Plan Review Details - Permit 15060110
Plan Review Stops For Permit 15060110
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-07-31 Cont ID  
Sent By jwitmer Date 2015-07-31 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2015-07-31 Time 12:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-30 Cont ID  
Sent By jwitmer Date 2015-07-30 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2015-07-30 Time 14:43 Sent To  
Notes
2015-07-30 14:45:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060110
 ADD: 201 S. NARCISSUS ST. # 504
 CONT: PDC DEVELOPMENT CORP.
 TEL: (561)793-5852
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:WED. JULY 30/ 2015
 ACTION: DENIED
  
 1) NEW COMMENT: FORMS WERE SUBMITTED FOR PROVATE
 PROVIDER (TEW & TAYLOR) FOR FIELD INSPECTIONS. THE
 ASSISTANT BUILDING OFFICIAL HAS LEFT MESSAGE ON 6/03/15
 @ 9:08 AM NEEDS:
  
 (1) RESUME AND LICENSE FOR SAID INSPECTOR, AND
  
 (2) COMPLIED 7/30/2015 PROOF OF INSURANCE FOR
 PROFESSIONAL AND COMPREHENSIVE LIABILITY PER
 FL S 553.791(16) PAGE 2 OF AGREEMENT THESE ITEMS ARE
 STILL MISSING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By jwitmer Date 2015-07-29 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2015-07-29 Time 09:45 Sent To  
Notes
2015-07-29 09:57:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060110
 ADD: 201 S. NARCISSUS ST. # 504
 CONT: PDC DEVELOPMENT CORP.
 TEL: (561)793-5852
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:WED. JULY 29/ 2015
 ACTION: DENIED
  
 1) NEW COMMENT: FORMS WERE SUBMITTED FOR PROVATE
 PROVIDER (TEW & TAYLOR) FOR FIELD INSPECTIONS. THE
 ASSISTANT BUILDING OFFICIAL HAS LEFT MESSAGE ON 6/03/15
 @ 9:08 AM NEEDS (1) RESUME AND LICENSE FOR SAID
 INSPECTOR, AND (2) PROOF OF INSURANCE FOR PROFESSIONAL
 AND COMPREHENSIVE LIABILITY PER FL S 553.791(16) PAGE 2
 OF AGREEMENT THESE ITEMS ARE STILL MISSING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 06:31 Sent To  
Notes
2015-06-19 07:15:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060110
 ADD: 201 S. NARCISSUS ST. # 504
 CONT: PDC DEVELOPMENT CORP.
 TEL: (561)793-5852
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 19/ 2015
 ACTION: DENIED
  
 1) PAGE 01 GENERAL NOTE # 9 MAKES REFERANCE TO REPAIR
 WORK TO COVER EXISTING RE-BAR. PLEASE BE AWARE, NO
 REPAIR WORK OF ANY SORT FOR THE SPALLING OF REBAR. THIS
 TYPE OF WORK IS OUT OF THE SCOPE OF THE CONTRACTORS
 LICENSE, A CBC IS NOT LICENSED TO DO ANY WORK ON THE
 STRUCTURE ITSELF, INCLUDING THAT OF BALCONY REPAIRS. A
 ENGINEER WOULD BE REQUIRED TO COME IN AND INSPECT ANY
 SPALLING OF CONCRETE BALCONIES AND OR COLUMNS AND WRITE
 UP THE REQUIRED REPAIRS.
  
 THIS WOULD ALSO INACT THE THRESHOLD REQUIREMENTS THAT
 WILL REQUIRE A FLORIDA LICENSED CGC. A SPECIAL
 THRESHOLD INSPECTOR ON SITE,
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 2) THE NEW FLOOR TILE WILL REQUIRE:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) IN THE MASTER BATH SHEET A-1 INDICATES THE REMOVAL
 OF DRYWALL FROM ALL WALLS. PLEASE PROVIDE DOCUMENTATION
 OF WALL INSULATION AND COMPLIANCE WITH: FBC-B 2010
 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4) THE ONE HOUR FIRE RATED WALLS INDICATE THE USE OF
 JUST 5/8 INCH DRYWALL.PLEASE PROVIDE EITHER A UL
 LISTING OR GYPSUM NUMBER FOR THE ONE HOUR FIRE RATED
 TENANT SEPARATION WALL. FBC-B 709.6.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-03 Cont ID  
Sent By dharvey Date 2015-08-03 Time 15:54 Rev Time 0.00
Received By dharvey Date 2015-08-03 Time 15:54 Sent To  
Notes
2015-08-03 15:54:45WITH NOTES ON PLANS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-23 Cont ID  
Sent By jwitmer Date 2015-07-23 Time 12:10 Rev Time 0.00
Received By dhayes Date 2015-07-23 Time 12:17 Sent To B
Notes
2015-07-23 12:10:377/23/2015
 PROJECT: MARY FISHER RENOVATION
 PERMIT#: 15060110
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A LUMINAIRE SCHEDULE INDICATING COMPLIANCE
 WITH THE FBC-E, THE NEC 110.3, AND 410.
  
 2) PROVIDE A PANEL SCHEDULE THAT INCLUDES THE OCPD AND
 CORRESPONDING WIRE SIZES AND WIRING METHODS PROPOSED.
 NEC 408.4.
 THE PANEL SCHEDULE INCLUDED IN THE RESUBMITTAL PROVIDES
 NAMES OF CIRCUITS ONLY. BREAKER AND WIRE SIZES ARE
 REQUIRED. THERE IS NO WAY TO VERIFY COMPLIANCE WITHOUT
 THIS INFORMATION.
  
 3) INDICATE COMPLIANCE WITH THE FBC FOR ANY
 PENETRATIONS OF WALLS OR FLOOR/CEILING ASSEMBLIES
 REQUIRED TO BE FIRE-RESISTANCE RATED. THESE
 PENNETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH THE
 FBC-R302.
  
 4) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING
 UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT.
 NEC 210.12
  
 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION AS NEEDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By dhayes Date 2015-07-07 Time 16:35 Rev Time 0.00
Received By dhayes Date 2015-07-07 Time 16:10 Sent To  
Notes
2015-07-07 16:35:377/7/2015
 PROJECT: MARY FISHER RENOVATION
 PERMIT#: 15060110
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING.
  
 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL.
  
 3) PROVIDE A PANEL SCHEDULE. NEC 408.4
  
 4) PROVIDE A SCOPE OF WORK DELINIATING BETWEEN WHAT IS
 EXISTING TO REMAIN AND WHAT IS PROPOSED TO BE INSTALLED
 NEW.
  
 5) PROVIDE A GFI OUTLET ON THE BALCONIES. NEC
 210.52(E)(3).
  
 6) PROVIDE RECEPTACLES SO THAT NO POINT MEASURED
 HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL SPACE IS
 MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE OUTLET. 210.52
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-05 Cont ID  
Sent By pleduc Date 2015-06-05 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 13:18 Sent To  
Notes
2015-06-05 13:19:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-03 Cont ID  
Sent By dharvey Date 2015-08-03 Time 15:54 Rev Time 0.00
Received By dharvey Date 2015-07-30 Time 11:58 Sent To  
Notes
2015-07-30 11:59:10DHAYES DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-29 Cont ID  
Sent By jwitmer Date 2015-07-29 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2015-07-21 Time 09:49 Sent To  
Notes
2015-07-23 09:49:37RESUB ROUTED TO DHAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-07 Cont ID  
Sent By dhayes Date 2015-07-07 Time 16:35 Rev Time 0.00
Received By dhayes Date 2015-06-02 Time 16:26 Sent To  
Notes
2015-06-02 16:23:22****EXPEDITED****
 B40
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-25 Cont ID  
Sent By tklarge Date 2015-06-25 Time 04:30 Rev Time 0.00
Received By tklarge Date 2015-06-25 Time 04:02 Sent To  
Notes
***NONE***