| 2015-06-10 07:47:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060073 |
| | ADD: 529 S. FLAGLER DR. SUITE # 15E |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: ( 561)784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 10/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) AN ITEMIZED LIST OF PROPOSED WORK WAS SUBMITTED, NO |
| | PLANS SHOWING THE AREA AND DESCRIPTION OF WORK TO BE |
| | COMPLETED WITHIN THIS PROJECT. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3 |
| | ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE |
| | DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA |
| | NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION |
| | AND THE BASIS OF CALCULATIONS. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE |
| | BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR |
| | ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL, |
| | SIGNATURE AND DATE AS STATE LAW REQUIRES. |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. |
| | |
| | 107.3.5 107.3.5.1 COMMERCIAL BUILDINGS. MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: |
| | 107.3.5.1.1 BUILDING |
| | A FLOOR PLAN |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE |
| | SPRINKLERS |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: DROPPED CEILINGS |
| | AND SOFFIT DESIGN AND ATTACHMENT. |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | SANITATION: TYPE OF TILE BACKING MATERIAL |
| | SOUND PROOFING OF TENANT WALLS AND FLOOR SYSTEMS. |
| | |
| | 2) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION: NOTE |
| | PROTECTO WRAP MEETS ALL THREE OF THE ASTM TEST, MISSING |
| | FROM THE REPORTS IS THE FLAME SPREAD INDEX TESTING |
| | REPORT. |
| | |
| | 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |