| 2015-06-26 15:36:12 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060362 |
| | ADD: 2210 N. AUSTRALIAN AVE. |
| | CONT: MONROE CONTRACTING |
| | TEL: (561)455-6600 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 26/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A-1.0, BUILDING CODE SUMMARY: |
| | 1A) IT IS UNCLEAR IF THIS IS A CHANGE OF OCCUPANCY OR |
| | NOT. WHAT WAS THE USE FOR THIS SPACE BEFORE THE |
| | SUBMISION OF PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. THE CODE SUMMARY INDICATES THIS SPACE WAS |
| | UNFINISHED BUT SHEET A-1.1 ALSO INDICATES AN EXISTING |
| | 3'-0" SAW CUT AND UNFINISHED GRADE. WHAT WAS THE LAST |
| | KNOWN USE. |
| | |
| | 1B) THE COVERSHEET INDICATES THIS PROJECT IS LOCATED IN |
| | AN ASSISSTED LIVING FACILITY, BUT THE PLANS DO NOT |
| | REFLECT THE BUILDING AS A MIXED USE OCCUPANCY BETWEEN |
| | I-2 & A-2. |
| | |
| | 1C) TYPE OF CONSTRUCTION IS INDICATED AS BUILDING TYPE |
| | VB. THE ASSISTED LIVING IS CONSIDERED AN 1-2 OCCUPANCY. |
| | PLEASE REFER TO THE 2010 FBC-B TABLE 503 FOR A 6 STORY |
| | BUILDING AS A I-2 OCCUPANCY THE MINIMUM BUILDING TYPE |
| | IS A I-A NOT V-B. |
| | |
| | 1D) THE BUILDING CODE SUMMARY ALSO INDICATES THE ADA |
| | (AMEREICANS WITH DISIBILITY ACT) AS THE CODE IN AFFECT. |
| | PLEASE NOT THE FLORIDA 2010 ACCESSIBILITY CODE HAS BEEN |
| | APPROVED BY THE DEPARTMENT OF JUSTICE, THE FLORIDA |
| | ACCESSIBILITY CODE HAS THE ADA, IN THE FLORIDA CODE, |
| | THE GREY BOXES ARE FLORIDA SPECIFIC AMENDMENTS TO THE |
| | ADA. |
| | |
| | 1E) OCCUPANT LOADS, PLEASE REVIEW STORAGE AN ACCESSORY |
| | USE OF 592 SQ. FT. / 300 GROSS= 2 OCCUPANTS. 2010 FBC-B |
| | TABLE 1004.1.1. |
| | |
| | 2) SHEET A-1.1 DEMOLITION PLAN. |
| | 2A) THE CBS WINDOW INFILL DETAIL, SHOWS THE BOTTOM |
| | CLEAN OUTS AND KNOCK OUT HOLES IN THE 2ND COURSE OF |
| | BLOCK FROM THE TOP COURSE OF BLOCK, HOW IS THE GROUT |
| | GOING TO FILL THE UPPER BLOCK WORK. THE UPPER 1/2 OF |
| | THE TOP COURSE OF BLOCK SHOULD BE WHERE THE GROUT |
| | ENTERS THE BLOCK INFILL. THIS WAY THE REINFORCING GETS |
| | THE GROUT COMPLETELY AROUND ENCASING THE REINFORCING |
| | BARS AND THE LAP SPLICE. |
| | 2010 FBC-B 2108.2 & ACI 530/ASCE 5.3.3.3.3 DEVELOPMENT. |
| | |
| | 2B) ON THE NORTH SIDE OF THE BUILDING BETWEEN GRID |
| | LINES 4 & 5 THE PLANS SHOW A INFILL OF A WINDOW WHERE |
| | AS SHEET A1.2 ON THE SAME GRID LINE 4/ 5 THE PLANS SHOW |
| | A SET OF OUTSWING DOORS. DISCREPANCY IN PLANS. |
| | 107.2.1.3 ADDITIONAL INFOMATION IS REQUIRED. THESE |
| | WOULD BE THE 2ND SET OF REQUIRED EXIT DOORS FROM THIS |
| | ROOM SINCE THE OCCUPANCY LOAD IS GREATERE THAN 49 |
| | OCCUPANTS. 2010 FBC-B TABLE 1015.1. |
| | |
| | 3) SHEET A-1.2: |
| | 3A) PLEASE NOTE THIS APPEARS TO BE A MIXED USE |
| | OCCUPANCY, AGAIN THE CODE SUMMARY DOES NOT STATE WHAT |
| | TYPE OF OCCUPANCY IS ON THE OTHER END OF THE BUILDING |
| | AND THIS SHEET DOES NOT SHOW WHERE THE OCCUPANCY |
| | SEPARATION WALL IS LOCATED. 2010 FBC-B TABLE 508.4. IF |
| | THIS IS A I-2 OCCUPANCY A 2 HR FIRE SEPARATION IS |
| | REQUIRED. |
| | |
| | 3B) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-1.4 THE |
| | LIFE SAFETY PLAN SHOW WALL IDENTIFICATION TAGS, SHEET |
| | A-2.2 DOES IDENTIFY WALL TYPES, PLEASE LABLE THE WALLS |
| | ON EITHER OF THE SHEETS LISTED ABOVE SO CODE COMPLIANCE |
| | CAN BE ACHIEVED. 2010 FBC-B TABLE 508.4, FBC-B 1022.1 |
| | 1023.1 & 1023.3. |
| | |
| | 3D) PLEASE REVIEW DOOR 124 AND DOOR 125, BOTH THESE |
| | DOORS BLOCK, OR EMPEDE EGRESS INTO THE EXIT PASSAGEWAY. |
| | 1008.1.9.11 DOORS SHALL LEAVE UNOBSTRUCTED AT LEAST 1/2 |
| | OF THE REQUIRED WIDTH OF THE REQUIRED PASSAGEWAY. |
| | |
| | 3E) THE BACK VERTICAL EXIT AND EXIT PASSAGEWAY |
| | EXTENSION SHOW A ROOM AND DOOR MARKED 126. WHAT IS THIS |
| | ROOM USED FOR, WHILE IN A EXIT PASSAGEWAY. 2010 FBC-B |
| | 1023.1 AN EXIT PASSAGEWAY SHALL NOT BE USED FOR ANY |
| | PURPOSE OTHER THAN AS A MEANS OF EGRESS. |
| | SEE FBC-B 1023.3 CONSTRUCTION, 2 HR MINIMUM/ SHAFT |
| | RATED 2 HRS > 4 TORIES IN HEIGHT. FBC-B 1023.5 OPENINGS |
| | SHALL BE LIMITED TO THOSE NECESSARY FOR AN EXIT ACCESS |
| | TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED SPACES |
| | FOR EGRESS FROM THE EXIT PASSAGEWAY. |
| | |
| | 3F) PLEASE REVIEW THE DOOR SCHEDULE FOUND ON SHEET |
| | A-1.3 DOORS 124 & 125 SHOULD BE 90 MINUTE PER FBC-B |
| | TABLE 715.5. DOOR # 126 SHOULD BE ELIMINATED FROM THE |
| | EXIT PASSAGE WAY 2010 FBC-B 1023.5. DOOR # 100 APPEARS |
| | THIS MAYBE BECOME THE OCCUPANCY SEPARATION WALL (2 HR |
| | WALL/ 1 1/2 HR OPENING PROTECTIVE) PER TABLE 715.5. |
| | |
| | 3G) THE PLANS DO NOT MENTION IN THE CODE SUMMARY OF THE |
| | COVERSHEET NOR SHEET A-1.2 OR A-1.4 THE 2ND FLOOR/ |
| | CEILING ASSEMBLY RATING |
| | IN COMPLIANCE WITH FIRE BARRIERS OR HORIZONTAL |
| | ASSEMBLIES BETWEEN FIRE AREAS. 2010 FBC-B 707.3.9 & |
| | TABLE 707.3.9. |
| | |
| | 3H) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-1.4 THE |
| | LIFE SAFETY PLAN SHOW COMPLIANCE WITH THE 2010 |
| | FBC-ACCESSIBILITY 221.2.1 & TABLE 221.2.1. |
| | |
| | 3I) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-5.1 THE |
| | ACCESSIBILITY DETAIL SHEET PROVIDE CODE COMPLIANCE FOR |
| | FBC-ACCESSIBILITY 902.3 HEIGHT FOR TOPS OF DINING |
| | SURFACES. |
| | |
| | 4) THERE ARE NO PLANS SHOWING THE INFILL OF THE 1ST |
| | FLOOR (ASSUMED CONCRETE) AND COMPLIANCE WITH: |
| | 4A) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B TERMITE |
| | TRATMENT OF SLABS & 6 MILL VAPOR BARRIER. |
| | |
| | 4B) THE MINIMUM SLAB PROVISONS 31/2 INCHES & 6 MIL |
| | VAPOR BARIER. |
| | |
| | 4C) SLAB REINFORCING PER 2010 FBC-B 1910.2(2) 6X6 W1.4 |
| | X W1.4 WELDED WIRE REINFORCEMENT, IN THE MIDDLE TO |
| | UPPER 1/3RD OF SLAB, SUPPORTED EVERY 3 FEET OR IN |
| | ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. |
| | |
| | 4D) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-ENERGY |
| | CODE EITHER TABLE 502.1.1.1(1) WALLS >R30 OR TABLE |
| | 502.1.1.1(2) WALLS >R19. SHEET A-2.2 DETAIL F INDICATES |
| | THE USE OF ICYNENE TO ACHIEVE A R VALUE OF R11.62 IN A |
| | 1 1/2 CAVITY. PLEASE ALSO PROVIDE THE MANUFACTURERS |
| | TEST MATERIAL AND INSTALATION GUIDE FOR THIS PRODUCT, |
| | 2010 FBC-B 2603.5. SHALL COMPLY WITH 2603.5.1-2603.5.7. |
| | |
| | 4E) PLANS ARE LACKING THE WIND DESIGN CRITERIA FOR THE |
| | NEW EXTERIOR COMPONENTS AND CLADDING ELEMENTS. 2010 |
| | FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 |
| | OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 4E)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4E)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 4E)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4E)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4E)(5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) WALL LOUVERS, |
| | (G) EXTERIOR WALL MOUNTED EXHAUST FANS |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) SHEET A-1.4 THE LIFE SAFETY; |
| | 7A) THE PLAN DOES NOT SHOW COMPLIANCE WITH EXIT |
| | DIRECTIONAL SIGNAGE, EXIT SIGNS PER 2010 FBC-B |
| | 1006.3.1, 106.3.2 VIEWING DISTANCE NOT GREATER THAN 100 |
| | FT. |
| | |
| | 7B) MISSING BATTERY BACK UP FBC-B 1006.1.6.2. |
| | |
| | 7C) PLEASE PROVIDE TACTILE SIGNAGE FBC-B 1006.3.4 & |
| | ACCESSIBILITY CODE 703.2 RAISED CHARACTERS, 703.3 |
| | BRAILLE & 703.4 .1 HEIGHT ABOVE THE FINISH FLOOR. |
| | |
| | 7D) THIS IS A NEW DINING & KITCHEN FACILITY. WITH THE |
| | NEW GAS APPLIANCES BEING INTRODUCED INTO THE BUILDING |
| | AND THE REMAINDER OF THE I-2 SLEEPING ROOMS WILL NEED |
| | TO SHOW COMPLIANCE WITH FBC-B 916.1 , & 916.1.1THE |
| | EXCEPTIONS DO NOT APPLY UNDER THE 2010 EXISTING |
| | BUILDING CODE SEE 912.2 FIRE ALARM AND DETECTION. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |