Plan Review Details - Permit 15060392
Plan Review Stops For Permit 15060392
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-18 Cont ID  
Sent By jwitmer Date 2015-12-18 Time 09:12 Rev Time 0.00
Received By jwitmer Date 2015-12-18 Time 07:01 Sent To  
Notes
2015-12-18 08:14:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060392
 ADD: 638 BELVEDERE RD.
 CONT: EXCEL GENERAL CONSTRUCTION
 TEL: (305)984-3488
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. DEC.18/2015
 ACTION: BUILDING PROVISO
  
 1) PROVISO: THIS PERMIT AND PLANS WERE DESIGNED AND
 ISSUED UNDER THE 2010 FBC-B 140 MPH / 3 SECOND GUST.
 SEPARATE PLANS AND PERMITS WILL BE REQUIRED KITCHEN
 HOOD, HOOD FIRE SUPPRESSION SYSTEM, ROOF TOP EXHAUST
 FANS, WALK-IN COOLER AND FREEZER. THE SUBMITTED WIND
 DESIGN FOR ROOF TOP EQUIPMENT WAS FOR THE 2014 FBC WIND
 DESIGN OF 132 VASD NOT THE 140 MPH UNDER THE 2010
 FBC-B.
  
 PLEASE NOTE PERMITS FOR KITCHEN HOOD, HOOD FIRE
 SUPPRESSION SYSTEM, ROOF TOP EXHAUST FANS, WALK-IN
 COOLER AND FREEZER WILL BE SUBMITTED UNDER THE 2014
 FBC-B WIND DESIGN OF 170 MPH VULT & 132 MPH VASD.
 PLEASE REVIEW THE COMPUTER PRINTED WIND DESIGN PAGE 2
 MAPS INDICATE 160 MPH/150. NOTE THIS TYPE OF STRUCTURE
 IS A BUILDING RISK CATEGORY II 170 VULT MPH WIND ZONE
 NOT THE 160 VULT MPH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-24 Cont ID  
Sent By jwitmer Date 2015-09-24 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2015-09-24 Time   Sent To  
Notes
2015-09-24 08:59:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060392
 ADD: 638 BELVEDERE RD.
 CONT: EXCEL GENERAL CONSTRUCTION
 TEL: (305)984-3488
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 24/2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
  
 1) 2ND REQUEST. SHEET H-1 DOES SHOW ATTACHMENT CURB
 DETAILS FOR THE EXHAUST FAN.
  
 1A) THERE ARE MULTIPLE TYPE OF FASTENERS PROVIDED ON
 THE PLANS WITH THE USE OF THE WORD "OR", THE PLANS NEED
 TO BE SPECIFIC TO THE TYPE OF FASTENER. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 1B) 2ND REQUET, SEMI-COMPLIED. ENGINEERING SHEETS
 ATTACHED PROVIDES THE WIND DESIGN CRITERIA AND ROOF
 PRESSURES OF 21.8/ -60.2. THE PRESSURES ARE ASSUMED
 VULT? THERE ARE 3 ROOF ZONES, 1,THE CENTER OF THE ROOF,
 2 ZONE THE PERIMETER AND ZONE 3 THE CORNERS OF THE
 ROOF. PLEASE ALSO IDENTIFY TO WHICH ROOF ZONE THESE
 PRESSURES ARE PROVIDED. NOTE THE ROOF TOP CURBS AND
 ROOF TOP EXHAUST FANS AND INTAKE FANS THAT ARE
 CONNECTED TO THE HOOD SYSTEM WILL NEED TO SUPPLY THE
 PRODUCT APPROVALS FOR THE CURB AND FANS. WE WILL NEED
 THE WIND DESIGN CRITERIA CORRECT UNDER THIS PERMIT. THE
 PRODUCT APPROVALS CAN BE SUPPLIED WITH THE HOOD PERMIT
 AND DESIGN.
  
 1C) NEW COMMENT, THERE IS NO INFORMATION AS TO THE ROOF
 TOP PENETRATIONS TYPE OF ROOF FRAMING, TYPE OF DECK,
 AND IF ADDITIONAL FRAMING WILL BE REQUIRED FOR THE
 ANCHORING OF ROOF CURBS AND ROOF TOP A/C STANDS.
 107.2.1.3 COMPONENTS AND CLADDING.
  
 SHOW COMPLIANCE WITH: WIND DESIGN, A PARTIAL DESIGN IS
 GIVEN 170 MPH. WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C/ 1609.3 WIND
 SPEED CONVERSION
  
 1B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1C) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES NO APPROVALS
 WERE SUBMITTED.
 (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP FANS & CURBS.
  
 THE SUBMITTED A/C STAND PRODUCT APPROVAL IS FROM THE
 2007 FBC UNDER RULE 9B-72 AND IS A COPY. PLEASE NOTE
 THIS ADMINISTRATIVE RULE HAS BEEN CHANGED TO 9N-3 NOV.
 01/2010. PLEASE UPDATE THE PRODUCT APPROVAL TO ONE THAT
 HAS CURRENT APPROVAL.
  
 D) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2) 2ND REQUEST. THE DESIGNER OF RECORD HAS JUST COPIED
 THE REQUIREMENTS OF THE CODE SECTIONS LISTED BELOW, NOT
 SHOWN COMPLIANCE. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 1ST REVIEW COMMENT. SHEET A-1 NEEDS TO SHOW COMPLIANCE
 WITH 2010 FBC-B 1210.1 AND 1210.2.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 11:17 Rev Time  
Received By jwitmer Date 2015-06-25 Time   Sent To  
Notes
2015-06-25 11:17:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060392
 ADD: 638 BELVEDERE RD.
 CONT: EXCEL GENERAL CONSTRUCTION
 TEL: (305)984-3488
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 25/2015
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEET DOES NOT SHOW ANY INTAKE NOR
 EXHAUST UNITS. SHEET H-1 DOES SHOW ATTACHMENT CURB
 DETAILS FOR THE EXHAUST FAN.
 1A) THERE ARE MULTIPLE TYPE OF FASTENERS PROVIDED ON
 THE PLANS WITH THE USE OF THE WORD "OR", THE PLANS NEED
 TO BE SPECIFIC TTO THE TYPE OF FASTENER. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 1B) SHOW COMPLIANCE WITH: WIND DESIGN, A PARTIAL DESIGN
 IS GIVEN 170 MPH. WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C/ 1609.3 WIND
 SPEED CONVERSION
  
 1B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP FANS
  
 D) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) SHEET A-1 NEEDS O SHOW COMPLIANCE WITH 2010 FBC-B
 1210.1 AND 1210.2.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-18 Cont ID  
Sent By albarran Date 2015-12-18 Time 12:01 Rev Time 0.00
Received By albarran Date 2015-12-18 Time 10:38 Sent To I
Notes
2015-12-18 12:02:35ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 19:01 Rev Time 0.00
Received By albarran Date 2015-10-28 Time 17:55 Sent To I
Notes
2015-10-28 19:02:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. CORRECT CONDUCTOR INSULATION NOTE. CONDITIONS AND
 NOT SIZING DICTATE CONDUCTOR INSULATION REQUIREMENTS.
 2. FBC-ENERGY CONSERVATION CODE SECTION 502.3.8
 RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND SEALED TO REDUCE
 TRANSMISSION OF AIR BETWEEN IT AND THE CEILING SURFACE.
 3. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET BY EVERY PEDESTRIAN ENTRYWAY TO EVERY COMMERCIAL
 ESTABLISHMENT.
 4. FBC-E SECTION 505.2.1 REQUIRES THAT LIGHTING BE
 INDEPENDENTLY CONTROLLED WITH THE SPACE.
 5. ALL LUMINAIRES ON THE SUSPENDED CEILING SHALL BE
 SUPPORTED AS INDICATED IN NEC 410.32.
 6. ALL LUMINAIRE OUTLETS ON WALLS OR CEILINGS SHALL
 ABIDE BY THE REQUIREMENTS OF NEC 314.27.
 7. MARK THE LOCATION OF THE RESTROOM, KITCHEN AND ALL
 OTHER ROOMS WITHIN THE PREMISES.
 8. PANEL A INDICATES TO BE IN THE HALLWAY, YET THE
 FLOOR PLAN SHOWS IT ON THE REA WALL. CORRECT THE
 LOCATION ACCORDINGLY AND IF NOT ON THE REAR WALL,
 INSTALL THE REQUIRED DISCONNECT FOR THE WATER HEATER AS
 INDICATED BY NEC 422.31(B).
 9. PROVIDE SPEC SHEETS FOR ALL PROPOSED EQUIPMENT:
 CONDENSING UNITS EXHAUST & SUPPLY FANS AS WELL AS ALL
 PERMANENTLY INSTALLED ELECTRICAL EQUIPMENT.
 10. FLOOR PLANS AND EQUIPMENT LAYOUT DIFFERS FROM
 SHEETS A-1, E-1 & H-1. CORRECT TO MATCH.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
  
 WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED BY THE
 STANDARD CITY RE-SUBMITTAL FORM.
  
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By albarran Date 2015-07-17 Time 09:16 Rev Time 0.00
Received By albarran Date 2015-07-17 Time 08:37 Sent To I
Notes
2015-07-17 09:43:59PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. 2010 FBC-E SECTION 505 HAS MANDATORY LIGHTING
 REQUIREMENTS WHICH SHALL BE COMPLIED WITH.
 2. 2008 NEC 220.88 HAS LOAD CALCULATION REQUIREMENTS
 FOR NEW RESTAURANTS. PROVIDE LOAD CALCS.
 3. 2010 FBC-# 505.5.3 HAS SPECIFIC LIGHT DENSITY
 REQUIREMENTS WHICH SHALL BE ADHERED TO.
 4. 2008 NEC 210.63 REQUIRES A SERVICE OUTLET WITHIN 25'
 OF HVAC CONDENSING UNITS. PROVIDE A ROOF ELECTRIC
 DRAWING SHOWING COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-10 Cont ID  
Sent By pleduc Date 2015-12-10 Time   Rev Time 0.00
Received By pleduc Date 2015-12-10 Time 15:47 Sent To  
Notes
2015-12-10 15:55:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 SHEET H.1 - THE HOOD AND SUPPRESSION SYSTEM SHALL BE
 PERMITTED UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-12 Cont ID  
Sent By pleduc Date 2015-06-12 Time   Rev Time 0.00
Received By pleduc Date 2015-06-12 Time 13:18 Sent To  
Notes
2015-06-12 13:53:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE HOOD AND SUPPRESSION SYSTEM SHALL BE PERMITTED
 UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-18 Cont ID  
Sent By albarran Date 2015-12-18 Time 12:02 Rev Time 0.00
Received By albarran Date 2015-12-08 Time 10:42 Sent To  
Notes
2015-12-18 12:05:5112/18/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA PHONE MESSAGE ION LIEU OF MISSING EMAIL ADDRESS.
 SENT TO SMALL READY BIN ":E". MA
2015-12-09 10:42:35C23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 19:04 Rev Time 0.00
Received By albarran Date 2015-08-19 Time 14:24 Sent To  
Notes
2015-10-28 19:04:4310/28/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 WILL CALL IN 10/29/15 TO INQUIRE ON STATUS. SENT TO
 SMALL DENIED BIN "E". MA
2015-08-19 14:24:29C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-17 Cont ID  
Sent By albarran Date 2015-07-17 Time 09:48 Rev Time  
Received By albarran Date 2015-06-10 Time   Sent To  
Notes
2015-07-17 09:47:587/17/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA PHONE CALL. SENT TO SMALL DENIED BIN "E". MA
2015-06-11 10:44:02SENT TO C-17.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-11 Cont ID  
Sent By jwitmer Date 2015-06-11 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2015-06-11 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-16 Cont ID  
Sent By ccole Date 2015-12-16 Time 16:43 Rev Time 0.00
Received By ccole Date 2015-12-16 Time 16:43 Sent To  
Notes
2015-12-18 07:27:25PLAN NOTES, 12/17/15
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD,
 HOOD FIRE SUPPRESSION SYSTEM, AND WALK-IN COOLER AND
 FREEZER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-01 Cont ID  
Sent By ccole Date 2015-09-01 Time 08:36 Rev Time 0.00
Received By ccole Date 2015-09-01 Time 08:35 Sent To  
Notes
2015-09-01 08:41:032ND REVIEW: FBC 2010 MECHANICAL
 9/1/2015
  
 1) THE COMMENTS FROM THE1ST REVIEW PRINTED BELOW STILL
 EXIST. PLEASE COMPLY:
  
 1ST REVIEW: FBC 2010 MECHANICAL
 7/9/15
  
 1) THE CITY OF WPB CONSTRUCTION SERVICES DEPT. REQUIRES
 SEPARATE PERMITS FOR COMMERCIAL KITCHEN HOODS AND
 ASSOCIATED FIRE SUPPRESSION SYSTEMS, AND WALK-IN
 COOLERS AND FREEZERS. PLEASE PLACE NOTES ON THE PLAN
 ACCORDINGLY.
 2) SHOW COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL
 FOR MINIMUM EXHAUST VENTILATION RATE IN THE KITCHEN-
 0.7 CFM PER S.F., AND MINIMUM O/A RATE FOR OCCUPANTS IN
 THE DINING AREA. PLEASE NOTE THAT NO MEANS OF
 VENTILATION IS SHOWN ON THE PLAN FOR THE KITCHEN AREA.
 PROVIDE AN AIR BALANCE CALCULATION ON THE PLAN FOR THE
 ENTIRE OCCUPANCY.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By ccole Date 2015-07-09 Time 08:36 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 12:34 Sent To  
Notes
2015-07-09 13:07:031ST REVIEW: FBC 2010 MECHANICAL
 7/9/15
  
 1) THE CITY OF WPB CONSTRUCTION SERVICES DEPT. REQUIRES
 SEPARATE PERMITS FOR COMMERCIAL KITCHEN HOODS AND
 ASSOCIATED FIRE SUPPRESSION SYSTEMS, AND WALK-IN
 COOLERS AND FREEZERS. PLEASE PLACE NOTES ON THE PLAN
 ACCORDINGLY.
 2) SHOW COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL
 FOR MINIMUM EXHAUST VENTILATION RATE IN THE KITCHEN-
 0.7 CFM PER S.F., AND MINIMUM O/A RATE FOR OCCUPANTS IN
 THE DINING AREA. PLEASE NOTE THAT NO MEANS OF
 VENTILATION IS SHOWN ON THE PLAN FOR THE KITCHEN AREA.
 PROVIDE AN AIR BALANCE CALCULATION ON THE PLAN FOR THE
 ENTIRE OCCUPANCY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-27 Cont ID  
Sent By skennedy Date 2015-09-27 Time 11:12 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 11:12 Sent To  
Notes
2016-01-27 11:13:56I REVIEWED THE PERMIT SET OF PLANS AND FOUND THAT
 TKLARGE APPROVED THE GAS BY STAMPING THE PLAN ON
 9/5/15. SAKENNEDY
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 05:37 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 04:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By tklarge Date 2015-07-10 Time 06:52 Rev Time 0.00
Received By tklarge Date 2015-07-10 Time 05:18 Sent To  
Notes
2015-07-10 06:51:291) SHT. A-1 - EQUIPMENT SCHEDULE SHOWS ITEM #3 ( WORK
 TABLE) AS GAS BUT THERE IS NO BTU LOAD SHOWN. CLARIFY.
 2) THE SMOKEHOUSE IS SHOWN AS 60,000 BTU'S ON THE GAS
 RISER BUT THE SCHEDULE ON A-1 SHOWS 75,000 BTU'S.
 CLARIFY.
 3) THE RICE COOKER IS SHOWN AS 31,200 BTU'S ON THE
 SCHEDULE BUT THE GAS RISER SHOWS 30,000 BTU'S. CLARIFY.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. THE SPECIFICATIONS SHALL SHOW THAT THE GAS
 EQUIPMENT IS LISTED AND LABELED PER 2010 FBC-FUEL GAS
 SEC.301.3.
 5) INDICATE THE DELIVERY PRESSURE OF THE GAS SYSTEM ON
 THE PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) INDICATE ON THE PLANS THE TYPE OF PIPE BEING
 INSTALLED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 7) SHT. P-1 - SIZE EACH SECTION OF PIPE THAT SUPPLIES
 THE DEEP FRYERS. COMPLY WITH FGC SEC. 402.
 8) THE TOTAL BTU LOAD OF THE APPLIANCES SHOWN ON THE
 EQUIPMENT SCHEDULE DOES NOT CORRELATE WITH THE BTU LOAD
 YOU HAVE SHOWN ON SHT. P-1. CLARIFY.
 9) THERE IS A NOTE ON SHT. P-1 FOR THE GAS THAT READS
 "NAT GAS TB 403 <2>. I HAVE NO IDEA WHAT THIS RELATES
 TO. CLARIFY.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S SPEC SHEETS
 FOR THE TANKLESS WATER HEATER. THE PLANS NOTE THIS AS A
 RESIDENTIAL UNIT.
 11) SEDIMENT TRAPS SHALL BE INSTALLED IN THE GAS LINE
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE PER 2010 FGC
 SEC. 408.4.
 12) SHT. A-1 - LOAD CALCULATION TABLE SHOWS A GREASE
 INTERCEPTOR CALCULATION THAT MAKES NO SENSE. CLARIFY.
 CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH 2010
 FBC-PLUMBING, TABLE 1003.5.1 FOR SIZING AND
 SECS.1003.3.4 OR F.A.C. 64E-6 AND FPC SEC.1003.5.1,
 1003.5.2 & 1003.5.3. SUBMIT COMPLETE DETAILS FOR THE
 INTERCEPTOR SHOWING CCOMPLIANCE. SUBMIT SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTOR.
 13) SHOW THE LOCATION OF THE GREASE INTERCEPTOR ON THE
 PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) THE INTERCEPTORR SHALL BE EQUIPPED WITH A SAMPLING
 PORT ON THE DISCHARGE LINE. CONTACT KELLY CRANFORD AT
 561-494-1040 IN THE ENGINEERING DEPT.FOR DETAILS.
 15) SUBMIT DETAILS FOR MEANS OF CONTROLLING THERMAL
 EXPANSION WITHIN THE HOT WATER SYSTEM PER 2010 FPC SEC.
 607.3.L
 A THOROUGH REVIEW COULD NOT BE PERFORMED DUE TO THE
 LACK OF SUFFICIENT INFORMATION.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By llouie Date 2015-12-11 Time 13:05 Rev Time 0.00
Received By llouie Date 2015-12-11 Time 13:05 Sent To  
Notes
2015-12-11 13:06:01INTERIOR BUILD-OUT ONLY. RESTAURANT USE PERMITTED IN
 GC.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-24 Cont ID  
Sent By llouie Date 2015-06-24 Time 09:06 Rev Time 0.00
Received By llouie Date 2015-06-24 Time 08:21 Sent To  
Notes
2015-06-24 09:06:46INTERIOR BUILD OUT. ONLY GC USES PERMITTED BY RIGHT
 ALLOWED.