| 2015-06-19 07:59:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060473 |
| | ADD: 525 S. FLAGLER DR. 5TH FLOOR WELLNESS AREA |
| | CONT: URBAN BUILDING CONCEPTS |
| | TEL: ( 561)727-8343 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S1-1 DETAIL # 1 INDICATES THE USE OF HU410 OR |
| | HUC410 BUCKETS TO TO SECURED TO THE CONCRETE SLAB . |
| | THERE ARE (2) ISSUES: |
| | 1A) THE USE OF OR CAN NOT BE USED. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. . SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 1B) SHEET A1-1 DETAIL # 1 INDICATES THE USE OF UL |
| | LISTING G556 A UNRESTRAINED FLOOR / CEILING ASSEMBLY. |
| | REQUIREMENT NOTE # 2 DEALS WITH THE METAL JOIST AND |
| | CLIP ASSEMBLIES. THE HANGER BUCKETS ARE NOT PART OF |
| | THIS ASSEMBLY. PLEASE IDENTIFY WHICH PARTS OF THIS |
| | ASSEMBLY ARE GOING TO BE INSTALLED. WITHAPPROPRIATE RIM |
| | JOIST OR IF THE CLIP ANGLES ARE GOING TO BE INSTALLED. |
| | IF STIFFNER FLANGES ARE REQUIRED, IF SO MINIMUM LENGTH, |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1C) ALSO FOUND IN THE SAME FLOOR INFILL, BRIDING |
| | REQUIREMENTS FOUND UNDER REQUIREMENT # 3 OF UL G556. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1D) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE |
| | USE OF A RESILIENT CHANNEL RC-1 OR EQUAVALENT 107.2.1 |
| | CAN NOT USE OR THE PLANS HAVE TO BE SPECIFIC. |
| | |
| | 1E) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE |
| | USE OF A RESILIENT CHANNEL DOES NOT SHOW THE CENTER TO |
| | CENTER OF THE CHANNELS NOR TYPE OF FASTENER. |
| | |
| | 2) THE COVERSHEET ALSO INDICATES UPDATING THE CORRIDOR |
| | WALL WITH STOREFRONT WINDOW AND DOOR SYSTEMS, BUT DOES |
| | NOT PROVIDE ANY INFORMATION AS TO DESIGN FOR LIFE |
| | SAFETY FOR THIS FLOOR, NO LIFE SAFETY PLAN WAS |
| | INCLUDED. WHAT FACTORS ARE IN PLACE THAT WILL ALLOW |
| | THIS FLOOR TO BE A NON-FIRE RATED EXIT ACCESS COORIDOR |
| | (FBC-B TABLE 1015.1 & TABLE 1016.1 )? HOW FAR FROM THE |
| | FURTHEST POINT ON THE FLOOR TO AN EXIT TABLE 1016.1?AND |
| | SINCE THERE ARE ELEVATORS, WHY NO ELEVATOR LOBBIES |
| | (708.14.1 IN PLACE OR EXCEPTIONS)? NO OCCUPANCY |
| | CLASSIFICATION FOR THIS FLOOR HAS BEEN DECLARED, IS |
| | THIS A MIXED OCCUPANCY? ARE OCCUPANCY SEPARATION WALLS |
| | REQUIRED AND WHERE? FBC-B 508.2.4. |
| | |
| | 3) SHEET A1.1 SHOWS VARIOUS GYMS ON THIS FLOOR PLEASE |
| | PROVIDE THE SQUARE FOOTAGE OF EACH AREA AND OCCUPANT |
| | LOAD AT 15 SQ.FT./ OCCUPANT SINCE THERE IS NO |
| | EQUIPMENT. NOTE WHEN THERE IS OVER 49 OCCUPANTS IN A |
| | ROOM FBC-B TABLE 1015.1 REQUIRES A 2ND MEANS OF EGRESS |
| | OUT OF THE ROOM. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |