| 2015-11-14 10:26:35 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15060341 |
| | W. P. B. PERMIT: 14120225 |
| | ADD: 1309 N. FLAGLER |
| | CONT: WESTBROOKE |
| | TEL: (561)239-7133 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. NOV. 14/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SEMI-COMPLIED. SHEET A2.24 NOT UPDATED, SHOW A |
| | PRIVATE OFFICE TB#248B WITH 2 DOORS IN SERIES. PLEASE |
| | SEE THE 2010 FBC-ACCESSIBLITY CODE 404.2.6 DOORS IN |
| | SERIES. |
| | |
| | 2) 2ND REQUEST SHEET A2.41, A2.A2.42 & A2.44ALL SHOW A |
| | STORAGE ROOM # TB254 AND THE DOORWAY TO THE LEFT (LEADS |
| | INTO THE CORRIDOR) DOES NOT COMPLY WITH SECTION FROM |
| | THE 2010 FBC-ACCESSIBLITY CODE 404.2.4 AND FIGURE |
| | 404.2.4.1(A). MANEUVERING CLEARANCES. |
| | |
| | 3) 2ND REQUEST. SEMI-COMPLIED. A MIAMI-DADE NOA |
| | 14-0325.06 GREENHECK FAN PRODUCT APPROVAL WAS SUBMITED. |
| | PLEASE PROVIDE WHERE IN THE MECHANICAL SHEETS THE MODEL |
| | (SERIES) OF THE EXHAUST FAN TO BE INSTALLED ON THE |
| | ROOF. THE PRODUCT APPROVAL IS VERY SPECIFIC TO WHICH |
| | UNITS ARE COVERED UNDER THIS APPROVAL. THE MODEL/ |
| | SERIES ON THE MECHANICAL SHEETS WILL NEED TO MATCH ONE |
| | LISTED WITHIN THE NOA APPROVAL. THE PRESSURES FOR THIS |
| | NOA ARE GOOD FOR +/-90 PSF. |
| | |
| | ROOF TOP STAND NOA 09-0804.05 PLEASE SEE THE TECHNICAL |
| | SHEET 2 PLEASE IDENTIFY WHICH STAND WILL BE INSTALLED |
| | ON THIS JOBSITE, WXDXH AND MAXIMUM STAND HEIGHT, AND |
| | MIN. CLEAR HEIGHT, THIS WILL PROVIDE WITH THE TYPE |
| | ANCHOR A AND THE MAXIMUM ALLOWABLE PRESSURES TO BE USED |
| | WITH THIS STAND. |
| | |
| | 1ST REVIEW COMMENT. SHEET M3.2 DETAIL # 1 SHOWS ROOF |
| | TOP EQUIPMENT, EXHAUST FAN AND CURB. THE PLAN DETAIL |
| | REQUIRES A NOA, A MIAMI-DADE NOTICE OF ACCEPTANCE |
| | REPORT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS, CURBS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/ C STANDS |
| | |
| | 4) SEMI-COMPLIED, ADDTIONAL INFORMATION IS EQUIRED FROM |
| | THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS |
| | PROJECT. 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 4.1)COMPLIED. THE BASIC WIND SPEED, VU, SHALL BE |
| | DETERMINED IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10 180 |
| | VULT. |
| | |
| | 4.2) COMPLIED. AN IMPORTANCE FACTOR, FIGURE 1609 A-C, |
| | ASCE 7-10. BUILD. CAT. III |
| | |
| | 4.3) COMPLIED. AN EXPOSURE CATEGORY SHALL BE DETERMINED |
| | IN ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) NOT COMPLIED, 2ND REQUEST, DEIGN PRESSURES FOR |
| | ROOF TOP EQUIPMENT NOT GIVEN. A HEIGHT AND EXPOSURE |
| | ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED FROM |
| | TABLE 1609.7.2. ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP |
| | 10 FEET ABOVE THE ROOF DECK LOCATED AT 69 FEET S101. |
| | EXPOSURE C/ 180 MPH. |
| | |
| | 4.5) NOT COMPLIED, 2ND REQUEST, COMPONENTS & CLADDING |
| | PRESSURES POSITIVE & NEGATIVE TABLE 1609.2(2) ABOVE 60 |
| | FEET ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP 10 FEET |
| | ABOVE THE ROOF DECK LOCATED AT 69 FEET S101. EXPOSURE |
| | C/ 180 MPH. |
| | |
| | |
| | 5) 2ND EQUEST. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| | 1609.8 ROOFTOP STRUCTURES AND EQUIPMENT. |
| | |
| | 6) SEMI-COMPLIED. SHEET S101 SHOWS A DETAIL FOR GUY |
| | WIRES BUT IS MISSING THE TOP CONNECTION TO THE |
| | GALVANIZED L 2X2X 1/4 WELDED ANGLE FRAME. SHEET M3.2 |
| | DETAIL # 1. PLEASE PROVIDE ENGINEERING FOR THE GUY |
| | WIRES FOR THE ROOF TOP EXHAUST FAN DEPICTED. SHOW THE |
| | WIRE GAUGE, |
| | HOW THE GUY WIRE WILL BE SECURED AT EACH END, WHAT WILL |
| | THE GUY WIRE BE FASTENED TOO AND TYPE OF FASTENERS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |