Plan Review Details - Permit 15060123
Plan Review Stops For Permit 15060123
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2015-06-22 Time 13:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-17 Cont ID  
Sent By skennedy Date 2015-08-17 Time 17:05 Rev Time 0.00
Received By skennedy Date 2015-08-17 Time 17:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 19:11 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 18:42 Sent To I
Notes
2015-07-16 19:36:19PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. NEC 408.4 REQUIRES THAT YOU PROVIDE AN ACCURATE
 PANEL SCHEDULE IDENTIFYING ALL CIRCUITS.
 2. NEC 230.72(C) REQUIRES THAT ALL OCCUPANT HAVE ACCESS
 TO THE DISCONNECTING MEANS FOR THEIR UNITS, INDICATE ON
 THE PLANS THE LOCATION OF SUCH.
 3. NEC 220.16 PROVIDE THE REQUIRED ELECTRICAL LOAD
 CALCS IN ACCORDANCE WITH 220.12 EDUCATIONAL OCCUPANCY 3
 W/SQ FT.
 4. NEC 210.8(7) REQUIRES ALL OUTLETS WITH 6' OF A SINK
 TO BE GFI PROTECTED.
 5. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET ABOVE
 EVERY ENTRANCE DOOR.
 6. FBC-E SECTION 505 HAS SPECIFIC AND MANDATORY
 LIGHTING REQUIREMENTS WHICH SHALL BE ADDRESSED.
 7. FBC-B 1006.2 HAS SPECIFIC EMERGENCY LIGHTING
 REQUIREMENTS WHICH DO NOT APPEAR TO HAVE BEEN MET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-05 Cont ID  
Sent By pleduc Date 2015-06-05 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 12:01 Sent To  
Notes
2015-06-05 12:21:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 EXIT SIGNS AND EMERGENCY LIGHTS SHALL BE LOCATED DURING
 FIRE INSPECTION AND CONFIRMED IN THE REQUIRED AREAS
 THAT MAY NOT BE SHOWN ON THE SUBMITTED PLAN.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-17 Cont ID  
Sent By skennedy Date 2015-08-17 Time 17:05 Rev Time 0.00
Received By skennedy Date 2015-08-17 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 19:36 Rev Time  
Received By albarran Date 2015-06-03 Time   Sent To  
Notes
2015-07-16 19:39:427/16/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "C". MA
2015-06-03 12:37:51B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 13:22 Rev Time  
Received By jwitmer Date 2015-06-22 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By ccole Date 2015-06-26 Time 11:37 Rev Time 0.00
Received By ccole Date 2015-06-26 Time 11:37 Sent To  
Notes
2015-06-26 11:41:26MECHANICAL PROVISOS: 6/26/15
  
 1) REQUIRED FIRE DAMPERS @ DUCT/RATED WALL PENETRATIONS
 SHALL BE EXISTING AND FUNCTION OR A REVISON TO THE PLAN
 IS REQUIRED FOR NEW DAMPER INSTALLATIONS.
 2) CONTRACTOR TO VERIFY REQUIRED O/A FOR EACH STUDIO IS
 BEING PROVIDED OR ADJUST SYSTEM TO MEET THE DEMAND.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-10 Cont ID  
Sent By eschneid Date 2015-07-10 Time 16:53 Rev Time 0.25
Received By eschneid Date 2015-06-05 Time 15:00 Sent To  
Notes
***NONE***