Plan Review Details - Permit 15060504
Plan Review Stops For Permit 15060504
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-06-18 Cont ID  
Sent By skennedy Date 2015-06-18 Time 11:45 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-06-18 11:46:00SEE 15050654

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-15 Cont ID  
Sent By albarran Date 2015-06-15 Time 12:41 Rev Time 0.00
Received By albarran Date 2015-06-15 Time 12:41 Sent To B
Notes
2015-06-15 12:46:22THIS SUBMITTAL WAS REJECTED FOR THE FOLLOWING:
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 IN ADDITION TO THE ABOVE, AN ELECTRICAL DIAGRAM
 INDICATING THE EXTENT OF THE ELECTRICAL RE4REQUIREMENTS
 SHALL BE SUBMITTED AS WELL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-18 Cont ID  
Sent By wjolin Date 2015-06-18 Time 17:51 Rev Time 0.00
Received By wjolin Date 2015-06-18 Time 17:50 Sent To  
Notes
2015-06-18 17:51:486751/7501 NORTH JOG ROAD
 PERMIT #15060504
 REVIEW COMMENTS - FIRE DEPARTMENT
 UP: 06/18 DN: 06/29
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 SEVERAL OF THE TENTS AND TRAILERS APPEAR TO BE LOCATED
 IN FIRE LANES.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By wjolin Date 2015-06-12 Time 12:45 Rev Time 0.00
Received By wjolin Date 2015-06-12 Time 12:06 Sent To B
Notes
2015-06-12 12:44:577501 NORTH JOG ROAD
 PERMIT #15060504
 REVIEW COMMENTS - FIRE DEPARTMENT
 UP: 06/18 DN: 06/29
  
 ADDRESS ON PERMIT APPLICATION DOES NOT MATCH THE
 ADDRESS OF THE ACTUAL EVENT; APPEARS TO BE 6751 NORTH
 JOG ROAD - ADMIN BUILDING.
  
 SEPARATE PERMITS ARE NEEDED FOR THE RESTROOM TRAILER
 AND POSSIBLY THE "GAMING" TRAILER IF OCCUPANTS CAN
 ENTER THE STRUCTURE.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 DO ANY OF THE TENTS HAVE SIDEWALLS ON MORE THAN 2
 SIDES?
  
 SEVERAL OF THE TENTS AND TRAILERS APPEAR TO BE LOCATED
 IN FIRE LANES.
  
 ARE THE TABLES/CHAIRS LOCATED BENEATH A TENT (TENT SIZE
 CANNOT BE READ)?
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 WHAT TYPE OF COOKING OPERATIONS ARE TO BE PERFORMED
 UNDER THE FOOD TENT?
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-18 Cont ID  
Sent By wjolin Date 2015-06-18 Time 17:51 Rev Time 0.00
Received By wjolin Date 2015-06-11 Time 14:39 Sent To  
Notes
2015-06-11 14:40:40ROUTED TO TEMP TENTS/FIRE

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-06-18 Cont ID  
Sent By skennedy Date 2015-06-18 Time 11:45 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-06-18 11:46:11SEE 15050654

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 13:12 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 13:12 Sent To  
Notes
2015-06-12 13:30:161)SUBMIT A SITE PLAN THAT IS LARGE ENOUGH TO READ WHAT
 IS BEING PLACED ON THE SITE. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) INDICATE THE ESTIMATED NUMBER OF ATTENDEES. SANITARY
 FACILITIES SHALL BE PROVIDED.
 3) IF PORTABLE SANITARY FACILITIES ARE BEING PROVIDED
 SUCH AS A TRAILER AND IT IS CONNECTED TO A SEWAGE
 HOLDING TANK, INDICATE THE SIZE OF THE HOLDING TANK. A
 PERMIT FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT MAY
 BE REQUIRED. SHOW THE LOCATION OF ALL PORTABLE SANITARY
 FACILITIESFOR THIS EVENT. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 4) IF POTABLE WATER WILL BE CONNECTED ANY PORTABLE
 RESTROOM UNITS, A BACKFLOW PREVENTION DEVICE SHALL BE
 INSTALLED ON THE WATER LINE PER THE CITY'S CROSS
 CONNECTION ORDINANCE.FPC SEC.608.
 5) IF NON-POTABLE WATER CONNECTIONS ARE USED, SIGNS
 SHALL BE POSTED IN CONSPICUOUS PLACES STAING THAT THE
 WATER IS NON-POTABLE, DO NOT DRINK.FPC 608.8.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  