Plan Review Details - Permit 15060073
Plan Review Stops For Permit 15060073
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-20 Cont ID  
Sent By jwitmer Date 2015-07-20 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2015-07-20 Time 07:01 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2015-06-25 Time 05:57 Sent To  
Notes
2015-06-25 06:27:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060073
 ADD: 529 S. FLAGLER DR. SUITE # 15E
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: ( 561)784-3722
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 25/ 2015
 ACTION: DENIED
  
 1) THE PLANS CREATED BY KEITH CARRINGTON DESIGNS DOES
 NOT COMPLY WITH FLORIDA ADMINISTRATIVE CODE; 61 G
 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE INTERIOR
 DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR INTERIOR
 DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND
 SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS
 CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT.
 DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE
 RESPONSIBLE INTERIOR DESIGNER. FINAL OFFICIAL RECORD
 DOCUMENTS (NOT TRACINGS, ETC.) SHALL BE SO SIGNED. THE
 SIGNING AND SEALING OF THE SPECIFICATION INDEX SHEETS
 SHALL BE CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND
 PAGES SHALL BE SO SIGNED AND SEALED. AN INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN INTERIOR DESIGNER
 SHALL NOT USE HIS SEAL OR DO ANY OTHER ACT AS AN
 INTERIOR DESIGNER UNLESS HOLDING AT THE TIME A
 CERTIFICATE OF REGISTRATION AND ALL REQUIRED RENEWALS
 THEREOF.
  
 FL. S. 481.023 DEFINITIONS (8) ?INTERIOR DESIGN? MEANS
 DESIGNS, CONSULTATIONS, STUDIES, DRAWINGS,
 SPECIFICATIONS, AND ADMINISTRATION OF DESIGN
 CONSTRUCTION CONTRACTS RELATING TO NONSTRUCTURAL
 INTERIOR ELEMENTS OF A BUILDING OR STRUCTURE. ?INTERIOR
 DESIGN? INCLUDES, BUT IS NOT LIMITED TO, REFLECTED
 CEILING PLANS, SPACE PLANNING, FURNISHINGS, AND THE
 FABRICATION OF NONSTRUCTURAL ELEMENTS WITHIN AND
 SURROUNDING INTERIOR SPACES OF BUILDINGS. ?INTERIOR
 DESIGN? SPECIFICALLY EXCLUDES THE DESIGN OF OR THE
 RESPONSIBILITY FOR ARCHITECTURAL AND ENGINEERING WORK,
 EXCEPT FOR SPECIFICATION OF FIXTURES AND THEIR LOCATION
 WITHIN INTERIOR SPACES. AS USED IN THIS SUBSECTION,
 ?ARCHITECTURAL AND ENGINEERING INTERIOR CONSTRUCTION
 RELATING TO THE BUILDING SYSTEMS? INCLUDES, BUT IS NOT
 LIMITED TO, CONSTRUCTION OF STRUCTURAL, MECHANICAL,
 PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING,
 ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS, OR
 CONSTRUCTION WHICH MATERIALLY AFFECTS LIFESAFETY
 SYSTEMS PERTAINING TO FIRESAFETY PROTECTION SUCH AS
 FIRE-RATED SEPARATIONS BETWEEN INTERIOR SPACES,
 FIRE-RATED VERTICAL SHAFTS IN MULTISTORY STRUCTURES,
 FIRE-RATED PROTECTION OF STRUCTURAL ELEMENTS, SMOKE
 EVACUATION AND COMPARTMENTALIZATION, EMERGENCY INGRESS
 OR EGRESS SYSTEMS, AND EMERGENCY ALARM SYSTEMS.
  
 FL. S. 481.213?LICENSURE.(2)?THE BOARD SHALL CERTIFY
 FOR LICENSURE BY EXAMINATION ANY APPLICANT WHO PASSES
 THE PRESCRIBED LICENSURE EXAMINATION AND SATISFIES THE
 REQUIREMENTS OF SS. 481.209, FOR INTERIOR DESIGNERS.
  
 2) APPROVED, WHISPER MAT CS DOES MEET ALL OF THE
 REQUIRED ASTM STANDARDS, ASTM E-90, ASTM E-492 & ASTM
 E-84.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 07:26 Sent To  
Notes
2015-06-10 07:47:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060073
 ADD: 529 S. FLAGLER DR. SUITE # 15E
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: ( 561)784-3722
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 10/ 2015
 ACTION: DENIED
  
 1) AN ITEMIZED LIST OF PROPOSED WORK WAS SUBMITTED, NO
 PLANS SHOWING THE AREA AND DESCRIPTION OF WORK TO BE
 COMPLETED WITHIN THIS PROJECT.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3
 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE
 BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR
 ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE AS STATE LAW REQUIRES.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 107.3.5 107.3.5.1 COMMERCIAL BUILDINGS. MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 107.3.5.1.1 BUILDING
 A FLOOR PLAN
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE
 SPRINKLERS
 STRUCTURAL REQUIREMENTS SHALL INCLUDE: DROPPED CEILINGS
 AND SOFFIT DESIGN AND ATTACHMENT.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION: TYPE OF TILE BACKING MATERIAL
 SOUND PROOFING OF TENANT WALLS AND FLOOR SYSTEMS.
  
 2) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION: NOTE
 PROTECTO WRAP MEETS ALL THREE OF THE ASTM TEST, MISSING
 FROM THE REPORTS IS THE FLAME SPREAD INDEX TESTING
 REPORT.
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-20 Cont ID  
Sent By skennedy Date 2015-07-20 Time 16:55 Rev Time 0.00
Received By skennedy Date 2015-07-20 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-02 Cont ID  
Sent By albarran Date 2015-07-02 Time 11:10 Rev Time 0.00
Received By albarran Date 2015-07-02 Time 11:07 Sent To I
Notes
2015-07-02 11:12:02SEE PRIOR FAILED NOTES AND ADDRESS EVERY ITEM REQUESTED
 THEREIN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By dhayes Date 2015-06-17 Time 15:43 Rev Time 0.00
Received By dhayes Date 2015-06-17 Time 15:40 Sent To  
Notes
2015-06-17 16:23:556/17/2015
 PROJECT: APARTMENT 15-E
 PERMIT#: 15060073
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEE BUILDING REVIEW NOTES. COMPLY WITH BUILDING REVIEW
 AND INCLUDE ALL ELECTRICAL ELEMENTS ON NEW PLANS WHEN
 RESUBMITING. IN ADDITION INCLUDE THE FOLLOWING
 ELECTRICAL ELEMENTS IN THE NEW PLANS PER THE 2010
 FLORIDA BUILDING CODE AND THE 2008 NATIONAL ELECTRICAL
 CODE.
  
 1) FBC-RESIDENTIAL 314 AND 315. ADD SMOKE DETECTORS AS
 REQUIRED FOR NEW CONSTRCTION.: WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
 2) NEC 210.12, 406.11ALL NEW GENERAL PURPOSE OUTLETS
 MUST BE TAMPER RESISTANT AND AFCI PROTECTED.
  
 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
 3(B) NEC 210.8.(A) ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS.
  
 4) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
  
 5) FBC-E 502.3.8 RECESSED LIGHTING. RECESSED LUMINAIRES
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 AND AIR TIGHT RATED AND SEALED TO LIMIT AIR LEAKAGE
 BETWEEN CONDITIONED AND UNCONDITIONED SPACES.
  
 6) NEC 408.4 PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT
 AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE.
  
 7) NEC 220.16 LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-07-16 Cont ID  
Sent By pleduc Date 2015-07-16 Time   Rev Time 0.00
Received By pleduc Date 2015-07-16 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 14:25 Sent To  
Notes
2015-06-25 14:40:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LETTER ADDRESSING PREVIOUS COMMENTS IS ACCEPTED;
 HOWEVER, THE PLAN WILL BE STAMPED PENDING BUILDING
 COMMENT REVIEW AND APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 12:25 Sent To  
Notes
2015-06-03 12:32:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DETAIL TO APPROVE THE PROPOSED
 PROJECT.
  
 PROVIDE EXISTING AND PROPOSED DETAILS.
  
 THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS/CEILINGS REQUIRES AN EVALUATION AND/OR PROTECTION
 OF THE LIFE SAFETY DEVICES.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-20 Cont ID  
Sent By skennedy Date 2015-07-20 Time 16:55 Rev Time 0.00
Received By skennedy Date 2015-07-13 Time 06:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-02 Cont ID  
Sent By skennedy Date 2015-07-02 Time 11:13 Rev Time 0.00
Received By albarran Date 2015-06-24 Time 18:08 Sent To  
Notes
2015-07-02 11:15:047/2/15 - FAILED SECOND REVIEWS. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO SMALL DENIED BIN "C". MA
2015-06-24 18:08:40TO B45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-17 Cont ID  
Sent By   Date 2015-06-17 Time   Rev Time 0.00
Received By shill Date 2015-06-02 Time 14:17 Sent To  
Notes
2015-06-02 14:17:25****EXPEDITED****
 B45
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-20 Cont ID  
Sent By skennedy Date 2015-07-20 Time 16:55 Rev Time 0.00
Received By skennedy Date 2015-07-20 Time 16:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-02 Cont ID  
Sent By tklarge Date 2015-07-02 Time 06:31 Rev Time 0.00
Received By tklarge Date 2015-07-02 Time 06:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-13 Cont ID  
Sent By tklarge Date 2015-06-13 Time 08:57 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 08:38 Sent To  
Notes
2015-06-13 08:56:411) AN ITEMIZED LIST HAS BEEN SUBMITTED LISTING THE
 SCOPE OF WORK TO BE DONE BUT NOTHING IS SHOWN ON THE
 FLOOR PLAN THAT WAS SUBMITTED. CLEARLY SHOW THE ENTIRE
 SCOPE OF WORK TO BE DONE ON THE PLANS. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  