Plan Review Details - Permit 15060070
Plan Review Stops For Permit 15060070
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By hmoser Date 2015-06-22 Time 08:52 Rev Time 0.00
Received By hmoser Date 2015-06-17 Time 07:34 Sent To  
Notes
2015-06-18 07:34:42SENT TO H MOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-06 Cont ID  
Sent By hmoser Date 2015-06-06 Time 07:35 Rev Time 0.00
Received By hmoser Date 2015-06-02 Time 17:12 Sent To  
Notes
2015-06-02 17:12:45TO MECHANICAL
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By hmoser Date 2015-06-22 Time 08:51 Rev Time 0.00
Received By hmoser Date 2015-06-22 Time 08:36 Sent To  
Notes
2015-06-22 09:00:23REFER TO SECTION 602.2.1 NO COMBUSTIBLES IN
 RETURN AIR PLENUM. 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By hmoser Date 2015-06-06 Time 07:35 Rev Time 0.00
Received By hmoser Date 2015-06-06 Time 07:24 Sent To  
Notes
2015-06-06 07:35:36PLAN DENIED
 1) REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M)
 2) PROVIDE CFM ON SUPPLY DROPS. SECTION 107
 2010 FBC
 3) REFER TO SECTION 606.2.1 SUPPLY AIR
 2010 FBC (M)
 4) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS
 ON AIRCONDITIONING EQUIPMENT FOR NEXT REVIEW
 PER SECTION 304.1 GENERAL. 2010 FBC (M
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676