| Notes |
| 2015-06-11 11:42:07 | APPROVED WITH THE FOLLOWING PROVISOS | | | FOR FINAL INSPECTION THE FOLLOWING SHALL BE REQUIRED: | | | 1. CONDUCTOR INSULATION AS INDICATED ON THE SUBMITTED | | | DRAWINGS, DOES NOT COMPLY W/NEC 300.5(B) CORRECT | | | ACCORDINGLY. | | | 2. PANEL SCHEDULE AS PRESENTED INDICATES THE USE OF A | | | BACK-FED BREAKER, IF SO, IT SHALL COMPLY W/NEC | | | 408.36(D). | | | 3. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS | | | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL | | | INSPECTOR. NO SITE TUBES ARE ALLOWED. |
|
|