Plan Review Details - Permit 15060551
Plan Review Stops For Permit 15060551
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-12 Cont ID  
Sent By jwitmer Date 2015-11-12 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2015-11-12 Time 07:44 Sent To  
Notes
2015-11-12 08:28:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 4TH REVIEW
 DATE: THURS. NOV. 12/ 2015
 ACTION: BUILDING PROVISO
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1-6) COMPLIED.
  
  
 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
  
 EXPOSURE "C" @ 180 MPH, 25 FT ABOVE GRADE
 0365-A-ADF-02 BOILER GAS HANDLING BUILDING
 0382-A-ADF-04 FLOOR PLAN
 0386-A-ADF-08 ROOF PLAN
 0390-A-ADF-12 ELEVATIONS
 0391-A-ADF-13 ELEVATIONS
 0281-S-ADF-15 FOUNDATION
 0284-S-ADF-18 ROOF & PRESSURES
 0287-S-ADF-21 SECTIONS
 0365-A-GEN-02 DOOR SCHEDULE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-20 Cont ID  
Sent By jwitmer Date 2015-10-20 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2015-10-20 Time 08:25 Sent To  
Notes
2015-10-20 08:45:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. OCT. 09/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1-5) COMPLIED.
  
 6) 3RD. REQUEST.
  
 6A) THE RESPONSE COMMENTS INDICATE THE ROOF PRESSURES
 ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN THIS
 PERMIT PACKAGE. SHEET 0283 THEN JUMPS TO 0286. RESPONSE
 INDICATE THIS IS FOR T1 & T2 SLUDGE PUMPING ROOF? THIS
 IS FOR THE M1-M4 SLUDGE PUMPING & BOILER/ GAS HANDILING
 BUILDING.
 0386-A-ADF-08 BUILT -UP ROOF W/ 4 INCHES OF INSULATION/
 EXHAUST FANS & ROOF CURBS FOR EXHAUST FANS AS WELL AS
 ROOF TOP RTU'S.
 NOTE OVER A 3'-0" PARAPET ZONE 3 PRESSURES ARE TO BE
 THE SAME AS ZONE 2 PRESSURES. COMPONENTS AND CLADDING
 2010 FBC-B 1609.3/ TABLE 1609.2(2).
  
 6B) THE RESPONSE TO WHERE THE DOOR PRESSURES ARE FOUND
 IS ON SHEET 0365-A-GEN.01. THE WALL PRESSURES ARE IN
 VULT, IT IS ASSUMED THAT THE PRESSURES GIVEN ARE FOR
 THE SQUARE FOOTAGE OF THE OPENING. THEY ARE LOW AND ARE
 FOR WALL ZONE NUMBER 4 THE INTERIOR ZONE, THE PRESSURES
 FOR 180 VULT. APPEAR TO BE FOR EXPOSURE B AT A MEAN
 ROOF HEIGHT OF 25 FT. TABLE 1609.7.2 HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENT.
  
 6C) THE DOOR SCHEDULE FOUND ON SHEET 0365-A-GEN.02 DOES
 IDENTIFY THE DOORS BY NUMBERS, ON WHICH SHEET DO WE
 LOOK TO VERIFY THE LOCATION OF THE DOORS TO SEE IF THEY
 ARE IN ZONE 4 OR END ZONE 5. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO DETRMINE WALL ZONE 4 OR WALL
 ZONE 5.
  
 6D) PLEASE PROVIDE WHERE THE WALL LOUVER PRESSURES CAN
 BE LOCATED TO VERIFY COMPLIANCE WITH PRESSURES. )
 COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-11) COMPLIED.
  
 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO :
 EXPOSURE "C" @ 180 MPH, 25 FT ABOVE GRADE,@ 10 SQ. FT.
 :
 VULT FOR ROOF, ZONE 1 -78.70 , ZONE 2 -132.03 & ZONE 3
 -132.03 (3 FT. PARAPET).
 VASD FOR ROOF, ZONE 1 -47.22. ZONE 2 -79.21 & ZONE 3
 -79.21 (3 FT. PARAPET).
  
 12B) COMPLIED.
  
 13) COMPLIED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 0365-A-ADF-02 BOILER GAS HANDLING BUILDING
 0382-A-ADF-04 FLOOR PLAN
 0386-A-ADF-08 ROOF PLAN
 0390-A-ADF-12 ELEVATIONS
 0391-A-ADF-13 ELEVATIONS
 0281-S-ADF-15 FOUNDATION
 0284-S-ADF-18 ROOF
 0287-S-ADF-21 SECTIONS
 0365-A-GEN-02 DOOR SCHEDULE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-09 Cont ID  
Sent By jwitmer Date 2015-10-09 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2015-10-09 Time 06:45 Sent To  
Notes
2015-10-09 07:00:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. OCT. 09/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1) RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER
 ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE
 COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON
 THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE
 COMMENT RESPONSE.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 1ST REVIEW COMMNETS. PLEASE EITHER REMOVE THE INDEX
 SHEETS 0002-6-GEN.02 THROUGH 0005-6-GEN.05 OR VOID THEM
 OUT THEY ARE OF NO USE TO THIS PROJECT THE WAY IT WAS
 SUBMITTED. THE PLANS DO NOT FOLLOW THE INDEX BEING
 BROUGHT IN BY BUILDING TYPES. 107.2.1.4 QUALITY OF
 BUILDING PLANS.
  
 2-5) COMPLIED.
  
  
  
  
 6) 2ND REQUEST. THE RESPONSE COMMENTS INDICATE THE ROOF
 PRESSURES ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN
 THIS PERMIT PACKAGE. THE RESPONSE TO WHERE THE WINDOW
 AND POOR PRESSURES ARE FOUND IS ON SHEET 0364-A-GEN.01
 THE REMAINDER OF THE RESPONSE IS CUT OFF. THIS SHEET
 DOES SHOW WALL PRESSUREES FOR THESE WINDOW TYPES, BUT
 THEY CAN ONLY BE ASSUMPTIONS. THE PROBLEM WE HAVE AS
 PLAN REVIEWERS AND INSPECTORS IS THE LIMITED AMOUNT OF
 TIME TO FIND DOCUMENTATION. WHEN THE WIND DESIGN
 CRITERIA IS NOT GIVEN ON THE SAME PAGE WE ARE ONLY
 MAKING A ASSUMPTION, IS THE DESIGN TO 170 OR 180 MPH,
 EXPOSUSRE B OR C , THE MEAN ROOF HEIGHT OF THE BUILDING
 ARE THE PRESSURES REPRESENTED VULT OR VASD.
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1ST REVIEW COMMENT.PLEASE PROVIDE WHERE THE PRESSURES
 FOR COMPONENTS & CLADDING CAN BE FOUND. SHEET
 0283-S-ADF-17 T1 & T2 SLUDGE PUMPING ROOF PLAN DOES NOT
 PROVIDE THE PRESSURES FOR ROOF ZONES 1,2,3 NOR THE WALL
 ZONES 4 & 5.
  
  
 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-11) COMPLIED.
  
 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO :
 EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE, VASD FOR
 ROOF, ZONE 1 -40.40, ZONE 2 -67.76 & ZONE 3 -101.9.
  
 1ST REVIEW. SHEET 0284-S-ADF-18 PRESSURES FOR
 COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 20 FT
 ABOVE GRADE, VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE
 PRESSURES AT 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 2010 FBC-B
 1609.6.4.41 COMPONENTS & CLADDING
  
 12B). RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER
 ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE
 COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON
 THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE
 COMMENT RESPONSE.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 1ST REQUEST. SHEET 0284-S-ADF-01 THRU -S-ADF- 40 NO
 PRESSURES FOR THE DOOR OPENINGS ARE NOT PROVIDED FOR
 THIS BUILDING. 2010 FBC-B 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING.
  
 13) COMPLIED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-13 Cont ID  
Sent By jwitmer Date 2015-07-13 Time 09:58 Rev Time  
Received By jwitmer Date 2015-07-13 Time   Sent To  
Notes
2015-07-13 09:50:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JULY06/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02
 THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO
 USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS
 DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING
 TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE
 G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS,
 THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE
 CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION.
  
 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR.
 PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS
 SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS E-MAILED TO: [email protected] THURS.
 JULY 02/2015 07:25 AM.
  
 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected] OR [email protected]
  
 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected] OR [email protected]
  
 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST
 PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED
 IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT
 ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT
 THAT POINT.
  
 4) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, HAS A
 HEADING FOR FOUNDATION WORK BUT THERE IS NO CRITERIA
 LISTED FOR THE SOILS INVESTIGATION REPORT, DATE AND
 COMPANY COMPLETEING THE SOILS INVESTIGATION. 2010 FBC-B
 1803.5.2. FOUNDATION NOTE F-2 PROVIDES THE ALLOWABLE
 SOILS BEARING PRESSURES BUT THERE IS NO DOCUMENTATION
 OF A SOILS ANALYSIS AND EVALUATION EVER TAKING PLACE.
  
 5) PLEASE NOTE THAT A COPY OF DUNKELBERGER TESTING
 REPORT HD145002 APRIL 10, 2014 WAS SUBMITTED BY E-MAIL
 FOR REVIEW. THIS REPORT WILL NEED TO EITHER HAVE A HARD
 COPY SIGNED AND SEALED OR THE ELECTRONIC PEDDS
 SIGNATURE FOR ELECTRONIC VERSIONS OF THIS DOCUMENT.
  
 5A) DUNKELBERGER TESTING REPORT HD145002 APRIL 10,
 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION
 VIBRO-COMPACTION FOR THE PROJECT SHOULD BE CARRIED OUT
 BY AN EXPERIENCED CONTRACTOR EMPLOYING A GROUND
 IMPROVEMENT PLAN THAT HE/SHE PREPARES. THE PLAN SHOULD
 UTILIZE CENTER-TO-CENTER SPACINGS FOR THE
 VIBRO-COMPACTION POINTS THAT ARE NORMALLY USED IN
 GRANULAR SOILS TO ACHIEVE 80 PERCENT RELATIVE DENSITY.
 BEFORE ADOPTION, THE GROUND IMPROVEMENT PLAN SHOULD BE
 REVIEWED BY THE GEOTECHNICAL ENGINEER AND STRUCTURAL
 ENGINEER FOR CONFORMANCE WITH THE INTENT OF THE
 FOUNDATION DESIGN.
 PLEASE PROVIDE FOR REVIEW BY THE BUILDING DEPARTMENT
 FOR COMPLIANCE.
  
 5B) DUNKELBERGER TESTING REPORT HD145002 APRIL 10,
 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION
 RECOMENDS THE EXCAVATED FILL FOR ALL OF THE DIGESTOR
 TANKS NOT BE RE-USED, WILL THIS FILL BE USED ELSE WHERE
 ON SITE FOR FILL, AND IF SO STORED WHERE, A CONCERN AS
 TO THE CLOSENESS OF FILL STORED TO THE EXCAVATION OF
 THE DIGESTORS AND OR OTHER STRUCTURES. 2010 FBC-B
 3304.1.2 SURCHARGE & 1808.7 FOUNDATIONS ON OR ADJACENT
 TO SLOPES.
  
 5C) DUNKELBERGER TESTING REPORT HD145002 APRIL 10,
 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION
 RECOMENDS
 ADD FILL USED IN THE COMPACTION POINTS SHOULD CONSIST
 OF CLEAN SANDS HAVING A SUITABILITY NUMBER (SN) OF 20
 OR LOWER. WE DO NOT BELIEVE THAT THE ON-SITE SANDS WILL
 MEET THIS REQUIREMENT. THEREFORE THE ADD FILL WILL NEED
 TO BE IMPORTED. PLEASE INCORPORATE INTO THE VIBRO-
 FLOTATION PLAN.
  
 6) PLEASE PROVIDE WHERE THE PRESSURES FOR COMPONENTS &
 CLADDING CAN BE FOUND. SHEET 0283-S-ADF-17 T1 & T2
 SLUDGE PUMPING ROOF PLAN DOES NOT PROVIDE THE PRESSURES
 FOR ROOF ZONES 1,2,3 NOR THE WALL ZONES 4 & 5.
  
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) ADF ANAEROBIC DIGETION FACILITY. SHEET 0382-
 A-ADF-04 GAS HANDLING ROOM. PLEASE PROVIDE THE TYPE OF
 GAS TO BE HANDLED IN THIS ROOM, QUANITIES OF GAS TO BE
 USED & STORED IN THIS ROOM.
 MSDS SHEETS WERE SUBMITTED BUT NO INFORMATION WAS
 SUBMITTED WHERE THESE CHEMICALS WILL BE USED NOR
 STORED. IF QUANITIES OF CHEMICALS EXCEEDS THE AMOUNT IN
 2010 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITY
 PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A
 PHYSICAL HAZARDA, J, M, N, P. IF AMOUNTS OF CHEMICALS
 EXCEEDS THE ALLOWABLE AMOUNT IN TABLE 307.1(1) THEN
 EITHER ADDITIONAL CONTROL AREAS WOULD BE REQUIRED OR
 THIS PORTION OF THE BUILDING WILL NEED TO MEET THE
 REQUIREMENTS OF CHAPTER 414.
  
 10) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY
 103.2 ENERGY REPORTING FORMS. INFORMATION ON
 CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION
 FORMS. SEE TABLE 103.2.1.
  
 11) PLANS ARE MISSING THE REQUIRED INSULATION BY THE
 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR
 506 TOTAL BUILDING PERFORMANCE.
  
 12A) SHEET 0284-S-ADF-18 PRESSURES FOR COMPONENTS AND
 CLADDING EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE,
 VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE PRESSURES AT
 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 2010 FBC-B 1609.6.4.41
 COMPONENTS & CLADDING
  
 12B) SHEET 0284-S-ADF-01 THRU -S-ADF- 40 NO PRESSURES
 FOR THE DOOR OPENINGS ARE NOT PROVIDED FOR THIS
 BUILDING. 2010 FBC-B 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING.
  
 13) SHEET S-ADF-01 INDICATES THE ANAEROBIS DIGESTION
 FACILITY AND THE ANAEROBIS DIGESTION ELECTRIC BUILDING
 ARE WITHIN 10'=0" OF EACH OTHER. PLEASE PROVIDE ON THE
 ARCHITECTURAL SHEETS THE 2 BUILDING LOCATIONS AND AN
 ASSUMED PROPERTY LINE BETWEEN THE 2 BUILDINGS, PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-B TABLE 602
 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE.
 TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS
 BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING
 PROTECTION.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-18 Cont ID  
Sent By dharvey Date 2015-09-18 Time 08:11 Rev Time 0.00
Received By dharvey Date 2015-09-17 Time 15:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By cranford Date 2015-07-24 Time 09:56 Rev Time 0.00
Received By cranford Date 2015-07-24 Time 09:56 Sent To  
Notes
2015-07-24 09:56:28JOHN ROACH VERIFIED APPLICATION WAS CONSISTENT WITH
 APPROVED SITE PLAN. SITE PLAN APPROVAL LETTER NOT YET
 DRAFTED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By cranford Date 2015-06-30 Time 08:31 Rev Time 0.00
Received By cranford Date 2015-06-30 Time 08:30 Sent To  
Notes
2015-06-30 08:31:20FOR M-1 TO M-4 AND BOILER / GAS HANDLING BLDG
  
 1. PLEASE SUBMIT A COPY OF THE APPROVED SITE PLAN
 (Z14080026). WHEN SITE PLAN REVIEW IS REQUIRED, REVIEW
 AND APPROVAL ARE NECESSARY PRIOR TO ISSUANCE OF A
 BUILDING PERMIT. [SECTION 94-35(G) OF THE CITY'S CODE
 OF ORDINANCES]
  
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-25 Cont ID  
Sent By wjolin Date 2015-06-25 Time 13:24 Rev Time 0.00
Received By wjolin Date 2015-06-25 Time 13:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-11-10 Cont ID  
Sent By tklarge Date 2015-11-10 Time 11:52 Rev Time 0.00
Received By tklarge Date 2015-11-10 Time 11:52 Sent To  
Notes
2015-11-10 11:54:39A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE LP
 TANK AND LINE. TKL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-12 Cont ID  
Sent By jwitmer Date 2015-11-12 Time 08:34 Rev Time 0.00
Received By jwitmer Date 2015-11-04 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-30 Cont ID  
Sent By ccole Date 2015-10-30 Time 16:19 Rev Time 0.00
Received By ccole Date 2015-10-16 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By ccole Date 2015-10-14 Time 09:59 Rev Time 0.00
Received By ccole Date 2015-09-30 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-18 Cont ID  
Sent By lmarchan Date 2015-09-18 Time 09:36 Rev Time 0.00
Received By lmarchan Date 2015-06-17 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-11-10 Cont ID  
Sent By ccole Date 2015-11-10 Time 15:37 Rev Time 0.00
Received By ccole Date 2015-11-10 Time 15:37 Sent To  
Notes
2015-11-10 15:44:17BIO-SOLIDS PERMIT #15060551
 PROVISOS
 11/10/15
  
 1) SITE SPECIFIC WIND LOAD ENGINEERING FOR MOUNTING AND
 ANCHORING OF ALL EXTERIOR HVAC APPLIANCES, EQUIPMENT,
 AND CURBS SHALL BE REVIEWED AND APPROVED BY THE EOR AND
 SUBMITTED BUILDING DEPARTMENT PRIOR TO 1ST INSPECTION.
 2) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THEAPPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. SUBMITTALS SHALL INCLUDE
 BUT NOT BE LIMITED TO THE GAS DETECTORS, DUCT SMOKE
 DETECTORS, EXHAUST AND INTAKE LOUVERS, AND THE BOILER
 VENT SYSTEMS.
 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-30 Cont ID  
Sent By ccole Date 2015-10-30 Time 16:19 Rev Time 0.00
Received By ccole Date 2015-10-30 Time 16:18 Sent To  
Notes
2015-10-30 17:05:163RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060551
 10/30/15
  
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS: THIS IS
 THE THIRD REQUEST FOR THE SEQUENCE OF OPERATION FOR THE
 AC SYSTEMS. SEE SHEET H-ADF-01, NOTE #4 AND PROVIDE
 DETAILS ON THE PLAN.
 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS: THE
 DIAGRAMS PROVIDED ON SHEET I-ADF-20 DO NOT COMPLETELY
 ANSWER THE COMMENT: PLEASE PROVIDE THE REQUESTED
 NARRATIVE, SHOW THE ACTUAL LOCATIONS OF THE DETECTORS,
 AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 2) COMMENT #10: 3RD REQUEST FOR DUCT SMOKE DETECTORS TO
 BE INSTALLED IN THE AC SUPPLY AIR SYSTEMS- REFER TO
 SECTION 606.2.1 FBC-10 MECHANICAL. SHEET H-ADF-06 SHOWS
 THE DEVICES ONLY IN THE EXHAUST PLENUMS.
 4) NOTE: AS PREVIOUSLY COMMENTED, SITE SPECIFIC WIND
 LOAD ENGINEERING FOR ATTACHMENT OF THE FANS, FAN CURBS,
 AND AC UNITS IS REQUIRED PER SECTION 301.13. THE
 DETAILS ON SHEET H-STD-3 ARE INCOMPLETE AND NOT IN
 COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-14 Cont ID  
Sent By ccole Date 2015-10-14 Time 08:11 Rev Time 0.00
Received By ccole Date 2015-10-14 Time 07:48 Sent To  
Notes
2015-10-14 08:12:142ND REVIEW: FBC 2010 MECHANICAL
 PERMIT 15060551
 10/14/15
  
 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW, THE
 SUBMITTED NARRATIVE STATES THAT THE PROPOSED BUILDING
 IS EXEMPT FROM THE FLORIDA ENERGY CODE UNDER FAC RULE
 61G20-1.001. I WAS UNABLE TO FIND ANY LANGUAGE IN THE
 RULE SUPPORTING THAT CLAIM. PLEASE SEE SECTION
 C101.4.8.4 FBC-14 ENERGY CONSERVATION AND INDICATE
 WHICH OF THE 5 EXEMPTIONS LISTED PERTAINS TO THE
 PROPOSED BUILDING.
 2) IN RESPONSE TO COMMENT #2 THE NARRATIVE STATES THAT
 AIR HANDLER SCHEDULES ARE ON SHEET H0SCD-03, AND
 EXHAUST FAN SCHEDULES ON H-SCH-01. I WAS UNABLE TO FIND
 THESE SHEETS IN THE UPLOADED PLAN INDEX. PLEASE REVIEW
 AND PROVIDE THE PLAN SHEETS.
 3) IN RESPONSE TO COMMENT #3 THE NARRATIVE STATES THAT
 THE VENTILATION SYSTEM SEQUENCE OF OPERATION IS IN THE
 SPEC BOOK. PLEASE PROVIDE THE REQUESTED SEQUENCE ON THE
 PLANS FOR REVIEW AND INSPECTION PURPOSES.
 4) IN RESPONSE TO COMMENT #4 THE NARRATIVE STATES
 DETAILS TO BE FOUND ON SHEET 0456-I-ADF-20: THIS PLAN
 SHEET NOT UPLOADED.
 5) COMMENT #5: PER NARRATIVE RESPONSE, THE REQUESTED
 BOILER VENTING DETAILS ARE DEFERRED PENDING SUBMITTAL
 OF SHOP DRAWINGS.
 6) COMMENT #7: THE NARRATIVE STATES THE AIR
 DISTRIBUTION SCHEDULE IS ON SHEET H-SCHD-02: THIS PLAN
 SHEET NOT UPLOADED.
 7) COMMENT #10: AS PREVIOUSLY REQUESTED PROVIDE A
 SYMBOL FOR THE DS DETECTOR IN THE SUPPLY DUCTS SHOWN ON
 SHEET H-ADF-02.
 8) COMMENT #12: PER NARRATIVE RESPONSE, THE REQUESTED
 WIND LOAD TIE DOWN DETAILS ARE DEFERRED PENDING
 SUBMITTAL OF MANUFACTURER'S SHOP DRAWINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By ccole Date 2015-07-15 Time 06:58 Rev Time 0.00
Received By ccole Date 2015-07-14 Time 15:51 Sent To  
Notes
2015-07-15 07:22:231ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060551 M1-M4 SLUDGE PUMPING & BOILER/GAS
 HANDLING BUILDING
 7/15/15
  
 1) SUBMIT THE FOLLOWING ENERGY EFFICIENCY COMPLIANCE
 DOCUMENTS PREPARED BY THE ENGINEER OF RECORD: A)
 COOLING AND HEATING CALCULATIONS FOR AHU'S 1, 2, 3, & 4
 IN ACCORDANCE WITH ACCA MANUAL N OR APPROVED ALTERNATE
 METHOD- SECTION 503.2.1 FBC-10 ENERGY CONSERVATION . B)
 ENERGY EFFICIENCY FORM 502-2010 OR 506-2010- REFERENCE
 SECTIONS 101.3, 103, AND CHAPTER 5 FBC-10 ENERGY
 CONSERVATION. THE DESIGN PROFESSIONAL SHALL CHOOSE
 EITHER THE PRESCRIPTIVE (502) OR PERFORMANCE BASED
 (506) COMPLIANCE PATH FOR THE BUILDING AND BUILDING
 SYSTEMS INCLUDING BUT NOT LIMITED TO THE COMPONENTS OF
 THE THERMAL ENVELOPE, THE HVAC AND CHILLER EQUIPMENT,
 THE HYDRONIC PIPING, AND THE ELECTRICAL POWER,
 LIGHTING, AND CONTROLS.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 AHU'S, THE CHILLERS, THE EXHAUST FANS, THE BOILERS AND
 VENT SYSTEM, THE PUMPS, AND THE HEAT EXCHANGERS.
 3) PROVIDE A SEQUENCE OF OPERATION FOR THE VENTILATION
 SYSTEM TO CLARIFY HOW THE SYSTEM WILL FUNCTION-
 THERMOSTATICALLY, CONTINUOUSLY?
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE GAS DETECTOR,
 AND A NARRATIVE DESCRIPTION AND DIAGRAM ON THE PLAN
 DETAILING THE SEQUENCE OF OPERATION.
 5) PROVIDE BOILER VENTING DETAILS INDICATING COMPLIANCE
 WITH CHAPTER 5 FBC-10 FUEL GAS. PROVIDE DIMENSIONED
 SECTION VIEWS THAT A) INDICATE THE TYPE OF VENT PIPING
 AND HOW THEY WERE SIZED. B) SHOW THE TOTAL RUN LENGTH
 FROM THE BOILER TO TERMINATION CAP. C) INDICATE HOW THE
 PIPING ARE BEING SUPPORTED ABOVE AND BELOW THE ROOF-
 WHAT TYPES AND SIZES OF STRAPPING, CABLING, AND ANCHORS
 ETC. ARE TO BE USED. D) SHOW HOW THE ROOF PENETRATION
 IS TO BE SEALED, CURBING, AND ROOF PATCHING DETAILS.
 6) SHEET H-ADF-1, NOTE #4: COMBUSTION AIR FOR THE
 BOILER USING THE ONE-OPENING METHOD SHALL BE CALCULATED
 IN ACCORDANCE WITH SECTION 304.6.2 FBC-10 FUEL GAS.
 REVISE THE NOTE INDICATING COMPLIANCE WITH THE
 INTERNATIONAL 2009 CODE. PER THE NOTE, 128 SQ. FT. OF
 LOUVER AREA HAS BEEN PROVIDED, HOWEVER PLAN SHEET
 H-ADF-2 SHOWS AN 96"X96" LOUVER WHICH WOULD NOT YIELD
 THE REQUIRED AMOUNT OF FREE AIR: PLEASE CORRECT.
 7) PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE PLAN
 LISTING MAKES AND MODELS AND SIZES OF ALL COMPONENTS
 INCLUDING DUCTS, DIFFUSERS, AND RETURN GRILLS.
 8) PROVIDE TYPICAL DUCT HANGING AND CONNECTION DETAILS
 IN ACCORDANCE WITH THE SMACNA 2005 STANDARD.
 9) PROVIDE TESTED AND APPROVED FIRE STOPPING SYSTEM
 DETAILS FOR ALL PIPES OR DUCTS PENETRATING FIRE-RATED
 WALLS.
 10) H-ADF-02: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY DUCTS OF BOTH AHU- 1 & 2: PLEASE PROVIDE A
 SYMBOL ON THE PLAN TO SHOW THEIR LOCATIONS AND PROVIDE
 AN INSTALLATION DETAIL ON THE PLAN- SECTION 606.2.1
 FBC-10 MECHANICAL. PROVIDE INSTALLATION DETAILS FOR THE
 DEVICES, AND HOW THEY WILL BE SUPERVISED PER SECTION
 606.4.1.
 11) H-ADF-4: REFERENCE COMMENT #9 ABOVE AND APPLY TO
 AHU-3 & 4.
 12) H-ADF-3 & H-ADF-5: ENGINEERED WIND LOAD TIE-DOWN
 DETAILS FOR MOUNTING THE AHU'S AND CURBS, AND THE
 EXHAUST FANS AND CURBS ON THE ROOF ARE REQUIRED PER
 SECTION 301.12. PLEASE PROVIDE DETAILS, OR PLACE A NOTE
 INDICATING ON WHICH STRUCTURAL OR ARCHITECTURAL SHEET
 THE DETAILS ARE LOCATED. PROVIDE ELEVATION AND PLAN
 VIEW DRAWINGS INDICATING THE STRUCTURAL COMPONENTS OF
 THE CURBS, AND SHOW THE CURB HEIGHTS ABOVE THE FINISHED
 ROOF.
 13) PROVIDE SECTION VIEWS OF THE ROOF LADDERS TO
 INDICATE COMPLIANCE WITH THE DESIGN CRITERIA LISTED IN
 SECTION 306.5 FBC-10 MECHANICAL.
 14) PROVIDE WIND LOAD DESIGN CRITERIA, AND ENGINEERED
 TIE DOWN DETAILS FOR INSTALLATION OF THE CHILLERS AND
 PROPANE TANK- SECTION 301.12 FBC-10 MECHANICAL.
 15) CHILLERS: A) PROVIDE SYSTEM SIZING CALCULATIONS. B)
 PROVIDE THE EFFICIENCY RATINGS OF THE EQUIPMENT PER
 TABLE 503.2.3(7) FBC-10 ENERGY EFFICIENCY. C) PROVIDE
 AN ENLARGED DIAGRAM OF THE CHILLERS AND PIPING SYSTEMS
 INDICATING THE TYPES AND SIZES OF PIPING, PIPING
 INSULATIONS, UNDERGROUND PIPING PROTECTIONS, ETC.
 16) PROVIDE A GAS PIPING ISOMETRIC AND LAYOUT PLAN FOR
 THE PROPANE SYSTEM- REFERENCE CHAPTER 4 FBC-10 FUEL
 GAS.
 17) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 20) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPES SERVICING EACH TANK,
 FACILITY, OR BUILDING.
 21) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES A)
 FLORIDA PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S FOR
 ALL PRODUCTS REGULATED BY FAC RULE 9N-3 REVIEWED AND
 APPROVED IN WRITING BY THE DESIGN PROFESSIONAL OF
 RECORD (HVAC ROOF CURBS, EXHAUST FANS AND CURBS,
 EXHAUST AND INTAKE LOUVERS, ETC.). B) MANUFACTURER'S
 PRODUCT DATA SHEETS FOR THE AHU'S, ROOF MOUNTED EXHAUST
 FANS, THE CHILLERS, ELECTRONIC CONTROLS, PROCESS
 PIPINGS, AND PIPING INSULATION ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-11-10 Cont ID  
Sent By tklarge Date 2015-11-10 Time 11:52 Rev Time 0.00
Received By tklarge Date 2015-11-10 Time 05:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-24 Cont ID  
Sent By tklarge Date 2015-10-24 Time 08:08 Rev Time 0.00
Received By tklarge Date 2015-10-24 Time 06:48 Sent To  
Notes
2015-10-24 07:03:541) SHT. 0386- A - ADF - 08 - FBC 2010 SEC.1503.4.2.1
 OVERFLOW SCUPPERS - OVERFLOW SCUPPERS SHALL BE LOCATED
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS
 PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR
 WALL AND PARAPET SCUPPERS. NOTE # 2 STATES THE OVERFLOW
 SCUPPER WILL BE 3 INCHES ABOVE THE PRIMARY SCUPPER.
 INCLUDE IN THE NOTE THAT THE OVERFLOW SCUPPER SHALL BE
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF SURFACE.THIS IS THE LANGUAGE IN THE CODE.
 NOTE #2 STATES "3 INCHES ABOVE THE PRIMARY SCUPPER".
 THIS COULD POSSIBLY BE MISINTERPRETED AS MEANING THE
 TOP OF THE SCUPPER.
 2) THE DESIGN TEAM'S RESPONSE NARRATIVE FOR THE LP GAS
 REVIEW COMMENTS ARE VAGUE. THE FOLLOWING ITEMS ARE
 REQUIRED FOR A COMPREHENSIVE PLAN REVIEW TO BE DONE FOR
 THE LP GAS SYSTEM AND SHALL BE SUPPLIED WHEN THE GAS
 PERMIT IS APPLIED FOR BY AMERIGAS.
 A) SUBMIT AN GAS ISOMETRIC DRAWING THAT CLEARLY SHOWS
 THE LENGTH OF ALL CUT SECTIONS OF PIPE PER THE 2010
 FBC- FUEL GAS SEC.402.1.402.3 & NFPA 58.
 B) SHOW THE TYPE OF PIPING MATERIAL BEING INSTALLED &
 ALL PIPE SIZES. WPB AMEND. TO FBC SEC. 107.2.1.
 C) TYPE OF GAS ( LP OR NATURAL ).
 D) BTU LOAD OF EACH APPLIANCE OR PIECE OF EQUIPMENT AND
 THE TOTAL BTU LOAD ON THE SYSTEM.
 E) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,( METER
 OR 2 PSI REGULATOR ) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR THE SYSTEM.
 F) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER 2010
 FBC-FUEL GAS CODE SEC. 304.
 G) INDICATE THE DELIVERY PRESSURE ( PSI ) OF THE GAS.
 H) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE BUILDING, THE DISTANCE OF THE TANK
 FROM ALL SOURCES OF IGNITION, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANKPER
 NFPA 58, TABLE 3-2.2.2.
 I) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 OR BELOW GROUND AND SHOW THE REQUIRED PROTECTION OF THE
 TANK AND APPURTENANCES PER NFPA 58.
 3) IT DOES NOT APPEAR AS THOUGH THE PLUMBING PLAN
 REVIEW COMMENTS FROM 10/8/15 HAVE BEEN ADDRESSED.
 CLARIFY.
 SHT. 0167-M-ADF-34 DOES NOT PROVIDE ALL OF THE REQUIRED
 INFORMATION PREVIOUSLY REQUESTED FOR THE GAS RISER
 DIAGRAM.NEITHER DOES SHT.0164-M-ADF-31.SINCE THIS
 INFORMATION HAS NOT BEEN FULLY SUBMITTED, THE PLAN WILL
 BE MARKED THAT A SEPARATE PERMIT WILL BE REQUIRED FOR
 THE GAS AND ALL REQUIRED INFO WILL BE SUBMITTED AT TIME
 OF PERMIT APPLICATION SUBMITTAL ALONG WITH ALL NEW
 DRAWINGS OR SUBMIT ALL THE INFORMATION AS PREVIOUSLY
 REQUESTED.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE
 NARRATIVE RESPONSES TO THE GAS COMMENTS DO NOT PROVIDE
 SUFFICIENT INFO TO DO A COMPREHENSIVE REVIEW.
 5) THE NARRATIVE RESPONSE FOR PREVIOUS COMMENT # 9 DOES
 NOT COMPLY WITH SEC.905.2. THE VENT CONNECTION SHALL BE
 SO GRADED AND CONNECTED AS TO DRAIN BACK TO THE
 DRAINAGE PIPE BY GRAVITY. AS DRAWN, IT IS INSTALLED TO
 DRAIN BACK TO THE FIXTURE TO WHICH IT IS CONNECTED.IT
 DOES NOT COMPLY WITH 2010 FBC-PLUMBING SEC.706.3 &
 905.2.THE FITTING SHALL BE INSTALLED IN THE DIRECTION
 OF FLOW.AS DRAWN IT IS NOT.
 6) SHT.0696-H-ADF-01 REFERS TO TWO DIFFERENT STANDARDS
 FOR CALCULATING COMBUSTION AIR REQUIREMENTS. THE CODE
 IN EFFECT IS THE 2010 FBC-FUEL GAS. THE APPROPRIATE
 SECTION FOR USING TWO OPENINGS COMMUNICATING DIRECTLY
 WITH THE OUTDOORS IS 304.6.1. THE FORMULA IS A MINIMUM
 FREE AREA OF 1 SQUARE INCH PER 4000/ BTU OF TOTAL INPUT
 RATING OF ALL APPLIANCES IN THE ENCLOSURE. PLEASE
 EXPLAIN WHERE THE .47 FREE AREA COMES FROM IN YOUR
 EQUATION. SEC.304.10 OF 2010 FBC-FUEL GAS SPECIFIES
 METAL LOUVERS AND GRILLS WILL HAVE 75% FREE AREA. THE
 DESIGN MEETS THE REQUIRED COMBUSTION AIR BUT NOTES # 3
 & #4 ON SHT 0696-H-ADF-01 NEED TO BE REVISED.
  
 PLEASE CONTACT ME TO DISCUSS THESE REVIEW COMMENTS OR
 TO SET UP A MEETING TO GO OVER THE COMMENTS THANK YOU.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-06 Cont ID  
Sent By tklarge Date 2015-10-06 Time 11:46 Rev Time 0.00
Received By tklarge Date 2015-10-05 Time 12:46 Sent To  
Notes
2015-10-06 11:24:281) THE NARRATIVE RESPONSE TO REVIEW COMMENTS REFERS TO
 DRAWING 0456-I-ADF -20 FOR DETAILS FOR THE GAS DETECTOR
 INFO. THIS DRAWING IS NOT INCLUDED IN THIS PEMIT
 PACKAGE. PLEASE INCLUDE THIS DRAWING FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SHT. 0167-M-ADF-34 DOES NOT PROVIDE ANY OF THE
 REQUIRED INFORMATION PREVIOUSLY REQUESTED FOR THE GAS
 RISER DIAGRAM.NEITHER DOES SHT.0164-M-ADF-31.SINCE THIS
 INFORMATION HAS NOT BEEN SUBMITTED THE PLAN WILL BE
 MARKED THAT A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 GAS AND ALL REQUIRED INFO WILL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION SUBMITTAL ALONG WITH ALL NEW
 DRAWINGS OR SUBMIT ALL THE INFORMATION AS PREVIOUSLY
 REQUESTED.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE
 NARRATIVE RESPONSES TO THE GAS COMMENTS DO NOT PROVIDE
 SUFFICIENT INFO TO DO A COMPREHENSIVE REVIEW.
 3) SHT.0386-A-ADF-08 - DETAIL # 0763010 & NOTE #2 -
 NOTE # 2 STATES THE OVERFLOW SCUPPER WILL BE 3 INCHES
 ABOVE THE PRIMARY SCUPPER. INCLUDE IN THE NOTE THAT THE
 OVERFLOW SCUPPER SHALL BE NO LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF SURFACE.THIS
 IS THE LANGUAGE IN THE CODE.NOTE #2 STATES "3 INCHES
 ABOVE THE PRIMARY SCUPPER". THIS COULD BE
 MISINTERPRETED AS MEANING THE TOP OF THE SCUPPER.
 4) SHT. 0385-A-ADF-7- THE ROOF DRAINAGE CALCULATIONS
 SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES PER HOUR
 AS THERE IS NO 4.5 INCH RAINFALL RATE IN ANY OF THE
 SIZING TABLES.THE ALLOWABLE SQUARE FOOT AREA TO BE
 DRAINED BY EACH DRAIN/SCUPPER WILL HAVE TO BE ADJUSTED.
 5) THE NARRATIVE RESPONSE FOR PREVIOUS COMMENT # 9 DOES
 NOT COMPLY WITH SEC.905.2. THE VENT CONNECTION SHALL BE
 SO GRADED AND CONNECTED AS TO DRAIN BACK TO THE
 DRAINAGE PIPE BY GRAVITY. AS DRAWN, IT IS INSTALLED TO
 DRAIN BACK TO THE FIXTURE TO WHICH IT IS CONNECTED.IT
 DOES NOT COMPLY WITH 2010 FBC-PLUMBING SEC.706.3 &
 905.2.THE FITTING SHALL BE INSTALLED IN THE DIRECTION
 OF FLOW.AS DRAWN IT IS NOT.
 6) SHT.0696-H-ADF-01 REFERS TO TWO DIFFERENT STANDARDS
 FOR CALCULATING COMBUSTION AIR REQUIREMENTS. THE CODE
 IN EFFECT IS THE 2010 FBC-FUEL GAS. THE APPROPRIATE
 SECTION FOR USING TWO OPENINGS COMMUNICATING DIRECTLY
 WITH THE OUTDOORS IF 304.6.1. THE FORMULA IS A MINIMUM
 FREE AREA OF 1 SQUARE INCH PER 4000/ BTU OF TOTAL INPUT
 RATING OF ALL APPLIANCES IN THE ENCLOSURE. PLEASE
 EXPLAIN WHERE THE .47 FREE AREA COMES FROM IN YOUR
 EQUATION. SEC.304.10 OF 2010 FBC-FUEL GAS SPECIFIES
 METAL LOUVERS AND GRILLS WILL HAVE 75% FREE AREA. THE
 DESIGN MEETS THE REQUIRED COMBUSTION AIR BUT NOTES # 3
 & #4 ON SHT 0696-H-ADF-01 NEED TO BE REVISED.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By tklarge Date 2015-07-22 Time 03:21 Rev Time 0.00
Received By tklarge Date 2015-07-21 Time 14:06 Sent To  
Notes
2015-07-21 14:13:261) SUBMIT A GAS RISER DIAGRAM FOR THE LP TANK &
 PIPNG.INDICATE THE TYPE OF PIPING, THE TOTAL DEVELOPED
 LENGTH OF THE PIPNG FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET, THE TOTAL BTU LOAD ON THE SYSTEM,
 AND THE BTU LOAD OF EACH BOILER/APPLIANCE. 2010 FGC
 SEC.402.4.1.
 2) INDICATE IF THE LP TANK IS ABOVEGROUND OR BELOW
 GROUND. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 3) SHOW THE DISTANCE OF THE LP TANK FROM THE BUILDING.
 COMPLY WITH NFPA 58 FOR SPACING REQUIREMENTS.
 4) SHT. 0386-A-ADF-08 - OVERFLOW SCUPPERS SHALL BE
 PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TOTHE REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS PER FBC SEC.1503.4.2.1.
 5) SHT. 0386-A-ADF-08 REFERS TO SHT. A-ADF-07 FOR ROOF
 DRAIN CALCULATIONS. THIS SHEET IS NOT PART OF THIS PLAN
 PACKAGE. CLARIFY.
 6) SHT.0388-A-ADF-10 IS FOR THE ELECTRICAL BUILDING. IS
 THIS SHEET SUPPOSED TO BE PART OF THIS PLAN PACKAGE?
 7) PLEASE REFER TO THE SPECIFIC YARD PIPING DRAWINGS
 FOR THE CONTINUATION OF THE SANITARY AND WATER LINES.
 SEE SHTS. 0717-P-ADF-01 & 0719-P-ADF-03. WPB AMEND. TO
 FBC SEC. 107.2.1.
 8) SHT. 0717-P-ADF-01 - INDICATE WHAT IS BEING
 DISCHARGED INTO THE FLOOR FLOOR DRAINS. WASTES THAT
 COULD BE HARMFUL TO THE DRAINAGE SYSTEM SHALL BE
 DISCHARGED THROUGH A NEUTRALIZING OR DILUTION MEDIUM
 PER FPC SEC.803.2.
 9) SHT. 0766-M-STD-09 - DETAIL 1542102 - THE WYE SHALL
 BE INSTALLED IN THE DIRECTION OF FLOW PER FPC
 SEC.706.3.
 10) SHT. 0384-A-ADF-06 - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER THE FL.
 ACCESSIBILITY CODE SEC. 609.4.
 11) THE LEADING EDGE "HI" UNIT OF THE DRINKING FOUNTAIN
 MAY ONLY PROTRUDE 4 INCHES INTO THE ACCESSIBLE
 CIRCULATION PATH IF THE LEADING EDGE IS MORE THAN 27
 INCHES ABOVE THE FINISH FLOOR. A SKIRT MAY BE NEED ON
 THE UNIT TO PLACE THE LEADING EDGE BELOW 27 INCHES. PER
 THE FL. ACCESSIBILITY CODE SEC. 307.2.
 12 ) INDICATE ON THE PLANS HOW THE ROOF PENETRATION FOR
 THE BOILER VENTS WILL BE SEALED. SHOW THE TYPE OF VENT
 MATERIAL, TOTAL RUN( LENGTH) OF THE VENTS FROM THE
 DRAFT HOOD TO THE TERMINATION CAP.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 11:12 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-11-13 11:13:49SHEETS NEEDED M-STD 09, A-ADF 07, S-GEN 01, H-ADF 02,
 M-STD 03.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-09-08 Cont ID  
Sent By jroach Date 2015-09-08 Time 13:42 Rev Time 0.00
Received By jroach Date 2015-09-08 Time 13:42 Sent To  
Notes
***NONE***