Plan Review Details - Permit 15060306
Plan Review Stops For Permit 15060306
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By rmcdouga Date 2015-07-22 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2015-07-22 Time 11:19 Sent To  
Notes
2015-07-22 18:55:11APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) SUBMIT EXTERIOR DOOR AND WINDOW BUCK FASTENING
 DETAILS. FBC-R612.10.2
 2) SUBMIT STRUCTURAL DETAILS FOR ARCH OPENINGS.
 FBC-R601.2
  
 NOTE: INCREASED THE VALUE FROM $180,000.00 TO
 $240,466.00 BASED ON LATEST ICC VALUATION DATA. FBC
 109.3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-31 Cont ID  
Sent By albarran Date 2015-07-31 Time 13:17 Rev Time 0.00
Received By albarran Date 2015-07-31 Time 11:20 Sent To B
Notes
2015-07-31 13:25:33ALL PRIOR COMMENTS HAVE BEEN SUCCESSFULLY ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 12:12 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 10:54 Sent To M
Notes
2015-07-16 12:37:48PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. CORRECT THE FOLLOWING IN YOUR "GENERAL ELECTRICAL
 NOTES"
 NOTE 7: TO INCLUDE KITCHEN COUNTER RECEPTACLES, OR AS
 DIRECTED BY NEC 210.8 (1-8).
 NOTE 10: ROMEX, AS USED HERE TO REPRESENT A TYPE OF
 CABLE IS INCORRECT. ROMEX IS A BRAND NAME AND NOT A
 TYPE. YOU MAY REFER TO TYPE NM, OR THE HARDER TO FIND
 "NMC" & "NMS".
 NOTE 12: TO INCLUDE BATTERY BACK-UP AND BE
 INTER-CONNECTED.
 NOTE 20: TO READ "AS REQUIRED BY NEC 210.12(B) 2008
 ED." ARC-FAULT PROTECTED EXTENDS BEYOND THE LIVING
 ROOM.
 2. AN ADDITIONAL NOTE IS REQUIRED TO ADDRESS THE
 CEILING LUMINAIRE OUTLETS WHICH ARE TO SUPPORT 50LBS.
 PER NEC 314.27.
 3. IN GOING OVER YOUR SUBMITTED LOAD CALCS, I FOUND THE
 FOLLOWING:
 NEC 210.11(C)(1) REQUIRES TWO SMALL APPLIANCE OUTLETS
 IN ADDITION TO OTHER CIRCUITS. YOU ONLY SHOW ONE.
 YOUR GENERAL LIGHTING LOAD DOES NOT MATCH THE AREA
 INDICATED ELSEWHERE ON THE PLANS.
 YOUR CALCS CALL FOR A 700 WATT MICROWAVE/HOOD COMBO.
 REDO THE ELECTRICAL LOAD CALCS TO MATCH SITE SPECIFIC
 DATA.
 4. THE COMBINATION CO/SMOKE DETECTOR IN THE AREA
 LEADING TO THE MASTER BEDROOM NEEDS TO BE IN THE AREA
 OUTSIDE OF THE ROOM AND NOT IN A SEPARATE ROOM.
 SPECIALLY TAKING INTO ACCOUNT THE LOCATION OF THE
 GARAGE.
 5. IN THE RISER DIAGRAM, INCLUDE THE FOLLOWING:
 THE INTER-SYSTEM BONDING TERMINAL REQUIRED BY NEC
 250.94
 INDICATION TO THE SEALING REQUIREMENTS OF NEC 300.5(G)
 FOR THE UNDERGROUND SERVICE LATERAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2015-08-07 Cont ID  
Sent By rmcdouga Date 2015-08-07 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2015-08-07 Time 13:53 Sent To  
Notes
2015-08-07 13:54:20MU 2015 - 18988, NO FEES WERE DUE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2015-07-30 Time 15:35 Sent To  
Notes
2015-07-30 15:36:04ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-22 Cont ID  
Sent By rmcdouga Date 2015-07-22 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2015-06-08 Time 16:29 Sent To  
Notes
2015-06-09 16:29:42R24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 14:04 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 14:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 14:24 Sent To  
Notes
2015-08-03 14:25:27BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By rmcdouga Date 2015-07-22 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2015-07-22 Time 11:14 Sent To  
Notes
2015-07-22 11:19:00BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-16 Cont ID  
Sent By ccole Date 2015-07-16 Time 14:08 Rev Time 0.00
Received By ccole Date 2015-07-16 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-08 Time 06:15 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 05:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By rmcdouga Date 2015-07-22 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2015-07-22 Time 18:26 Sent To  
Notes
2015-07-22 18:28:32ROOFING MATERIAL
  
 GAF ASPHALT ROOF SHINGLES - NOA NO. 11-1122.04

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-30 Cont ID  
Sent By sgraham Date 2015-06-30 Time 15:32 Rev Time 0.00
Received By sgraham Date 2015-06-30 Time 15:32 Sent To  
Notes
***NONE***