Plan Review Details - Permit 15060362
Plan Review Stops For Permit 15060362
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-19 Cont ID  
Sent By skennedy Date 2015-11-19 Time 10:40 Rev Time 0.00
Received By skennedy Date 2015-11-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-03 Cont ID  
Sent By jwitmer Date 2015-11-03 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2015-11-03 Time 06:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 16:38 Sent To  
Notes
2015-10-02 13:56:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060362
 ADD: 2210 N. AUSTRALIAN AVE.
 CONT: MONROE CONTRACTING
 TEL: (561)455-6600
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT.02/2015
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) SHEET A-1.2:
  
 3A-3D) COMPLIED
  
 3E) 2ND REQUEST. THE BACK VERTICAL EXIT AND EXIT
 PASSAGEWAY EXTENSION SHOW A ROOM AND DOOR MARKED 126.
 WHAT IS THIS ROOM USED FOR, WHILE IN A EXIT PASSAGEWAY.
 2010 FBC-B 1023.1 AN EXIT PASSAGEWAY SHALL NOT BE USED
 FOR ANY PURPOSE OTHER THAN AS A MEANS OF EGRESS.
 SEE FBC-B 1023.3 CONSTRUCTION, 2 HR. MINIMUM/ SHAFT
 RATED 2 HRS. > 4 STORIES IN HEIGHT. FBC-B 1023.5
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR AN
 EXIT ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY
 OCCUPIED SPACES FOR EGRESS FROM THE EXIT PASSAGEWAY.
  
 3F) 2ND REQUEST. PLEASE REVIEW THE DOOR SCHEDULE FOUND
 ON SHEET A-1.3 DOORS 124 & 125 SHOULD BE 90 MINUTE PER
 FBC-B TABLE 715.5. DOOR # 126 SHOULD BE ELIMINATED FROM
 THE EXIT PASSAGE WAY 2010 FBC-B 1023.5. DOOR # 100
 APPEARS THIS MAYBE BECOME THE OCCUPANCY SEPARATION WALL
 (2 HR. WALL/ 1 1/2 HR. OPENING PROTECTIVE) PER TABLE
 715.5.
  
 3G) 2ND REQUEST. THE PLANS DO NOT MENTION IN THE CODE
 SUMMARY OF THE COVERSHEET NOR SHEET A-1.2 OR A-1.4 THE
 2ND FLOOR/ CEILING ASSEMBLY RATING IN COMPLIANCE WITH
 FIRE BARRIERS OR HORIZONTAL ASSEMBLIES BETWEEN FIRE
 AREAS. 2010 FBC-B 707.3.9 & TABLE 707.3.9. RESPONSE
 INDICATES SEE REVISED CODE SUMMARY COVERSHEET.
 HORIZONTAL OCCUPANCY IS NOT SHOWN. NOTE TABLE 721.3.2
 EQUIVALENT THICKNESS OF CONCRETE SHOWS 5 INCHES OF
 LIMESTONE BASED CONCRETE EQUALS A 3 HOUR RATING.
  
 3H-3I) COMPLIED
  
 4-4D) COMPLIED
  
 4E) 2ND REQUEST. THE LISTED CRITERIA IS WHAT IS NEEDED
 TO DETERMINE THE PRESSURES FOR THE NEW WINDOWS AND DOOR
 PRESSURES. PLANS ARE LACKING THE WIND DESIGN CRITERIA
 FOR THE NEW EXTERIOR COMPONENTS AND CLADDING ELEMENTS.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4E)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4E)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4E)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4E)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4E)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) 2ND REQUEST, UNTIL THE WIND DESIGN CRITERIA IS KNOWN
 AND THE PRESSURES, POSITIVE AND NEGATIVE ARE KNOWN THE
 PRODUCT APPROVALS CAN NOT BE REVIEWED FOR CODE
 COMPLIANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) WALL LOUVERS,
 (G) EXTERIOR WALL MOUNTED EXHAUST FANS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) COMPLIED. SHEET A-1.4 THE LIFE SAFETY;
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 10:15 Rev Time  
Received By jwitmer Date 2015-06-25 Time 16:15 Sent To  
Notes
2015-06-26 15:36:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060362
 ADD: 2210 N. AUSTRALIAN AVE.
 CONT: MONROE CONTRACTING
 TEL: (561)455-6600
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 26/2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0, BUILDING CODE SUMMARY:
 1A) IT IS UNCLEAR IF THIS IS A CHANGE OF OCCUPANCY OR
 NOT. WHAT WAS THE USE FOR THIS SPACE BEFORE THE
 SUBMISION OF PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. THE CODE SUMMARY INDICATES THIS SPACE WAS
 UNFINISHED BUT SHEET A-1.1 ALSO INDICATES AN EXISTING
 3'-0" SAW CUT AND UNFINISHED GRADE. WHAT WAS THE LAST
 KNOWN USE.
  
 1B) THE COVERSHEET INDICATES THIS PROJECT IS LOCATED IN
 AN ASSISSTED LIVING FACILITY, BUT THE PLANS DO NOT
 REFLECT THE BUILDING AS A MIXED USE OCCUPANCY BETWEEN
 I-2 & A-2.
  
 1C) TYPE OF CONSTRUCTION IS INDICATED AS BUILDING TYPE
 VB. THE ASSISTED LIVING IS CONSIDERED AN 1-2 OCCUPANCY.
 PLEASE REFER TO THE 2010 FBC-B TABLE 503 FOR A 6 STORY
 BUILDING AS A I-2 OCCUPANCY THE MINIMUM BUILDING TYPE
 IS A I-A NOT V-B.
  
 1D) THE BUILDING CODE SUMMARY ALSO INDICATES THE ADA
 (AMEREICANS WITH DISIBILITY ACT) AS THE CODE IN AFFECT.
 PLEASE NOT THE FLORIDA 2010 ACCESSIBILITY CODE HAS BEEN
 APPROVED BY THE DEPARTMENT OF JUSTICE, THE FLORIDA
 ACCESSIBILITY CODE HAS THE ADA, IN THE FLORIDA CODE,
 THE GREY BOXES ARE FLORIDA SPECIFIC AMENDMENTS TO THE
 ADA.
  
 1E) OCCUPANT LOADS, PLEASE REVIEW STORAGE AN ACCESSORY
 USE OF 592 SQ. FT. / 300 GROSS= 2 OCCUPANTS. 2010 FBC-B
 TABLE 1004.1.1.
  
 2) SHEET A-1.1 DEMOLITION PLAN.
 2A) THE CBS WINDOW INFILL DETAIL, SHOWS THE BOTTOM
 CLEAN OUTS AND KNOCK OUT HOLES IN THE 2ND COURSE OF
 BLOCK FROM THE TOP COURSE OF BLOCK, HOW IS THE GROUT
 GOING TO FILL THE UPPER BLOCK WORK. THE UPPER 1/2 OF
 THE TOP COURSE OF BLOCK SHOULD BE WHERE THE GROUT
 ENTERS THE BLOCK INFILL. THIS WAY THE REINFORCING GETS
 THE GROUT COMPLETELY AROUND ENCASING THE REINFORCING
 BARS AND THE LAP SPLICE.
 2010 FBC-B 2108.2 & ACI 530/ASCE 5.3.3.3.3 DEVELOPMENT.
  
 2B) ON THE NORTH SIDE OF THE BUILDING BETWEEN GRID
 LINES 4 & 5 THE PLANS SHOW A INFILL OF A WINDOW WHERE
 AS SHEET A1.2 ON THE SAME GRID LINE 4/ 5 THE PLANS SHOW
 A SET OF OUTSWING DOORS. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFOMATION IS REQUIRED. THESE
 WOULD BE THE 2ND SET OF REQUIRED EXIT DOORS FROM THIS
 ROOM SINCE THE OCCUPANCY LOAD IS GREATERE THAN 49
 OCCUPANTS. 2010 FBC-B TABLE 1015.1.
  
 3) SHEET A-1.2:
 3A) PLEASE NOTE THIS APPEARS TO BE A MIXED USE
 OCCUPANCY, AGAIN THE CODE SUMMARY DOES NOT STATE WHAT
 TYPE OF OCCUPANCY IS ON THE OTHER END OF THE BUILDING
 AND THIS SHEET DOES NOT SHOW WHERE THE OCCUPANCY
 SEPARATION WALL IS LOCATED. 2010 FBC-B TABLE 508.4. IF
 THIS IS A I-2 OCCUPANCY A 2 HR FIRE SEPARATION IS
 REQUIRED.
  
 3B) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-1.4 THE
 LIFE SAFETY PLAN SHOW WALL IDENTIFICATION TAGS, SHEET
 A-2.2 DOES IDENTIFY WALL TYPES, PLEASE LABLE THE WALLS
 ON EITHER OF THE SHEETS LISTED ABOVE SO CODE COMPLIANCE
 CAN BE ACHIEVED. 2010 FBC-B TABLE 508.4, FBC-B 1022.1
 1023.1 & 1023.3.
  
 3D) PLEASE REVIEW DOOR 124 AND DOOR 125, BOTH THESE
 DOORS BLOCK, OR EMPEDE EGRESS INTO THE EXIT PASSAGEWAY.
 1008.1.9.11 DOORS SHALL LEAVE UNOBSTRUCTED AT LEAST 1/2
 OF THE REQUIRED WIDTH OF THE REQUIRED PASSAGEWAY.
  
 3E) THE BACK VERTICAL EXIT AND EXIT PASSAGEWAY
 EXTENSION SHOW A ROOM AND DOOR MARKED 126. WHAT IS THIS
 ROOM USED FOR, WHILE IN A EXIT PASSAGEWAY. 2010 FBC-B
 1023.1 AN EXIT PASSAGEWAY SHALL NOT BE USED FOR ANY
 PURPOSE OTHER THAN AS A MEANS OF EGRESS.
 SEE FBC-B 1023.3 CONSTRUCTION, 2 HR MINIMUM/ SHAFT
 RATED 2 HRS > 4 TORIES IN HEIGHT. FBC-B 1023.5 OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR AN EXIT ACCESS
 TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED SPACES
 FOR EGRESS FROM THE EXIT PASSAGEWAY.
  
 3F) PLEASE REVIEW THE DOOR SCHEDULE FOUND ON SHEET
 A-1.3 DOORS 124 & 125 SHOULD BE 90 MINUTE PER FBC-B
 TABLE 715.5. DOOR # 126 SHOULD BE ELIMINATED FROM THE
 EXIT PASSAGE WAY 2010 FBC-B 1023.5. DOOR # 100 APPEARS
 THIS MAYBE BECOME THE OCCUPANCY SEPARATION WALL (2 HR
 WALL/ 1 1/2 HR OPENING PROTECTIVE) PER TABLE 715.5.
  
 3G) THE PLANS DO NOT MENTION IN THE CODE SUMMARY OF THE
 COVERSHEET NOR SHEET A-1.2 OR A-1.4 THE 2ND FLOOR/
 CEILING ASSEMBLY RATING
 IN COMPLIANCE WITH FIRE BARRIERS OR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS. 2010 FBC-B 707.3.9 &
 TABLE 707.3.9.
  
 3H) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-1.4 THE
 LIFE SAFETY PLAN SHOW COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY 221.2.1 & TABLE 221.2.1.
  
 3I) NEITHER SHEET A-1.2 THE FLOOR PLAN & NOR A-5.1 THE
 ACCESSIBILITY DETAIL SHEET PROVIDE CODE COMPLIANCE FOR
 FBC-ACCESSIBILITY 902.3 HEIGHT FOR TOPS OF DINING
 SURFACES.
  
 4) THERE ARE NO PLANS SHOWING THE INFILL OF THE 1ST
 FLOOR (ASSUMED CONCRETE) AND COMPLIANCE WITH:
 4A) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B TERMITE
 TRATMENT OF SLABS & 6 MILL VAPOR BARRIER.
  
 4B) THE MINIMUM SLAB PROVISONS 31/2 INCHES & 6 MIL
 VAPOR BARIER.
  
 4C) SLAB REINFORCING PER 2010 FBC-B 1910.2(2) 6X6 W1.4
 X W1.4 WELDED WIRE REINFORCEMENT, IN THE MIDDLE TO
 UPPER 1/3RD OF SLAB, SUPPORTED EVERY 3 FEET OR IN
 ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
  
 4D) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-ENERGY
 CODE EITHER TABLE 502.1.1.1(1) WALLS >R30 OR TABLE
 502.1.1.1(2) WALLS >R19. SHEET A-2.2 DETAIL F INDICATES
 THE USE OF ICYNENE TO ACHIEVE A R VALUE OF R11.62 IN A
 1 1/2 CAVITY. PLEASE ALSO PROVIDE THE MANUFACTURERS
 TEST MATERIAL AND INSTALATION GUIDE FOR THIS PRODUCT,
 2010 FBC-B 2603.5. SHALL COMPLY WITH 2603.5.1-2603.5.7.
  
 4E) PLANS ARE LACKING THE WIND DESIGN CRITERIA FOR THE
 NEW EXTERIOR COMPONENTS AND CLADDING ELEMENTS. 2010
 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6
 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4E)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4E)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4E)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4E)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4E)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) WALL LOUVERS,
 (G) EXTERIOR WALL MOUNTED EXHAUST FANS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A-1.4 THE LIFE SAFETY;
 7A) THE PLAN DOES NOT SHOW COMPLIANCE WITH EXIT
 DIRECTIONAL SIGNAGE, EXIT SIGNS PER 2010 FBC-B
 1006.3.1, 106.3.2 VIEWING DISTANCE NOT GREATER THAN 100
 FT.
  
 7B) MISSING BATTERY BACK UP FBC-B 1006.1.6.2.
  
 7C) PLEASE PROVIDE TACTILE SIGNAGE FBC-B 1006.3.4 &
 ACCESSIBILITY CODE 703.2 RAISED CHARACTERS, 703.3
 BRAILLE & 703.4 .1 HEIGHT ABOVE THE FINISH FLOOR.
  
 7D) THIS IS A NEW DINING & KITCHEN FACILITY. WITH THE
 NEW GAS APPLIANCES BEING INTRODUCED INTO THE BUILDING
 AND THE REMAINDER OF THE I-2 SLEEPING ROOMS WILL NEED
 TO SHOW COMPLIANCE WITH FBC-B 916.1 , & 916.1.1THE
 EXCEPTIONS DO NOT APPLY UNDER THE 2010 EXISTING
 BUILDING CODE SEE 912.2 FIRE ALARM AND DETECTION.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-19 Cont ID  
Sent By skennedy Date 2015-11-19 Time 10:42 Rev Time 0.00
Received By skennedy Date 2015-11-19 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 12:29 Rev Time 0.00
Received By albarran Date 2015-10-14 Time 11:42 Sent To I
Notes
2015-10-14 12:54:57ALL PREVIOUSLY MENTIONED DEFICIENCIES EXCEPT THE
 LIGHTING INSIDE THE WALK-IN COOLERS & FREEZERS HAVE
 BEEN ADDRESSED SATISFACTORILY. THE ITEM OF THE
 ADDITIONAL LIGHTING WILL BE LEFT TO THE INSPECTOR IN
 THE FIELD.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-21 Cont ID  
Sent By albarran Date 2015-07-21 Time 19:00 Rev Time 0.00
Received By albarran Date 2015-07-21 Time 17:02 Sent To I
Notes
2015-07-21 19:35:35PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.5 REQUIRES THAT THERE BE A SIGN OUTLET BY
 EVERY ENTRANCE, EXCEPT SERVICE HALLWAYS AND CORRIDORS.
 2. NEC 300.7 REQUIRES THAT RACEWAYS EXPOSED TO
 DIFFERENT TEMPERATURES BE SEALED TO PREVENT THE
 TRANSFER OF WARN AIR INTO THE COLD ENVIRONMENT.
 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS ON ALL
 PANEL OTHER THAN IN DWELLING UNITS.
 4 NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT
 ELECTRICAL EQUIPMENT. SUCH IS NOT INDICATED FOR
 EQUIPMENT/MECHANICAL ROOM 116.
 5. FBC-B 1006.2.1 EMERGENCY LIGHTING MAY BE REQUIRED
 INSIDE THE WALK IN COOLERS AND FREEZERS.
 6. THE EQUIPMENT/MECHANICAL ROOM 116 REFLECTS A DOOR
 ONLY IN THE ELECTRICAL PAGES, BUT NOT ON ANY OF THE "A"
 SHEETS. CORRECT THIS TO INDICATE THE PROPER DOOR AND
 SWING.
 7. PROVIDE A ROOF ELECTRICAL SHEET INDICATING THE
 LOCATION OF ALL ELECTRICAL EQUIPMENT INSTALLED ON THE
 ROOF.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2015-07-02 Cont ID  
Sent By cranford Date 2015-07-02 Time 11:15 Rev Time 0.00
Received By cranford Date 2015-07-02 Time 10:16 Sent To  
Notes
2015-07-02 11:15:52INTERNAL DEMOLITION AND CONSTRUCTION ONLY (PLUS WINDOWS
 AND DOORS). LAND STABILIZATION BOND NOT REQUIRED.
  
 KELLY CRANFORD, PE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-14 Cont ID  
Sent By pleduc Date 2015-09-14 Time   Rev Time 0.00
Received By pleduc Date 2015-09-14 Time 13:42 Sent To  
Notes
2015-09-14 14:38:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 SHEET HOOD; THE HOOD SYSTEM PLAN SHALL BE SUBMITTED
 UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-11 Cont ID  
Sent By pleduc Date 2015-06-11 Time   Rev Time 0.00
Received By pleduc Date 2015-06-11 Time 13:36 Sent To  
Notes
2015-06-11 13:56:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 1-1.0, THERE ARE INCORRECT REFERENCES TO THE
 FIRE CODE.
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) SHEET A-1.2, DOORS 125 & 126 OPEN INTO THE EXIT
 CORRIDOR, THOUGH EXISTING THEY ARE REQUIRED TO BE
 CORRECTED DUE TO THE NATURE AND EXTENT OF THE REMODEL.
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 3) PROVIDE A NOTE ACKNOWLEDGING THE FOLLOWING :
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) PROVIDE A NOTE ACKNOWLEDGING THE FOLLOWING.
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND HOOD VENTILATION SYSTEM SHOP
 DRAWINGS SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 5) SHEET A 1.3, THE DOOR SCHEDULE SHOW DOOR 124 WITH A
 LOCKSET. THE DOOR CAN NOT BE LOCKED AGAIST EGRESS. NO
 EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. ANY AND
 ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH CHAPTER
 7 OF THE FLORIDA FIRE PREVENTION CODE AND PRE-APPROVED
 (PRIOR TO INSTALLATION) BY THE BUREAU OF FIRE
 PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF FIRE
 PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2015-11-18 Cont ID  
Sent By gjohnson Date 2015-11-18 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2015-11-18 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 14:15 Sent To  
Notes
2015-10-29 15:11:42 
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1 .2ND REQUEST PLEASE SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 402.2 PER WPB AMEND. TO FBC
 SEC107.2.1.3
 2. SHEET P-1 SHOWS TANKLESS HEATER IN DIFFERENT
 LOCATION THAN SHEET P-3 IF LOCATION ON P-3 IS THE
 CORRECT LOCATION A NEW GAS AND WATER DIAGRAM WILL BE
 REQUIRED PLEASE CORRECT ALL SHEETS TO REFLECT THE SAME
 LOCATION AND RISER DIAGRAMS TO CORRELATE.
 PER WPB AMEND. TO FBC SEC 107.2.1
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-10-01 Cont ID  
Sent By tklarge Date 2015-10-01 Time 10:49 Rev Time 0.00
Received By tklarge Date 2015-10-01 Time 09:44 Sent To  
Notes
2015-10-01 10:19:001) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS
 LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3.
 2) SHT. P-2 - "COMBUSTION AIR REQUIREMENTS" NOTE AT
 BOTTOM OF BOX READS "PROVIDED 5902 CFM FROM HOOD SUPPLY
 FANS." THE HOOD SUPPLY FANS CANNOT BE USED TO SUPPLY
 COMBUSTION AIR FOR THE APPLIANCES.REFER TO THE 2010
 FBC- MECHANICAL SEC.508. THE MAKEUP AIR IS DEDICATED TO
 THE EXHAUST SYSTEM FOR THE KITCHEN.
 3) I AM THOROUGHLY CONFUSED AS TO YOUR CALCULATIONS FOR
 COMBUSTION AIR ON SHEET P-2. YOU SHOW A GAS INPUT OF
 451,000. HOW DID YOU ARRIVE AT THIS NUMBER? THE GAS
 CODE NO LONGER REFERS TO "CONFINED" & "UNCONFINED"
 SPACES. COMBUSTION AIR SHALL BE PROVIDED IN ACCORDANCE
 WITH THE 2010 FBC-FUEL GAS SEC.304.1.
 I DO NOT UNDERSTAND YOUR EQUATION FOR THE COMBUSTION
 AIR REQUIRED (18CFM X TOT BTUH/100,000). PLEASE
 EXPLAIN.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-07-11 Cont ID  
Sent By tklarge Date 2015-07-11 Time 04:59 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 04:15 Sent To  
Notes
2015-07-11 04:54:481) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS
 LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3.
 2) THE BTU LOAD OF THE GAS APPLIANCES SHOWN ON THE
 KITCHEN EQUIPMENT SCHEDULE ON A-3.0 DOES NOT MATCH THE
 BTU LOAD SHOWN ON THE GAS RISER ON SHT.P-2. CLARIFY.
 3) A 96,000 BTU GAS FIRED TILT SKILLET IS SHOWN ON THE
 EQUIPMENT SCHEDULE ON A-3.0 BUT NOT ON THE GAS RISER.
 CLARIFY.
 4) THE TOTAL BTU LOAD FOR THE LOW PRESSURE COOKLINE IS
 CALCULATED AS 771,500 BTU'S. SHOW THE TOTAL DEVELOPED
 LENGTH DISTANCE FROM THE LOW PRESSURE REGULATOR TO THE
 FURTHEST OUTLET ON THE COOKLINE ( FRYER ). SIZE THIS
 SECTION OF PIPING IN ACCORDANCE WITH TABLE 402.4 (2)..
 5) SEDIMENT TRAPS SHALL BE INSTALLED AT EACH APPLIANCE
 AND SHALL BE INSTALLED DOWNSTREAM OF THE APPLIANCE
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE APPLIANCE AS
 PRACTICAL. 2010 FGC SEC.408.4.
 6) MY CALCULATIONS FOR THE TOTAL BTU LOAD ON THE SYSTEM
 IS 1,014,500 BTU'S. PLEASE RECHECK YOUR CALCULATIONS
 FOR THE THE TOTAL BTU LOAD AND REVISE THE LOAD ON THE
 PLANS.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES PER 2010 FBC-FUEL GAS, SEC.304.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-19 Cont ID  
Sent By skennedy Date 2015-11-19 Time 10:40 Rev Time 0.00
Received By skennedy Date 2015-11-12 Time 10:10 Sent To  
Notes
2015-11-17 10:11:57C25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-03 Cont ID  
Sent By jwitmer Date 2015-11-03 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2015-10-22 Time 10:00 Sent To  
Notes
2015-10-23 10:02:02C18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 13:00 Rev Time 0.00
Received By albarran Date 2015-09-10 Time 08:52 Sent To  
Notes
2015-10-14 13:00:1110/14/15 THOUGH THE ELECTRICAL PLAN REVIEW PASSED OTHER
 TRADES HAVE TO BE APPROVED. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "M". MA
2015-09-11 08:53:06C31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-21 Cont ID  
Sent By albarran Date 2015-07-21 Time 19:35 Rev Time  
Received By albarran Date 2015-06-09 Time   Sent To  
Notes
2015-07-21 19:38:127/21/15 - FAILED ELECTRICAL REVIEW AS WELL AS OTHER
 TRADES. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE
 DENIED BIN "M". MA
2015-06-09 19:19:01C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-11-19 Cont ID  
Sent By jwitmer Date 2015-11-19 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2015-11-19 Time 13:36 Sent To  
Notes
2015-11-19 13:38:08RECEIVED A TELEPHONE CALL FROM P. B. C. IMPACT FEE
 OFFICE MICHELLE THAT SINCE THE DINING ROOM AND KITCHEN
 ARE FOR THE RESIDENCE I-1 OCCUPANCY THERE ARE NO IMPACT
 FEES DUE. J. WITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 10:14 Rev Time  
Received By jwitmer Date 2015-06-27 Time 10:13 Sent To  
Notes
2015-06-27 10:09:39BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-19 Cont ID  
Sent By skennedy Date 2015-11-19 Time 10:42 Rev Time 0.00
Received By skennedy Date 2015-11-19 Time 10:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By ccole Date 2015-09-21 Time 14:52 Rev Time 0.00
Received By ccole Date 2015-09-21 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-26 Cont ID  
Sent By ccole Date 2015-06-26 Time 16:49 Rev Time 0.00
Received By ccole Date 2015-06-26 Time 16:48 Sent To  
Notes
2015-06-26 17:14:391ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060362
  
 1) THE CITY OF WPB BUILDING DEPT. REQUIRES SEPARATE
 PERMIT APPLICATIONS AND PLAN SUBMITTALS FOR KITCHEN
 HOODS AND FIRE SUPPRESSION, FIRE SPRINKLERS, AND
 WALK-IN COOLERS AND FREEZERS. PLACE NOTES ON THE PLAN
 TO INDICATE COMPLIANCE.
 2) THE O/A CALCULATION ON SHEET M-1 DOES NOT INCLUDE
 THE LOBBY AND OFFICE AREAS, AND THE CALCULATION FOR THE
 DINING ROOM SHOULD BE BASED ON THE 213 OCCUPANT LOAD OR
 THE DEFAULT DENSITY LOAD IN TABLE 403.3 FBC-10
 MECHANICAL: PLEASE REVISE.
 3) PROVIDE AN AIR BALANCE CALCULATION ON SHEET M-1.
 4) M-2 PROVIDE THE WIND DESIGN CRITERIA AND DESIGN
 PRESSURES FOR TIE-DOWN OF THE CONDENSER UNITS- SECTION
 301.12 FBC-10 MECHANICAL.
 5) THE SUBMITTED ENERGY EFFICIENCY FORM 502-2010 IS
 LISTING NO VALUES FOR ENVELOPE COMPONENTS- REFERENCE
 TABLE 101.4.1 FBC-10 ENERGY CONSERVATION. PER THE
 TABLE, PREVIOUSLY UNCONDITIONED SPACES OR CHANGES OF
 OCCUPANCY REQUIRE COMPLIANCE WITH THE CURRENT CODE,
 INCLUDING THE THERMAL ENVELOPE COMPONENTS- REFERENCE
 SECTION 502.
 6) HOOD PLANS: ALTHOUGH THESE PLANS ARE NOT UNDER
 REVIEW AT THIS TIME, PLEASE REFERENCE SECTIONS 401.4,
 506.3.12.2, & 506.3.12.3 FOR AIR INTAKE AND EXHAUST
 TERMINATION LOCATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-11-18 Cont ID  
Sent By gjohnson Date 2015-11-18 Time 16:12 Rev Time 0.00
Received By gjohnson Date 2015-11-18 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 15:11 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 15:11 Sent To  
Notes
2015-10-29 15:30:15 
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
  
  
  
  
  
  
  
 1. SHEET P-1 SHOWS TANKLESS HEATER IN DIFFERENT
 LOCATION THAN SHEET P-3 IF LOCATION ON P-3 IS THE
 CORRECT LOCATION A NEW GAS AND WATER DIAGRAM WILL BE
 REQUIRED PLEASE CORRECT ALL SHEETS TO REFLECT THE SAME
 LOCATION AND RISER DIAGRAMS TO CORRELATE.
 PER WPB AMEND. TO FBC SEC 107.2.1
 2.PLEASE PROVIDE INFOMATION THAT RESTROOM 114 COMPLYS
 WITH FBC 2010 SEC 1210.5 TOILET ROOMS.
  
 TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM USED
 FOR THE PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-01 Cont ID  
Sent By tklarge Date 2015-10-01 Time 09:42 Rev Time 0.00
Received By tklarge Date 2015-09-30 Time 06:08 Sent To  
Notes
2015-10-01 09:41:181) RESTROOM #114 SHALL BE HANDICAP ACCESSIBLE PER 2010
 FBC-ACCESSIBILITY, SEC.213.2.
 2) INDICATE ON THE FLOOR PLAN WHICH URINAL IS FOR
 HANDICAP ACCESS. COMPLY W/2010 FAC SECS.213.3.3 & SEC.
 605.
 3) SHT. P-1 - THE GREASE SIZING CALCULATION TABLE
 REFERS TO TABLE 709.1 OF THE FL. PLUMBING CODE. THIS
 TABLE IS NOT TO BE USED FOR SIZING A GREASE
 INTERCEPTOR. REFER TO THE 2010 FPC SEC. 1003.3.4 OR
 TABLE 1003.5.1. THERE IS A NOTE UNDER THE GREASE SIZING
 TABLE THAT IS ON THE PLANS THAT REFERS TO A 4" SANITARY
 BUILDING DRAIN. DELETE THIS NOTE AS IT HAS NO RELEVANCE
 TO THE GREASE WASTE LINE OR CHANGE IT TO READ "GREASE
 BUILDING DRAIN PIPE=4".
 4) THE GRAVITY GREASE INTERCEPTOR SHALL COMPLY WITH THE
 LATEST VERSION OF THE CITY OF WEST PALM BEACH
 ENGINEERING DEPT. DETAIL AND FL. ADMIN. CODE RULE 64E-6
 . CONTACT KELLY CRANFORD AT 561-835-7243.
 5) SHT.P-2 - SIZE ALL SECTIONS OF THE VENTS ON THE
 SANITARY RISER .WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 THIS IS THE SECOND REQUEST FOR THE ABOVE ITEMS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-11 Cont ID  
Sent By tklarge Date 2015-07-11 Time 04:14 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 02:31 Sent To  
Notes
2015-07-10 13:36:211) THE WOMEN'S RESTROOM SHALL HAVE THE SAME NUMBER OF
 WATER CLOSETS AS THE COMBINED TOTAL OF WATER CLOSETS
 AND URINALS FOR THE MEN. 2010 FBC-PLUMBING, SEC.403.1.3
 (EXCEPTION).
 2) RESTROOM #114 SHALL BE HANDICAP ACCESSIBLE PER 2010
 FBC-ACCESSIBILITY, SEC.213.2.
 3) INDICATE ON THE FLOOR PLAN WHICH URINAL IS FOR
 HANDICAP ACCESS. COMPLY W/2010 FAC SECS.213.3.3 & SEC.
 605.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS
 LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3.
 5) SHT. A-3 IS ILLEGIBLE. SUBMIT A NEW SHEET THAT IS
 CLEAR IN DETAIL.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SHT. P-1 - THE GREASE SIZING CALCULATION TABLE
 REFERS TO TABLE 709.1 OF THE FL. PLUMBING CODE. THIS
 TABLE IS NOT TO BE USED FOR SIZING A GREASE
 INTERCEPTOR. REFER TO THE 2010 FPC SEC. 1003.3.4 OR
 TABLE 1003.5.1. THERE IS A NOTE UNDER THE GREASE SIZING
 TABLE THAT IS ON THE PLANS THAT REFERS TO A 4" SANITARY
 BUILDING DRAIN. DELETE THIS NOTE AS IT HAS NO RELEVANCE
 TO THE GREASE WASTE LINE OR CHANGE IT TO READ "GREASE
 BUILDING DRAIN PIPE=4".
 7) THE GRAVITY GREASE INTERCEPTOR SHALL COMPLY WITH THE
 LATEST VERSION OF THE CITY OF WEST PALM BEACH
 ENGINEERING DEPT. DETAIL AND FL. ADMIN. CODE RULE 64E-6
 . CONTACT KELLY CRANFORD AT 561-835-7243.
 8) SHT.P-2 - SIZE ALL SECTIONS OF THE VENTS ON THE
 SANITARY RISER .WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 9) THE BTU LOAD OF THE GAS APPLIANCES SHOWN ON THE
 KITCHEN EQUIPMENT SCHEDULE ON A-3.0 DOES NOT MATCH THE
 BTU LOAD SHOWN ON THE GAS RISER ON SHT.P-2. CLARIFY.
 10) A 96,000 BTU GAS FIRED TILT SKILLET IS SHOWN ON THE
 EQUIPMENT SCHEDULE ON A-3.0 BUT NOT ON THE GAS RISER.
 CLARIFY.
 11) THE TOTAL BTU LOAD FOR THE LOW PRESSURE COOKLINE IS
 CALCULATED AS 771,500 BTU'S. SHOW THE TOTAL DEVELOPED
 LENGTH DISTANCE FROM THE LOW PRESSURE REGULATOR TO THE
 FURTHEST OUTLET ON THE COOKLINE ( FRYER ). SIZE THIS
 SECTION OF PIPING IN ACCORDANCE WITH TABLE 402.4 (2)..
 12) SEDIMENT TRAPS SHALL BE INSTALLED AT EACH APPLIANCE
 AND SHALL BE INSTALLED DOWNSTREAM OF THE APPLIANCE
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE APPLIANCE AS
 PRACTICAL. 2010 FGC SEC.408.4.
 13) MY CALCULATIONS FOR THE TOTAL BTU LOAD ON THE
 SYSTEM IS 1,014,500 BTU'S. PLEASE RECHECK YOUR
 CALCULATIONS FOR THE THE TOTAL BTU LOAD AND REVISE THE
 LOAD ON THE PLANS.
 14) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES PER 2010 FBC-FUEL GAS, SEC.304.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-11-02 Cont ID  
Sent By llouie Date 2015-11-02 Time 08:40 Rev Time 0.00
Received By llouie Date 2015-10-30 Time 17:01 Sent To  
Notes
2015-11-02 08:41:06ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) NEW A/C UNITS ON THE NORTH SIDE OF THE NORTH
 BUILDING SHALL BE SCREENED FROM VIEW WITH LANDSCAPING.
  
 (REFERENCE: ZBA 3316)

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By llouie Date 2015-09-18 Time 08:37 Rev Time 0.00
Received By llouie Date 2015-09-17 Time 17:11 Sent To  
Notes
2015-09-18 08:52:44ZONING PROVISO:
  
 THE PLACEMENT OF THE NEW A/C UNITS ON THE NORTH SIDE OF
 THE NORTH BUILDING SHALL NOT INTERFERE WITH ANY
 EXISTING LANDSCAPING ON SITE. THE A/C UNITS SHALL BE
 SCREENED FROM VIEW WITH ADDITIONAL LANDSCAPING.
  
 (REFERENCE: ZBA CASE NO.3316; APPROVED ON 3/5/15)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By llouie Date 2015-06-24 Time 10:19 Rev Time 0.00
Received By llouie Date 2015-06-24 Time 10:19 Sent To  
Notes
2015-06-24 10:21:45** FAILED **
  
 1.) IT IS NOT CLEAR TO WHICH BUILDING ON THE PROPERTY
 IS THE PROPOSED ONSITE KITCHEN AND DINING ROOM LOCATED
 IN? INCLUDE A DIAGRAM/SITE PLAN WITH THE PLANS.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 (REFERENCE: ZBA 3316)