| 2015-07-02 10:49:06 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060538 DIGESTER T1 |
| | W. P. B. PERMIT 15060539 DIGESTOR T2 |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 2/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID. |
| | |
| | 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02 |
| | THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO |
| | USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS |
| | DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING |
| | TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | |
| | 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE |
| | G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS, |
| | THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE |
| | CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION. |
| | |
| | 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR. |
| | PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS |
| | SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO |
| | BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION |
| | 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF |
| | RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| | PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| | DEPARTMENT. |
| | FORMS E-MAILED TO: [email protected] THURS. |
| | JULY 02/2015 07:25 AM. |
| | |
| | 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] OR [email protected] |
| | |
| | 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] OR [email protected] |
| | |
| | 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS. |
| | |
| | 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST |
| | PALM BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED |
| | IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT |
| | ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT |
| | THAT POINT. |
| | |
| | 4) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, HAS A |
| | HEADING FOR FOUNDATION WORK BUT THERE IS NO CRITERIA |
| | LISTED FOR THE SOILS INVESTIGATION REPORT, DATE AND |
| | COMPANY COMPLETING THE SOILS INVESTIGATION. 2010 FBC-B |
| | 1803.5.2. FOUNDATION NOTE F-2 PROVIDES THE ALLOWABLE |
| | SOILS BEARING PRESSURES BUT THERE IS NO DOCUMENTATION |
| | OF A SOILS ANALYSIS AND EVALUATION EVER TAKING PLACE. |
| | |
| | 5) PLEASE NOTE THAT A COPY OF DUNKELBERGER TESTING |
| | REPORT HD145002 APRIL 10, 2014 WAS SUBMITTED BY E-MAIL |
| | FOR REVIEW. THIS REPORT WILL NEED TO EITHER HAVE A HARD |
| | COPY SIGNED AND SEALED OR THE ELECTRONIC PEDDS |
| | SIGNATURE FOR ELECTRONIC VERSIONS OF THIS DOCUMENT. |
| | |
| | 5A) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | VIBRO-COMPACTION FOR THE PROJECT SHOULD BE CARRIED OUT |
| | BY AN EXPERIENCED CONTRACTOR EMPLOYING A GROUND |
| | IMPROVEMENT PLAN THAT HE/SHE PREPARES. THE PLAN SHOULD |
| | UTILIZE CENTER-TO-CENTER SPACINGS FOR THE |
| | VIBRO-COMPACTION POINTS THAT ARE NORMALLY USED IN |
| | GRANULAR SOILS TO ACHIEVE 80 PERCENT RELATIVE DENSITY. |
| | BEFORE ADOPTION, THE GROUND IMPROVEMENT PLAN SHOULD BE |
| | REVIEWED BY THE GEOTECHNICAL ENGINEER AND STRUCTURAL |
| | ENGINEER FOR CONFORMANCE WITH THE INTENT OF THE |
| | FOUNDATION DESIGN. |
| | PLEASE PROVIDE FOR REVIEW BY THE BUILDING DEPARTMENT |
| | FOR COMPLIANCE. |
| | |
| | 5B) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | RECOMMENDS THE EXCAVATED FILL FOR ALL OF THE DIGESTER |
| | TANKS NOT BE RE-USED, WILL THIS FILL BE USED ELSE WHERE |
| | ON SITE FOR FILL, AND IF SO STORED WHERE, A CONCERN AS |
| | TO THE CLOSENESS OF FILL STORED TO THE EXCAVATION OF |
| | THE DIGESTERS AND OR OTHER STRUCTURES. 2010 FBC-B |
| | 3304.1.2 SURCHARGE & 1808.7 FOUNDATIONS ON OR ADJACENT |
| | TO SLOPES. |
| | |
| | 5C) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | RECOMMENDS |
| | ADD FILL USED IN THE COMPACTION POINTS SHOULD CONSIST |
| | OF CLEAN SANDS HAVING A SUITABILITY NUMBER (SN) OF 20 |
| | OR LOWER. WE DO NOT BELIEVE THAT THE ON-SITE SANDS WILL |
| | MEET THIS REQUIREMENT. THEREFORE THE ADD FILL WILL NEED |
| | TO BE IMPORTED. PLEASE INCORPORATE INTO THE VIBRO- |
| | FLOTATION PLAN. |
| | |
| | 6A) THE SHEET 0270-S-ADF-04 INDICATES THE GROUND |
| | ELEVATION AROUND ELEVATION 19.5 NGVD AND THE BOTTOM OF |
| | THE EXCAVATED BASIN AT ELEVATION 10.00 NGVD. |
| | DUNKELBERGER TESTING REPORT HD145002 APRIL 10, 2014, |
| | PAGE 10 UNDER THE HEADING OF DEWATERING STATES THAT THE |
| | CHOSEN SYSTEM SHOULD BE CAPABLE OF PRESERVING THE |
| | STRENGTH OF THE FOUNDATION BEARING MATERIALS, ASSURING |
| | STABILITY OF EXCAVATION SIDEWALLS, NOT REMOVING FINES |
| | FROM THE SUBSOILS AND MAINTAINING THE PRE-DRAINED |
| | SURFACE AT LEAST 30 INCHES BELOW THE EXCAVATION |
| | BOTTOMS. RELEASE OF GROUNDWATER TO ITS STATIC LEVEL |
| | SHOULD BE PERFORMED IN A MANNER THAT ASSURES STABILITY |
| | OF THE FOUNDATION SOILS, PREVENTS DISTURBANCE TO |
| | COMPACTED SOILS AND PREVENTS MOVEMENT OR FLOTATION OF |
| | STRUCTURES AND PIPING. |
| | |
| | WILL ALL OF THE DIGESTORS BE EXCAVATED AND FOUNDATION |
| | WORK AT THE SAME TIME, REQUIRING DEWATERING OF ALL 6 |
| | BASINS AT THE SAME TIME. PLEASE PROVIDE DOCUMENTATION |
| | OF HOW THIS WILL BE ACHIEVED AND WHERE THE OUT |
| | FLOWDISCHARGE OF WATER WILL BE DRAINED. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED |
| | SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS |
| | OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| | SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY |
| | PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE |
| | DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION, |
| | PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| | COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 6B) THE SHEET 0270-S-ADF-04 SHOWS NO INFORMATION FOR |
| | THE FIXED STEEL ROOF COVER. THERE IS NO DESIGN |
| | CRITERIA, NO INFORMATION FOR FRAMING MEMBERS, SIZE OF |
| | FRAMING MEMBERS, SPACING, ATTACHMENT OF ROOF SHEATHING/ |
| | DECK TO FRAMING MEMBERS. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 6C) DETAIL # 3 SHOWS ROOF TOP STRUCTURES PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1609.8 ROOF TOP STRUCTURES |
| | AND EQUIPMENT. |
| | |
| | 7A) SHEET 0275-S-ADF-09 DETAILS 1 & 2 WALL SECTIONS |
| | THERE MAY BE A DISCREPANCY IN THE RE-ENFORCING OF |
| | RE-BAR SIZES? FROM THE SLAB THE PLANS SHOW A # 10 DOWEL |
| | AT 6INCHES O. C. FURTHER UP THE PAGE THE PLANS INDICATE |
| | THE USE OF # 7 @ 6 INCHES O. C. IS THIS CORRECT, |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7B) SHEET 0275-S-ADF-09 DETAILS 1 & 2 WALL SECTIONS |
| | SHOW WATER STOPS BUT REFERANCE IS A SPEC. PLEASE |
| | PROVIDE ON PLANS, 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. . CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 8A) SHEET 0276-S-ADF-10 DETAIL B SHOWS A GUARDRAIL |
| | SYSTEM BUT THERE ARE NO DIMENSIONS VERTICALLY SHOWING |
| | COMPLIANCE WITH SECTION 2010 FBC-B 1013.2 HEIGHT. |
| | |
| | 8B) SHEET 0276-S-ADF-10 DETAIL B SHOWS A GUARDRAIL |
| | SYSTEM WITH NO VERTICAL DIMENSIONS SHOWING COMPLIANCE |
| | WITH THE 1013.2 HEIGHT. |
| | |
| | 8C) SHEET 0276-S-ADF-10 DETAIL B SHOWS A GUARDRAIL |
| | SYSTEM WITH NO VERTICAL DIMENSIONS SHOWING COMPLIANCE |
| | WITH THE 2010 FBC-B 1012.2 HEIGHT REQUIREMENTS. |
| | |
| | 8D) SHEET 0276-S-ADF-10 DOES NOT PROVIDE COMPLIANCE |
| | WITH 2010 FBC-B 1607.7.1 AND 1607.7.1.1. LOADS ON |
| | HANDRAILS AND GUARDS. |
| | |
| | 9A) SHEET 0276-S-ADF-12 DOES NOT PROVIDE COMPLIANCE |
| | WITH 2010 FBC-B 1607.7.1 AND 1607.7.1.1. LOADS ON |
| | HANDRAILS AND GUARDS. |
| | 9B) SHEET 0276-S-ADF-12 DOES NOT PROVIDE COMPLIANCE |
| | WITH 2010 FBC-B 1013.2 HEIGHT & 1013.2 HEIGHT. |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |