYSTEM 2010 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 THE DESIGNER OF RECORD IN THE COMMENT RESPONSE DOES
 PROVIDE THE WIND DESIGN CRITERIA AND THE GAS BURNER
 MANUFACTURER WILL BE SUBMITTING CALCULATIONS WITH SHOP
 DRAWINGS DEMONSTRTING COMPLIANCE WITH THE REQUIRED 180
 VULT WIND LOADS.
  
 BEFORE SHOP DRAWINGS ARE TO BE SUBMITTED THE ENGINEER
 OF RECORD FOR REVIEW AND APPROVAL BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-15 Cont ID  
Sent By jwitmer Date 2016-01-15 Time 06:49 Rev Time 0.00
Received By jwitmer Date 2016-01-12 Time 14:14 Sent To  
Notes
2016-01-15 06:49:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060554 WASTE GAS BURNER
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. JAN. 15/ 2016
 ACTION: DENIED
  
 1) SHEET 0298-S-ADF-32 SHOWS A ELEVATION OF THE WASTE
 GAS BURNER. BOTH DETAILS A & B SHOW THE WASTE GAS
 BURNER PIPE CUT OFF AND THE TOTAL HEIGHT OF
 THE BURNER IS NOT PROVIDED. SHEET 0298 M-ADF-39 WHEN
 MEASURED SCALES ABOUT 12.4 FEET ABOVE THE FLANGE #150.
 PLEASE PROVIDE ADDITIONAL INFORMATION IF THE SCHEDULE
 5S SST PIPE WILL REQUIRE LATERAL RESISTING SYSTEM FOR
 THE HEIGHT OF THE PIPE AS WELL FOR THE WIND DESIGN OF
 180 MPH.
  
 LATERAL FORCE-RESISTING SYSTEM 2010 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 2) 2010 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 09:15 Sent To  
Notes
2015-07-27 09:17:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060554 WASTE GAS BURNER
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JULY 27/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID.
  
 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02
 THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO
 USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS
 DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING
 TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE
 G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS,
 THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE
 CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION.
  
 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR.
 PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS
 SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS E-MAILED TO: [email protected] THURS.
 JULY 02/2015 07:25 AM.
  
 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected] OR [email protected]
  
 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected] OR [email protected]
  
 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST
 PALM BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED
 IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT
 ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT
 THAT POINT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-26 Cont ID  
Sent By dharvey Date 2016-02-26 Time 16:29 Rev Time 0.00
Received By dharvey Date 2016-02-26 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By dharvey Date 2015-12-07 Time 13:33 Rev Time 0.00
Received By dharvey Date 2015-12-07 Time 13:05 Sent To I
Notes
2015-12-07 13:33:14PAGE (FILE) 0479-E-GEN-02.PDF - CONNECTED LOAD AND
 DEMAND LOAD APPEAR TO EXCEED BUS RATING AND 80% OF
 DEMAND (CONTINUOUS) LOAD. PLEASE EXPLAIN
 BUS IS RATED 2000A. CONNECTED LOAD IS 3100 AND DEMAND
 LOAD LOAD IS 1700, GREATER THAN 80%. IS BUS RATED FOR
 CONTINUOUS DUTY?
 IDENTIFY ZONES THAT WILL NEED TO BE DELINEATED FOR
 HAZARDOUS (ELECTRICAL) ZONE OR CLASS AND DIVISION WITH
 THE SPECIFIC HAZARD (METHANE, CHLORINE, ETC.)

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By cranford Date 2015-07-24 Time 09:52 Rev Time 0.00
Received By cranford Date 2015-07-24 Time 09:52 Sent To  
Notes
2015-07-24 09:52:22JOHN ROACH VERIFIED APPLICATION WAS CONSISTENT WITH
 APPROVED SITE PLAN. SITE PLAN APPROVAL LETTER NOT YET
 DRAFTED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By cranford Date 2015-06-30 Time 08:35 Rev Time 0.00
Received By cranford Date 2015-06-30 Time 08:35 Sent To  
Notes
2015-06-30 08:35:44FOR WASTE GASE BURNERS
  
 1. PLEASE SUBMIT A COPY OF THE APPROVED SITE PLAN
 (Z14080026). WHEN SITE PLAN REVIEW IS REQUIRED, REVIEW
 AND APPROVAL ARE NECESSARY PRIOR TO ISSUANCE OF A
 BUILDING PERMIT. [SECTION 94-35(G) OF THE CITY'S CODE
 OF ORDINANCES]
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-25 Cont ID  
Sent By wjolin Date 2015-06-25 Time 14:09 Rev Time 0.00
Received By wjolin Date 2015-06-25 Time 14:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-01-15 Cont ID  
Sent By tklarge Date 2016-01-15 Time 09:50 Rev Time 0.00
Received By tklarge Date 2016-01-15 Time 09:49 Sent To  
Notes
2016-01-15 09:50:11PASSED WITH PROVISOS
  
 GAS PROVISOS -
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.) TYPE OF GAS (LP OR NATURAL).
  
 4.)TU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.
  
 9) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 10.) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11.) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO THE CHIEF PLUMBING INSPECTOR AT
 561-805-6692.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-25 Cont ID  
Sent By jwitmer Date 2016-03-25 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-26 Cont ID  
Sent By dharvey Date 2016-02-26 Time 16:29 Rev Time 0.00
Received By dharvey Date 2016-01-06 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-07 Cont ID  
Sent By cpuell Date 2015-12-07 Time 16:17 Rev Time 0.00
Received By cpuell Date 2015-06-17 Time 14:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-14 Cont ID  
Sent By ccole Date 2016-01-14 Time 17:07 Rev Time 0.00
Received By ccole Date 2016-01-14 Time 17:07 Sent To  
Notes
2016-01-14 17:14:47MECHANICAL PROVISOS:
 PERMIT #15060554
 01/14/1
 1) SHOP DRAWINGS AND WIND LOAD TIE DOWN ENGINEERING FOR
 THE WASTE GAS BURNER AND ASSOCIATED PIPING AND
 EQUIPMENT SHALL BE REVIEWED AND APPROVED BY THE EOR AND
 SUBMITTED TO THE BUILDING DEPARTRMENT PRIOR TO 1ST
 INSPECTION.
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By ccole Date 2015-08-04 Time 10:57 Rev Time 0.00
Received By ccole Date 2015-08-04 Time 10:57 Sent To  
Notes
2015-08-04 11:11:251ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060554 WASTE GAS BURNERS
 8/3/15
  
 1) REFER TO SECTION 301.12 FBC-10 MECHANICAL: THE WASTE
 GAS BURNER AND ALL OTHER ASSOCIATED EQUIPMENT SHALL BE
 DESIGNED AND INSTALLED TO WITHSTAND 170 MPH WIND LOADS
 AS OUTLINED IN SECTION 1609 FBC-10 BUILDING. PLEASE
 PROVIDE THE WINDLOAD DESIGN CRITERIA ON THE PLAN AND
 INSTALLATIOMN DETAILS AND NOTES TO SHOW COMPLIANCE.
 2) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 3) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 4) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-15 Cont ID  
Sent By tklarge Date 2016-01-15 Time 09:47 Rev Time 0.00
Received By tklarge Date 2016-01-15 Time 06:38 Sent To  
Notes
2016-01-15 09:47:05GAS PROVISOS -
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO THE CHIEF PLUMBING INSPECTOR AT
 561-805-6692.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-26 Cont ID  
Sent By tklarge Date 2015-07-26 Time 09:40 Rev Time 0.00
Received By tklarge Date 2015-07-26 Time 08:48 Sent To  
Notes
2015-07-26 09:00:221) SUBMIT ALL DRAWINGS RELATED TO THIS PORTION OF THE
 PROJECT.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT.0142-M-ADF-09 REFERS TO SHT. M-ADF-31 FOR
 INFORMATION ON THE PROPANE TANK/PIPING. SUBMIT THIS
 DRAWING FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) SUBMIT COMPLETE PLANS FOR THE LP TANK & PIPING
 SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SHT.0766-M-STD-09 - DETAIL # 1542102 - THE WYE SHALL
 BE INSTALLED IN THE DIRECTION OF FLOE. REVISE THE
 DETAIL. 2010 FPC SEC. 706.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By skennedy Date 2016-04-11 Time 11:21 Rev Time 0.00
Received By skennedy Date 2016-04-11 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-09-08 Cont ID  
Sent By jroach Date 2015-09-08 Time 13:46 Rev Time 0.00
Received By jroach Date 2015-09-08 Time 13:46 Sent To  
Notes
***NONE***