Plan Review Details - Permit 15060341
Plan Review Stops For Permit 15060341
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-12 Cont ID  
Sent By jwitmer Date 2016-02-12 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2016-02-04 Time 11:31 Sent To  
Notes
2016-02-04 16:31:38BUILDING PLAN REVIEW
 W. P. B. REVISION: 15060341
 W. P. B. PERMIT: 14120225
 ADD: 1309 N. FLAGLER
 CONT: WESTBROOKE
 TEL: (561)239-7133
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. FEB. 04/ 2016
 ACTION: DENIED
  
 1) COMPLIED. PRIVATE OFFICE TB#248B
  
 2)-6) COMPLIED.
  
 7) THE SHOP DRAWING NEW EXHAUST CHASE UNDER THE HEADING
 DESIGN CRITEIA HAS THE GOOD SAM PHARMACY IN HOLLYWOOD
 FLORIDA. PLEASE ALSO NOTE THIS REPORT IS BY THOMAS
 KELAHER P. E, 40159. THE ENGINEER HAS NOT SIGNED NOR
 SEALED THE PAGES IN THE REPORT NOR PROVIDED A SIGNED
 AND SEALED INDEX PAGE LISTING HOW MANY PAGES ARE
 COVERED UNDER THEIR SEAL.
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET...
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-14 Cont ID  
Sent By jwitmer Date 2015-11-14 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2015-11-14 Time 09:59 Sent To  
Notes
2015-11-14 10:26:35BUILDING PLAN REVIEW
 W. P. B. REVISION: 15060341
 W. P. B. PERMIT: 14120225
 ADD: 1309 N. FLAGLER
 CONT: WESTBROOKE
 TEL: (561)239-7133
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 14/ 2015
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SHEET A2.24 NOT UPDATED, SHOW A
 PRIVATE OFFICE TB#248B WITH 2 DOORS IN SERIES. PLEASE
 SEE THE 2010 FBC-ACCESSIBLITY CODE 404.2.6 DOORS IN
 SERIES.
  
 2) 2ND REQUEST SHEET A2.41, A2.A2.42 & A2.44ALL SHOW A
 STORAGE ROOM # TB254 AND THE DOORWAY TO THE LEFT (LEADS
 INTO THE CORRIDOR) DOES NOT COMPLY WITH SECTION FROM
 THE 2010 FBC-ACCESSIBLITY CODE 404.2.4 AND FIGURE
 404.2.4.1(A). MANEUVERING CLEARANCES.
  
 3) 2ND REQUEST. SEMI-COMPLIED. A MIAMI-DADE NOA
 14-0325.06 GREENHECK FAN PRODUCT APPROVAL WAS SUBMITED.
 PLEASE PROVIDE WHERE IN THE MECHANICAL SHEETS THE MODEL
 (SERIES) OF THE EXHAUST FAN TO BE INSTALLED ON THE
 ROOF. THE PRODUCT APPROVAL IS VERY SPECIFIC TO WHICH
 UNITS ARE COVERED UNDER THIS APPROVAL. THE MODEL/
 SERIES ON THE MECHANICAL SHEETS WILL NEED TO MATCH ONE
 LISTED WITHIN THE NOA APPROVAL. THE PRESSURES FOR THIS
 NOA ARE GOOD FOR +/-90 PSF.
  
 ROOF TOP STAND NOA 09-0804.05 PLEASE SEE THE TECHNICAL
 SHEET 2 PLEASE IDENTIFY WHICH STAND WILL BE INSTALLED
 ON THIS JOBSITE, WXDXH AND MAXIMUM STAND HEIGHT, AND
 MIN. CLEAR HEIGHT, THIS WILL PROVIDE WITH THE TYPE
 ANCHOR A AND THE MAXIMUM ALLOWABLE PRESSURES TO BE USED
 WITH THIS STAND.
  
 1ST REVIEW COMMENT. SHEET M3.2 DETAIL # 1 SHOWS ROOF
 TOP EQUIPMENT, EXHAUST FAN AND CURB. THE PLAN DETAIL
 REQUIRES A NOA, A MIAMI-DADE NOTICE OF ACCEPTANCE
 REPORT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS, CURBS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/ C STANDS
  
 4) SEMI-COMPLIED, ADDTIONAL INFORMATION IS EQUIRED FROM
 THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS
 PROJECT. 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4.1)COMPLIED. THE BASIC WIND SPEED, VU, SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10 180
 VULT.
  
 4.2) COMPLIED. AN IMPORTANCE FACTOR, FIGURE 1609 A-C,
 ASCE 7-10. BUILD. CAT. III
  
 4.3) COMPLIED. AN EXPOSURE CATEGORY SHALL BE DETERMINED
 IN ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) NOT COMPLIED, 2ND REQUEST, DEIGN PRESSURES FOR
 ROOF TOP EQUIPMENT NOT GIVEN. A HEIGHT AND EXPOSURE
 ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED FROM
 TABLE 1609.7.2. ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP
 10 FEET ABOVE THE ROOF DECK LOCATED AT 69 FEET S101.
 EXPOSURE C/ 180 MPH.
  
 4.5) NOT COMPLIED, 2ND REQUEST, COMPONENTS & CLADDING
 PRESSURES POSITIVE & NEGATIVE TABLE 1609.2(2) ABOVE 60
 FEET ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP 10 FEET
 ABOVE THE ROOF DECK LOCATED AT 69 FEET S101. EXPOSURE
 C/ 180 MPH.
  
  
 5) 2ND EQUEST. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1609.8 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 6) SEMI-COMPLIED. SHEET S101 SHOWS A DETAIL FOR GUY
 WIRES BUT IS MISSING THE TOP CONNECTION TO THE
 GALVANIZED L 2X2X 1/4 WELDED ANGLE FRAME. SHEET M3.2
 DETAIL # 1. PLEASE PROVIDE ENGINEERING FOR THE GUY
 WIRES FOR THE ROOF TOP EXHAUST FAN DEPICTED. SHOW THE
 WIRE GAUGE,
 HOW THE GUY WIRE WILL BE SECURED AT EACH END, WHAT WILL
 THE GUY WIRE BE FASTENED TOO AND TYPE OF FASTENERS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By JWITMER Date 2015-06-29 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2015-06-29 Time 11:49 Sent To  
Notes
2015-06-29 13:57:17BUILDING PLAN REVIEW
 W. P. B. REVISION: 15060341
 W. P. B. PERMIT: 14120225
 ADD: 1309 N. FLAGLER
 CONT: WESTBROOKE
 TEL: (561)239-7133
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29/ 2015
 ACTION: DENIED
  
 1) SHEETS A2.22 & A2.24 SHEETS SHOW A PRIVATE OFFICE
 TB#248B WITH 2 DOORS IN SERIES. PLEASE SEE THE 2010
 FBC-ACCESSIBLITY CODE 404.2.6 DOORS IN SERIES.
  
 2) SHEET A2.41, A2.A2.42 & A2.44ALL SHOW A STORAGE ROOM
 # TB254 AND THE DOORWAY TO THE LEFT DOES NOT COMPLY
 WITH SECTION FROM THE 2010 FBC-ACCESSIBLITY CODE
 404.2.4 AND FIGURE 404.2.4.1(A). MANEUVERING
 CLEARANCES.
  
 3) SHEET M3.2 DETAIL # 1 SHOWS ROOF TOP EQUIPMENT,
 EXHAUST FAN AND CURB. THE PLAN DETAIL REQUIRES A NOA, A
 MIAMI-DADE NOTICE OF ACCEPTANCE REPORT. 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS, CURBS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/ C STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS
 PROJECT. 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10 180 VULT.
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 BUILD. CAT. III
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2)
  
 5) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 6) SHEET M3.2 DETAIL # 1. PLEASE PROVIDE ENGINEERING
 FOR THE GUY WIRES FOR THE ROOF TOP EXHAUST FAN
 DEPICTED. SHOW THE WIRE GAUGE,
 HOW THE GUY WIRE WILL BE SECURED AT EACH END, WHAT WILL
 THE GUY WIRE BE FASTENED TOO AND TYPE OF FASTENERS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By vperez Date 2016-02-16 Time 14:24 Rev Time 0.00
Received By vperez Date 2016-02-16 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-11-30 Time 17:53 Rev Time 0.00
Received By albarran Date 2015-11-30 Time 17:11 Sent To I
Notes
2015-11-30 17:55:09REVISIONS AS MARKED BY DELTA 1 & HIGHLIGHTED IN YELLOW
 ARE APPROVED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By albarran Date 2015-09-01 Time 15:28 Rev Time 0.00
Received By albarran Date 2015-09-01 Time 13:48 Sent To I
Notes
2015-09-01 15:36:03PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FIRE ALARM REQUIRES A SEPARATE SUBMITTAL AND
 SHOP DRAWINGS.
 2. PAGE "A1.01" IDENTIFIED THE AREA OF WORK, BUT THAT
 AREA IS NOT CLEARLY DEFINED ON THE ELECTRICAL SHEETS.
 3. THE ELECTRICAL METER ROOMS AND ADJACENT AREA APPEAR
 TO BE OUTSIDE OF THE AREA OF WORK AS DESCRIBED ON A1.01
 4. LIGHTING CONTROLS DO NOT APPEAR TO BE WITHIN THE
 FBC-E GUIDELINES.
 5. YOU SHALL SUBMIT THE ELECTRICAL RISER DIAGRAM WITH
 THE RESPECTIVE ELECTRICAL LOAD CALCS.
 6. YOU SHALL PROVIDE A CIRCUIT IDENTIFICATION SHEET
 (PANEL SCHEDULE)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-25 Cont ID  
Sent By pleduc Date 2016-01-25 Time   Rev Time 0.00
Received By pleduc Date 2016-01-25 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-18 Cont ID  
Sent By pleduc Date 2015-11-18 Time   Rev Time 0.00
Received By pleduc Date 2015-11-17 Time 16:38 Sent To  
Notes
2015-11-23 14:00:2911/23/15 ON MALBARRAN'S DESK. CP

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-11 Cont ID  
Sent By PLEDUC Date 2015-06-11 Time   Rev Time 0.00
Received By pleduc Date 2015-06-11 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-16 Cont ID  
Sent By vperez Date 2016-02-16 Time 14:24 Rev Time 0.00
Received By vperez Date 2016-02-16 Time 14:24 Sent To  
Notes
2016-02-16 14:26:08TO CAROLINE/ LAURA
2016-01-19 13:48:41C34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-11-30 Time 17:56 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 09:24 Sent To  
Notes
2015-11-30 17:57:0511/30/15 PASSED ELECTRICAL REVIEW BUT FAILED OTHER
 TRADES. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE
 DENIED BIN "W". MA
2015-11-05 09:24:40C35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-01 Cont ID  
Sent By albarran Date 2015-09-01 Time 15:52 Rev Time  
Received By albarran Date 2015-06-09 Time   Sent To  
Notes
2015-09-01 15:54:499/1/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "W". MA
2015-06-09 19:32:00C29

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-02-18 Cont ID  
Sent By ccole Date 2016-02-18 Time 07:00 Rev Time 0.00
Received By ccole Date 2016-02-17 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By ccole Date 2016-01-25 Time 16:55 Rev Time 0.00
Received By ccole Date 2016-01-25 Time 16:55 Sent To  
Notes
2016-01-25 16:56:213RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060341
 1/25/16
  
 1) PLEASE PROVIDE AN MSDS SHEET FOR THE CHEMO, AND
 REFER TO SECTION 510 HAZARDOUS EXHAUST SYSTEMS. IF THE
 MATERIAL STORED OR DISPENSED IN THE ROOM MEETS ANY OF
 THE THREE CONDITIONS LISTED UNDER 510.2 THEN AN
 INDEPENDENT HAZARDOUS EXHAUST SYSTEM, NOT CONNECTED
 WITH THE TRASH ROOM AND DRUG STORAGE, SHALL BE
 INSTALLED.
 2) PROVIDE VENTILATION CALCULATIONS FOR THE TRASH,
 CHEMO, AND DRUG STORAGE ROOMS- SEE TABLE 403.3, AND
 ALSO ASHRAE 170-2008.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-11-10 Cont ID  
Sent By ccole Date 2015-11-10 Time 11:06 Rev Time 0.00
Received By ccole Date 2015-11-10 Time 11:06 Sent To  
Notes
2015-11-10 12:10:462ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060341
 11/10/15
  
 1) SHEET M3.1 WHICH IS SHOWING THE "NEW FAN SCHEDULE"
 WAS NOT INCLUDED WITH THE REVISED PLANS SETS. PLEASE
 PROVIDE THE SHEET AND CLARIFY WHICH FAN IS THE NEW
 TRASH ROOM FAN (SEE NOTE #9 ON SHEET A2.43).
 2) PLACE A TARGET NOTE ON THE VARIOUS FLOOR PLAN
 DRAWINGS TO INDICATE THE LOCATION OF THE NEW EXHAUST
 CHASE.
 3) M3.2: AS PREVIOUSLY REQUESTED IN COMMENT #1 FROM THE
 1ST REVIEW ABOUT THE ROOF DUCT SUPPORT DETAIL "INDICATE
 THE TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO
 ATTACH THE STRAPS TO THE STAND, AND THE STAND BASE
 PLATES TO THE ROOF STRUCTURE".
 4) M3.2: THERE IS NO DETAIL FOR ATTACHMENT OF THE
 EXHAUST FAN EQUIPMENT CURB TO THE ROOF STRUCTURE-
 EITHER ON THE PLAN- OR IN THE GREENHECK FAN NOA. IS
 THERE A SEPARATE NOA FOR THIS PRODUCT?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By HMOSER Date 2015-06-29 Time 08:20 Rev Time 0.00
Received By ccole Date 2015-06-29 Time 08:20 Sent To  
Notes
2015-06-29 09:00:251ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE REVISED PLANS DO NOT INDICATE THE AHCA REQUESTED
 COMPLIANCE INFORMATION AND WIND LOAD ANCHORING DETAILS
 FOR HVAC EQUIPMENT HAVE BEEN PROVIDED. PLEASE REVIEW
 SECTION 419.4.2.6.1 AND 1609.1 FBC-10 BUILDING. THE
 ENGINERER OF RECORD SHALL PROVIDE THE WIND LOAD DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLANS. ALL
 REQUIRED NOA'S SHALL BE REVIEWED BY THE EOR AND ALL
 APPLICABLE DETAILS, NOTES, AND DESIGN PRESSURES ON THE
 DOCUMENTS SHALL HAVE IDENTIFYING MARKS, CIRCLES, OR
 HIGHLIGHTS. REFERENCE SHEET M3.2 DETAIL 1- A) INDICATE
 HOW THE GUY WIRES ARE ATTACHING TO THE EXHAUST DUCT AND
 TO THE ROOF. B) INDICATE HOW THE FAN UNIT IS ATTACHING
 TO THE STAND, AND HOW THE STAND IS ATTACHED TO THE
 ROOF. C) INDICATE THE NOA NUMBER FOR THE ROOF STAND.
 REFERENCE M3.2 DETAIL 4- A) PROVIDE THE GAGE OF STEEL
 FOR THE DUCT SUPPORT AND DUCT STRAP. B) INDICATE THE
 TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO ATTACH
 THE STRAPS TO THE STAND, AND THE STAND BASE PLATES TO
 THE ROOF STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-27 Cont ID  
Sent By tklarge Date 2016-01-27 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-01-27 Time 05:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 09:02 Rev Time 0.00
Received By tklarge Date 2015-11-16 Time 06:39 Sent To  
Notes
2015-11-16 09:02:421) SUBMIT ALL THE PLUMBING SHEETS LISTED IN THE LIST OF
 DRAWINGS ON A0.01 FOR REVIEW. (SHEETS P1.1 & P1.2)
 2) INDICATE THE ROOM NUMBERS ON THE SANITARY RISER
 DIAGRAMS WHERE THE WORK IS BEING DONE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-11 Cont ID  
Sent By TLARGE Date 2015-07-11 Time 05:41 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 05:09 Sent To  
Notes
2015-08-20 10:21:16MALBERRAN'S DESK
2015-07-11 06:45:51PLAN REVIEW COMMENTS IN PLUMBING DO NOT APPLY. THE
 PLUMBING IS APPROVED FOR THIS PERMIT. TKL.
2015-06-29 13:04:06BUILDING PLAN REVIEW
 W. P. B. REVISION: 15060341
 W. P. B. PERMIT: 14120225
 ADD: 1309 N. FLAGLER DR.
 CONT: WESTBROOKE CORP.
 TEL: (561)239-7133
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29/2015
 ACTION: DENIED
  
 1) SHEETS A2.22 & A2.24 REVISION TO ROOM TB248B SHOWS
 (2) INSWING DOORS WITH LESS THAN 4'-0" BETWEEN DOORS.
 PLEASE PROVIDE CODE COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY CODE SECTION 404.2.6 DOORS IN SERIES.
  
 2) SHEETS A2.41 & A.4.2 PLEASE SEE STORAGE ROOM # TB254
 THE EXISTING DOOR TO THE LEFT OF THIS ROOM INTO THE
 COORIDOR DOES NOT HAVE 18 INCHES MEANUVERING
 CLEARANCES. 2010 FBC-ACCESSIBILITY CODE 404.2.4, FIGURE
 404.2.4.1(A).
  
 3) SHEETS A2.4.1 & A2.4.2 BOTH SHEETS INDICATE THE USE
 OF ALTERNATE BIDS. PLEASE REVIEW 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  