Plan Review Details - Permit 15060045
Plan Review Stops For Permit 15060045
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2016-02-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 08:30 Sent To  
Notes
2015-10-01 12:28:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: THURS. OCT.01/2015
 ACTION: BUILDING PROVISO
  
 1) ALL PRODUCT APPROVALS HAVE BEEN REQUESTED BY THE
 DESIGNER OF RECORD TO BE DEFERRED SUBMITTALS UNTIL
 AFTER PERMIT ISSUANCE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 NOTE: MANY OF THE PRODUCT APPROVALS HAVE MORE THAN ONE
 TYPE OF GLAZING, IDENTIFY TYPE OF GLAZING, WIDTH,
 HEIGHT, TYPE OF ANCHORS AND ASSOCIATED PRESSURES.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS, & ROOF TOP EXHAUST FANS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-03 Cont ID  
Sent By jwitmer Date 2015-09-03 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2015-09-03 Time 06:31 Sent To  
Notes
2015-09-03 08:54:05 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 02/2015
 ACTION: DENIED
  
 1) THIS BUILDING WILL NEED TO HAVE A RESIDENT INSPECTOR
 ON SITE. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: (2) .
 FOR ALL MAJOR STRUCTURAL ALTERATIONS.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 1A) FORMS SUBMITTED ARE COPIES NOT ORIGINAL NOTARIZED
 DOCUMENTS. RESIDENT INSPECTOR FORMS WERE
 E-MAILED TO ;[email protected]
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 1D) NOTE ONLY (2) SETS OF PLANS WERE RETURNED. NOTE FOR
 PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. FOR
 DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT
 LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 1E) PLEASE CALL THE CITY OF WEST PALM BEACHES?
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2-4) COMPLIED
  
 5) LS1.01 HAS A NOTE THAT FIRE ALARM DRAWINGS SHALL BE
 REQUIRED PRIOR TO THE GC STARTS WORK. SECTION 907.2.1
 DOES REQUIRE A FIRE ALARM FOR AN A2 ASSEMBLY OCCUPANCY
 WHEN THERE IS A OCCUPANT LOAD OF 300 OR MORE. NOTE A
 SEPARATE PERMIT IS REQUIRED WITH DRAWINGS.
  
 6) THE COVERSHEET NOTES THAT NEW EXTERIOR GLAZING
 SYSTEMS, STOREFRONT WINDOWS AND DOORS WILL BE PART OF
 THIS PROJECT. PLEASE SHOW COMPLIANCE WITH: COMPONENTS &
 CLADDING
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 NOTE: MANY OF THE PRODUCT APPROVALS HAVE MORE THAN ONE
 TYPE OF GLAZING, IDENTIFY TYPE OF GLAZING, WIDTH,
 HEIGHT, TYPE OF ANCHORS AND ASSOCIATED PRESSURES.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS SEE
 COMMENTS UNDER ROOF REVIEW!!!
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, & ROOF TOP EXHAUST FANS
 PRE-ENGINEERED A/C STANDS HIGHLIGHT THE WIDTH, HEIGHT
 TO BE INSTALLED AND ASSOCIATED
 PRESSURES.
  
 PLEASE NOTE IF THE BUILDING WIND DESIGN CRITERIA IS
 CORRECT AND ASSOCIATED PRESSURES THE PRODUCT APPROVALS
 CAN BE A DEFERRED SUBMITTAL IS THE DESIGN PROFESSIONAL
 AND OR CONTRACTOR INDICATES SUCH IN A WRITTEN RESPONSE.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 7) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS,?
  
 8) 2ND REQUEST. COPIES SUBMITTED, 3 ORIGINAL SIGNED AND
 SEALED DOCUMENTS. THE STRUCTURAL SHEET S-1 GRIDLINE ?L?
 SHOWS A NEW ADDITION TO THE BUILDING BUT THERE WAS NO
 SOILS REPORT SUBMITTED, PLEASE SHOW COMPLIANCE WITH
 2010 FBC-B 1803.5.2 QUESTIONABLE SOILS.
  
 9) THIS SUBMITTAL THERE WAS NO DOCUMENTATION SUBMITTED
 AS TO HOW THE LEVEL 3 ALTERATION IS GOING TO COMPLY
 WITH THE 2010 FBC-ENERGY 103.2.1.
  
 10) COMPLIED.
  
 11)2ND REQUEST. SHEET 4 INDICATES ON VARIOUS COLUMNS
 THE CAPS ARE TO BE FULLY WELDED. THE TYPE OF WELD NOR
 THE SIZE OF THE WELD HAS BEEN IDENTIFIED.
 SHEET S3-5 SHOW VARIOUS COLUMNS WITH EITHER OR BOTH THE
 BOTTOM PLATE AND TOP PLATE BEING WELDED, THERE IS NO
 WELD INFORMATION ON THE PLANS AS TO TYPE OF WELD NOR
 THE SIZE OF THE WELD. FBC-B 2204.1.
  
 12)2ND REQUEST. THIS DETAIL IS NOT CLEAR AS DRAWN HOW
 THE BAR JOIST ARE TO BE ANCHORED AS WELL AS THE 2 X6 @
 24 INCHES ON CENTER. SHEET S-4 DETAIL C IS MISSING THE
 ANCHORING OF THE BAR JOIST AND 2 X 6 RAFTERS TO THE
 W8X60 STEEL BEAM THIS IS PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 13)2ND REQUEST. SHEET S-6 COMPONENTS AND CLADDING
 PRESSURES ARE LOW FOR ZONES 4 & 5. FBC-B 1609.1.5 /
 1609.1.2.3.2. PLEASE NOTE THERE ARE NO PRESSURES
 PROVIDED FOR THE SLOPED METAL ROOFING.
  
 14)2ND REQUEST FOR CURB DETAILS AND PRODUCT APPROVALS.
 SHEET # 3 FROM CAPTIVE AIR BY BUCHNANAN P. E.
 CONSULTING ENGINEER DOES SHOW ROOF TOP CURBS AND ROOF
 TOP EXHAUST FANS, NO DESIGN FOR ANCHORING OF SYSTEMS,
 AND NO FLORIDA PRODUCT APPROVAL SUBMITTED OR LISTED FOR
 THESE UNITS, THE PLANS ARE NOT SIGNED NOR SEALED BY A
 FLORIDA P.E. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 15) COMPLIED. THE PRODUCT APPROVALS SUBMITTED IS A
 MIAMI-DADE NOA 14-0211.09. SHEET 3 OF 7 INDICATES THE
 USE OF 5/16 INCH O. A. LAMINATED GLASS 1/8 INCH
 ANNEALED GLASS, 0.100 INCH PVB INTERLAYER AND A 3/32
 INCH ANNEALED GLASS.
 THE 0.100 INCH PVB INTER LAYER = 2.3813 MM, REQUIRED
 0.76 MM. 2010FBC-B 2405.2(1)
  
 COMMENT FROM 1ST REVIEW. SHEETS A1.01 & A2.02 DOORS
 IDENTIFIED AS MARK 4-7 ARE GLAZED ROLL-UP OVERHEAD
 DOORS. PLEASE SHOW HOW COMPLIANCE WITH FBC-B SECTION
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
  
 16) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By jwitmer Date 2015-06-06 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2015-06-05 Time 11:00 Sent To  
Notes
2015-06-05 18:04:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETEMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 06/2015
 ACTION: DENIED
  
 1) THIS BUILDING WILL NEED TO HAVE A RESIDENT INSPECTOR
 ON SITE. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES
 SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE
 IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF
 SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE
 OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING
 INSTANCES: (2) . FOR ALL MAJOR STRUCTURAL ALTERATIONS.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 RESIDENT INSPECTOR FORMS WERE E-MAILED TO
 ;[email protected]
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED.
 FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT
 LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) ) COVERSHEET INDICATES THIS TO BE A TYPE VB BUILDING
 TYPE, WITH 11,482 SQ. FT., PLEASE PROVIDE WHICH
 INCREASES WERE TAKEN SINCE FBC-B T-503 ONLY ALLOWS
 6,000 SQ. FT. FOR THIS BUILDING TYPE FBC-B SECTION
 BUILDING MODIFICATIONS.
 3) COVERSHEET & LS1.01INDICATE THE OCCUPANT LOAD TO BE
 329 OCCUPANTS, PLEASE PROVIDE THE SQUARE FOOT BREAK
 DOWN OF THE OCCUPANT LOAD PER FBC-B TABLE 1004.1.1 FOR
 THE A2 SEATING AREAS, BAR AREA FRONT AND BACK,
 INTERACTIVE GAME AREA, KITCHEN, STORAGE AND OFFICE
 AREAS. FBC-B 1004.1.1 DOES NOT ALLOW YOU TO ROLL DOWN
 FRACTION OF OCCUPANTS.
 4) THE LS1.01 SHEET INDICATES DOORS IN A MEANS OF
 EGRESS DO NOT REQUIRE PANIC HARDWARE SERVING MORE THAN
 100 OCCUPANTS. PLEASE REFER TO FBC-B 1008.1.10. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN AN A OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LOCK OR LATCH UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
 5) LS1.01 HAS A NOTE THAT FIRE ALARM DRAWINGS SHALL BE
 REQUIRED PRIOR TO THE GC STARTS WORK. SECTION 907.2.1
 DOES REQUIRE A FIRE ALARM FOR AN A2 ASSEMBLY OCCUPANCY
 WHEN THERE IS A OCCUPANT LOAD OF 300 OR MORE. NOTE A
 SEPARATE PERMIT IS REQUIRED WITH DRAWINGS.
 6) THE COVERSHEET NOTES THAT NEW EXTERIOR GLAZING
 SYSTEMS, STOREFRONT WINDOWS AND DOORS WILL BE PART OF
 THIS PROJECT. PLEASE SHOW COMPLIANCE WITH: COMPONENTS &
 CLADDING
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, & ROOF TOP EXHAUST FANS
  
 PLEASE NOTE IF THE BUILDING WIND DESIGN CRITERIA IS
 CORRECT AND ASSOCIATED PRESSURES THE PRODUCT APPROVALS
 CAN BE A DEFERRED SUBMITTAL IS THE DESIGN PROFESSIONAL
 AND OR CONTRACTOR INDICATES SUCH IN A WRITTEN RESPONSE.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,?
  
 8) THE STRUCTURAL SHEET S-1 GRIDLINE ?L? SHOWS A NEW
 ADDITION TO THE BUILDING BUT THERE WAS NO SOILS REPORT
 SUBMITTED, PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1803.5.2 QUESTIONABLE SOILS.
  
 9) THIS SUBMITTAL THERE WAS NO DOCUMENTATION SUBMITTED
 AS TO HOW THE LEVEL 3 ALTERATION IS GOING TO COMPLY
 WITH THE 2010 FBC-ENERGY 103.2.1.
  
 10) SHEET S3 INDICATES A DETAIL ?C? ON SHEET S3 MISSING
 ONLY DETAIL IS SECTION A. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THE FAR RIGHT OF THE DETAIL
 SHOWN AT ELEVATION 13 FEET THE TIE DOWN INFORMATION IS
 NOT SHOWN.
  
 11) SHEET S3-5 SHOW VARIOUS COLUMNS WITH EITHER OR BOTH
 THE BOTTOM PLATE AND TOP PLATE BEING WELDED, THERE IS
 NO WELD INFORMATION ON THE PLANS AS TO TYPE OF WELD NOR
 THE SIZE OF THE WELD. FBC-B 2204.1.
  
 12) SHEET S-4 DETAIL C IS MISSING THE ANCHORING OF THE
 BAR JOIST AND 2 X 6 RAFTERS TO THE W8X60 STEEL BEAM
 THIS IS PART OF THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM).
  
 13) SHEET S-6 COMPONENTS AND CLADDING PRESSURES ARE LOW
 FOR ZONES 4 & 5. FBC-B 1609.1.5 / 1609.1.2.3.2.
  
 14) SHEET # 3 FROM CAPTIVE AIR BY BUCHNANAN P. E.
 CONSULTING ENGINEER DOES SHOW ROOF TOP CURBS AND ROOF
 TOP EXHAUST FANS, NO DESIGN FOR ANCHORING OF SYSTEMS,
 AND NO FLORIDA PRODUCT APPROVAL SUBMITTED OR LISTED FOR
 THESE UNITS, THE PLANS ARE NOT SIGNED NOR SEALED BY A
 FLORIDA P.E. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 15) SHEETS A1.01 & A2.02 DOORS IDENTIFIED AS MARK 4-7
 ARE GLAZED ROLL-UP OVERHEAD DOORS. PLEASE SHOW HOW
 COMPLIANCE WITH FBC-B SECTION 2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-09-21 Cont ID  
Sent By albarran Date 2015-09-21 Time 18:37 Rev Time 0.00
Received By albarran Date 2015-09-21 Time 17:58 Sent To  
Notes
2015-09-21 18:38:36THE SCOPE OF THIS REVIEW WAS TO STAMP PREVIOUSLY
 APPROVED SHEETS
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-09-16 Cont ID  
Sent By albarran Date 2015-09-16 Time 13:40 Rev Time 0.00
Received By albarran Date 2015-09-16 Time 13:40 Sent To  
Notes
2015-09-16 13:43:28I RECEIVED FRO IRINA GOLDBERG A REVISED DRAWINGS VIA
 PDF WHICH HAD BEEN CORRECTED. I ELECTRONICALLY APPROVED
 THE DRAWINGS AND RETURNED TO HER FOR PRINTING AND
 INSERTION INTO THE PERMIT PLAN SET. AS SOON AS SHE
 DOES, I WILL SIGN-OFF ON THE PLANS AND THE ELECTRICAL
 REVIEW WILL BE COMPLETE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-14 Cont ID  
Sent By albarran Date 2015-09-14 Time 14:08 Rev Time 0.00
Received By albarran Date 2015-09-11 Time 11:06 Sent To I
Notes
2015-09-14 14:09:02PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. ONE OF THE TWO SETS OF PLANS IS MISSING SHEET E0.1
 2. COMMENTS 4, 5 & 6 WERE DELEGATED TO THE ARCHITECT
 WHO HAS NOT YET COMPLETED HIS CORRECTIONS/RESPONSES TO
 THESE NOTES.
 3. YOUR RESPONSE TO NOTE 8 STATES THAT THE SHOW WINDOW
 OUTLETS ARE INCLUDED ON THE DRAWINGS AND HAVE BEEN
 INCLUDED ON THE CALCULATIONS. THE OUTLETS INDICATED
 ABOVE THE WINDOWS, ACCORDING TO PANEL ?A? SCHEDULE ARE
 FOR THE MOTORIZED SHADES.
 4. YOU INDICATE THAT THERE ARE FOUR (4) LOCATIONS
 INDICATED FOR SIGN OUTLETS. THAT IS ALL FINE, YOU MAY
 ALL THE SIGNAGE YOU DECIDE AS LONG AS YOU HAVE AT LEAST
 THOSE REQUIRED BY CODE BY EVERY DOOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 16:59 Rev Time 0.00
Received By albarran Date 2015-07-13 Time 13:42 Sent To I
Notes
2015-07-13 17:02:12JOB PERMIT NUMBER: 15060045
 JOB ADDRESS: 2224 PALM BEACH LAKES BLVD.
  WEST PALM BEACH, FL
 DATE: JULY 13TH, 2015
  ELECTRICAL PLAN REVIEW COMMENTS
  
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER NEC 422.52, ELECTRIC DRINKING FOUNTAINS SHALL BE
 ON A GFCI PROTECTED CIRCUIT.
 2. PER NEC 110.16, ALL ELECTRICAL PANELS SHALL BEAR THE
 ARC-FLASH WARNING LABEL.
 3. SEPARATE PERMIT AND SUBMITTAL REQUIRED FOR FIRE
 ALARM WORK.
 4. AMEND NOTE 41 TO INCLUDE, "WHEN USING
 NON-COMMUNICATING PARTITIONS", OTHERWISE ALL BOXES
 SHALL BE PROPERLY FIRE STOPPED.
 5. PROVIDE A FIRE RATED WALL DETAIL INDICATING THE TYPE
 OF STUD EMPLOYED TO ASCERTAIN COMPLIANCE W/FBC-B
 SECTION 713.3.2
 6. PLANS ARE MISSING GENERAL NOTES PAGES GN0.01 -
 GN0.04,
 7. ALL AUXILIARY SOUND SHALL BE MUTED VIA THE FACP IN
 THE EVENT OF AN ALARM CONDITION.
 8. THOUGH THE NOTES ADDRESS THE SHOW WINDOW OUTLETS
 REQUIRED BY NEC 210.62, THEY ARE NOT INDICATED ON THE
 PLANS AND THUS NOT CONSIDERED WITH THE LOAD CALCS.
 9. NEC 600.5 REQUIRES A SIGN OUTLET AT EACH ENTRANCE OF
 EVERY COMMERCIAL OCCUPANCY NOT JUST AT THE MAIN DOOR.
 10. EMERGENCY LIGHTING REQUIRED INSIDE THE WALK-IN
 COOLERS, WALK-IN FREEZER AND STORAGE.
 11. FACP CIRCUIT TO COMPLY WITH NFPA 72 SECTION
 10.5.5.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH, PH. (561) 805-6746
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-30 Cont ID  
Sent By wjolin Date 2015-09-30 Time 10:29 Rev Time 0.00
Received By wjolin Date 2015-09-30 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By wjolin Date 2015-09-11 Time 12:17 Rev Time 0.00
Received By wjolin Date 2015-09-10 Time 12:31 Sent To E
Notes
2015-09-11 12:17:242224 PALM BEACH LAKES BOULEVARD
 PERMIT #15060045
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: SEVERAL SHEETS NOT SIGNED/SEALED BY THE
 DESIGN PROFESSIONAL(S).
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By wjolin Date 2015-06-12 Time 14:37 Rev Time 0.00
Received By wjolin Date 2015-06-11 Time 13:54 Sent To  
Notes
2015-06-11 16:57:562224 PALM BEACH LAKES BOULEVARD
 PERMIT #15060045
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ONLY SHEET SIGNED/SEALED BY THE DESIGN
 PROFESSIONAL(S) IS THE COVER SHEET.
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 CONFIRM ALL EXIT DOORS AND EXIT GATES ARE EQUIPPED WITH
 PANIC HARDWARE.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 SHEET P1.1: DRAWING INDICATES SPRINKLER RISER AND
 NATURAL GAS LINES RUN INTO AND THROUGH ELECTRICAL ROOM.
  
 SHEET P1.1: FIRE PIT IS NOT APPROVED AT THIS TIME.
 ADDITIONAL INFORMATION IS NEEDED TO SHOW COMPLIANCE
 WITH NFPA 1. IS THIS AN ENCLOSED FLAME WITH A LISTED
 PIECE OF EQUIPMENT OR AN OPEN FLAME.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-09-25 Cont ID  
Sent By gjohnson Date 2015-09-25 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2015-09-25 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2015-12-09 Time 16:40 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-10 Cont ID  
Sent By cpuell Date 2015-12-10 Time 16:40 Rev Time 0.00
Received By cpuell Date 2015-09-17 Time 11:50 Sent To  
Notes
2015-09-21 11:04:11ASSIGNED TO C27, BUT PLACED ON MIKE ALBARRAN'S DESK TO
 EXPEDITE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-14 Cont ID  
Sent By albarran Date 2015-09-14 Time 14:29 Rev Time 0.00
Received By albarran Date 2015-08-17 Time 09:54 Sent To  
Notes
2015-09-14 14:31:479/14/15 - FAILED ELECTRICAL REVIEW. NARRATIVE FAILED TO
 ADDRESS ALL PREVIOUS COMMENTS. ONE OF THE SETS IS
 MISSING PAGE E0.1. CONTACTED MR. PEDRO RAMOS, OTHER
 EMAIL WAS RETURNED. SENT TO LARGE DENIED BIN "C". MA
2015-08-18 09:54:29C35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 17:08 Rev Time  
Received By albarran Date 2015-06-01 Time   Sent To  
Notes
2015-07-13 17:11:057// - FAILED FIRST ELECTRICAL REVIEW AS NOTED. FRITZ
 MASSON CONTACTED VIA EMAIL. SENT TO LARGE DENIED BIN
 "T". MA
2015-06-02 12:02:40C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 13:35 Sent To  
Notes
2015-10-01 13:37:49PALM BEACH COUNTY IMPACT FEE ASSESSMENT:
 SEPT. 19/2015
 MU-2015-22079
 292 SQUARE FEET ADDED
 $3,675.99

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-09-02 Cont ID  
Sent By jwitmer Date 2015-09-02 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 15:14 Sent To  
Notes
2015-09-02 15:14:38IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By jwitmer Date 2015-06-06 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2015-06-06 Time 12:12 Sent To  
Notes
2015-06-06 12:13:15IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-12-16 Cont ID  
Sent By hmoser Date 2015-12-16 Time 09:50 Rev Time 0.00
Received By hmoser Date 2015-12-16 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-09-23 Cont ID  
Sent By ccole Date 2015-09-23 Time 08:38 Rev Time 0.00
Received By ccole Date 2015-09-23 Time 08:38 Sent To  
Notes
2015-09-23 08:44:07MECHANICAL PROVISOS.
 PERMIT #15060045
 09/23/15
  
 1) WIND LOAD TIE DOWN ENGINEERING FOR ALL ROOFTOP
 MECHANICAL EQUIPMENT- RTU'S, CONDENSERS, CURBS, STANDS,
 AND FANS SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT,
 AND REVIEWED AND APPROVED PRIOR TO 1ST INSPECTION.
  
 2) ALL NOA'S & PRODUCT APPROVALS SHALL BE REVIEWED AND
 APPROVED BY THE E.O.R. AND ALL APPLICABLE NOTES,
 DETAILS, ETC. SHALL BE CIRCLED, HIGHLIGHTED, OR
 OTHERWISE MARKED UP BY THE E.O.R.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-03 Cont ID  
Sent By ccole Date 2015-09-03 Time 13:37 Rev Time 0.00
Received By ccole Date 2015-09-03 Time 13:37 Sent To  
Notes
2015-09-03 13:39:222ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060045
 9/3/15
  
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 3) THE DESIGN PROFESSIONALS OF RECORD SHALL
 SIGN AND SEAL ALL THE MECHANICAL AND KITCHEN HOOD PLAN
 SHEETS IN COMPLIANCE WITH SECTION 61G15-23.002 FL.
 ADMIN. CODE.
 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 4) SHEET M0.1, DETAILS M3, M4, M7, M8, & M11:
 WINDLOAD TIE-DOWN ENGINEERING DETAILS ARE REQUIRED FOR
 THE ROOF TOP HVAC INSTALLATIONS SHOWN IN THE DETAILS,
 ALONG WITH FL. PRODUCT AND/OR MIAMI-DADE NOA'S REVIEWED
 AND STAMPED BY THE DESIGN PROFESSIONAL OF RECORD.
 SUBMIT ALL THE REQUIRED DOCUMENTS, AND REVISE THE
 DETAILS TO INCLUDE CURB HEIGHTS, AND STAND CLEARANCE
 HEIGHTS ABOVE THE ROOF. THE ENGINEER OF RECORD SHALL
 PROVIDE THE WIND DESIGN CRITERIA ON THE PLANS AND
 COMPLETE DETAILS FOR ALL ROOF-MOUNTED EQUIPMENT
 INCLUDING MODIFICATIONS TO THE EXISTING ROOF STRUCTURE,
 AND THE TYPES, SIZES, AND SPACINGS OF ANCHORS AND
 FASTENERS FOR ATTACHING THE ROOF CURBS TO THE
 STRUCTURE, AND MOUNTING THE EQUIPMENT TO THE CURBS AND
 STANDS. PLEASE REFER TO DETAIL M3 ON SHEET M0.1 AND
 INDICATE THE EXACT PLAN SHEETS WHERE THE DETAILS CAN BE
 FOUND.
 3) COMMENT #5 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 5) M0.1, DETAIL 6: UPDATE THE SMACNA HANGER
 TABLE TO 5-1 & FIG. 5-5 PER THE 2005 EDITION IN EFFECT.
 4) COMMENT #6 FROM THE 1ST REVIEW HAS BEEN ADDRESSED ON
 THE PLANS, HOWEVER THERE APPEARS TO BE INADEQUATE O/A
 FOR THE MAN CAVE AREA BASED ON TABLE 403.3. THE AREA IS
 APPROXIMATELY 650 SQ. FT. WHICH AMOUNTS TO
 APPROXIMATELY 454 CFM'S OF O/A BY THE TABLE, OR 274 BY
 THE AMOUNT OF SEATS (21).
 5) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. IN RESPONSE TO THIS COMMENT REGARDING DUCT
 SMOKE DETECTOR SEQUENCE OF OPERATIONS, THE DESIGN
 PROFESSIONAL HAS STATED IN THE NARRATRIVE RESPONSE THAT
 THE COMPLIANCE INFORMATION WOULD BE FOUND ON SHEET
 FA0.1 WHCICH WAS NOT INCLUDED WITH THE CORRECTED PLAN
 SETS. PLEASE PROVIDE THE SHEET.
 6) COMMENT #10 FROM THE 1ST REVIEW HAS BEEN ADDRESSED
 HOWEVER NO CONDENSATE DISPOSAL DETAILS ARE SHOWN FOR
 RTU #3. IN ADDITION PLEASE INDICATE HOW THE NEW
 CONDENSATE PIPES WILL BE SUPPORTED AND PROTECTED FROM
 UV DEGRADATION.
 7) COMMENT #12 FROM THE 1ST REVIEW HAS BEEN ADDRESSED
 HOWEVER THE ENERGY CALCULATION FORM 506-2010 DOES NOT
 INCLUDE ANY DATA FOR THE OAU AAON RTU- PLEASE REVISE
 ACCORDINGLY.
 8) REFER TO BUILDING COMMENTS FOR ADDITIONAL ROOF TOP
 EQUIPMENT REQUIREMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By ccole Date 2015-06-22 Time 12:14 Rev Time 0.00
Received By ccole Date 2015-06-22 Time 12:13 Sent To  
Notes
2015-06-22 12:28:391ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE PERMIT VALUE OF $750,000.00 APPEARS TO BE
 UNDER-VALUED FOR THE SCOPE OF THE PROPOSED RESTAURANT
 PROJECT. PLEASE ADJUST THE VALUE ON THE APPLICATION AND
 PROVIDE DETAILED ESTIMATES AND/OR BONA FIDE CONTRACTS
 PER FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 2) THE CITY OF WPB CONSTRUCTION SERVICES DEPT. REQUIRES
 SEPARATE PERMITS FOR KITCHEN HOODS AND FIRE SUPPRESSION
 SYSTEMS, WALK-IN COOLER AND FREEZERS, AND FIREPLACES
 INCLUDING OUTDOOR FIRE PITS AND EXHAUST SYSTEMS. PLEASE
 PROVIDE AN INTEMIZED LIST OF ALL WORK TO BE DONE UNDER
 SEPARATE PERMITS ON COVER SHEET CSO.01.
 3) THE DESIGN PROFESSIONALS OF RECORD SHALL SIGN AND
 SEAL ALL THE MECHANICAL AND KITCHEN HOOD PLAN SHEETS IN
 COMPLIANCE WITH SECTION 61G15-23.002 FL. ADMIN. CODE.
 4) SHEET M0.1, DETAILS M3, M4, M7, M8, & M11: WINDLOAD
 TIE-DOWN ENGINEERING DETAILS ARE REQUIRED FOR THE ROOF
 TOP HVAC INSTALLATIONS SHOWN IN THE DETAILS, ALONG WITH
 FL. PRODUCT AND/OR MIAMI-DADE NOA'S REVIEWED AND
 STAMPED BY THE DESIGN PROFESSIONAL OF RECORD. SUBMIT
 ALL THE REQUIRED DOCUMENTS, AND REVISE THE DETAILS TO
 INCLUDE CURB HEIGHTS, AND STAND CLEARANCE HEIGHTS ABOVE
 THE ROOF.
 5) M0.1, DETAIL 6: UPDATE THE SMACNA HANGER TABLE TO
 5-1 & FIG. 5-5 PER THE 2005 EDITION IN EFFECT.
 6) M0.2: THE OUTSIDE AIR CALCULATIONS FOR DINING AREA
 AND INTERIOR BAR ARE NOT IN COMPLIANCE WITH TABLE 404.3
 FBC-10 MECHANICAL. PER THE TABLE THE NUMBER OF PEOPLE
 IN THE DINING AREA SHALL BE 266 , AND IN THE INTERIOR
 BAR SHALL BE105. TOTAL REQUIRED AIR FOR DINING- 2685
 CFM'S, AND FOR THE BAR- 1065. PLEASE CORRECT THE TABLE,
 THE O/A DIAGRAM, AND THE AC EQUIPMENT SCHEDULES TO
 REFLECT COMPLIANCE, AND ADD THE KITCHEN EXHAUST
 CALCULATION TO THE TABLE.
 7) M1.1: THIS PLAN SHEET WAS PLACED INTO EACH OF THE
 SETS IN UPSIDE DOWN POSITION: PLEASE INSERT IT PROPERLY
 FOR REVIEW- SECTION 107.2.1 FBC-10 BUILDING.
 8) M1.1: PLEASE LABEL EACH OF THE RTU'S AND THE O/A AIR
 UNIT ON THE PLAN WITH THE CORRESPONDING NUMBERS SHOWN
 IN THE SCHEDULES ON SHEET M0.2.
 9) M1.1: CLARIFY THE FAN SHUTDOWN PROCEDURE OR SEQUENCE
 OF OPERATIONS RELATING TO THE DUCT SMOKE DETECTORS AND
 THE FIRE ALARM SYSTEM- SECTION 606.4.1 FBC-10 MECH.
 WILL ALL OF THE SYSTEMS SHUT IF SMOKE IS DETECTED IN
 ONE SINGLE SYSTEM?
 10) M2.1: NOTE 8 REFERENCES P2.1 FOR THE RTU CONDENSATE
 DISPOSAL PLAN, HOWEVER P2.1 SHOWS ONLY DETAILS FOR THE
 NEW RTU #5, AND ALL OTHER UNITS ARE LABELED AS EXISTING
 WITH EXISTING DISPOSAL: PLEASE CORRECT AND PROVIDE
 COMPLETE DETAILS.
 11) PROVIDE AC LOAD CALCULATIONS FOR ALL OF THE NEW
 SYSTEMS IN ACCORDANCE WITH ACCA MANUAL J, OR
 ASHRAE/ACCA STANDARD 183- SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 12) PROVIDE ENERGY CALCULATION IN COMPLIANCE WITH
 SECTION 101.4.3, AND TABLE 101.4.1 FBC-10 ENERGY.
 13) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE
 ENGINEER OF RECORD THAT INCLUDES MANUFACTURER'S SPECS
 FOR THE AC EQUIPMENT, EXHAUST FANS, DUCT SMOKE
 DETECTORS, AND AC CURBS AND STANDS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-09-23 Cont ID  
Sent By gjohnson Date 2015-09-23 Time 17:20 Rev Time 0.00
Received By gjohnson Date 2015-09-23 Time 17:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By tklarge Date 2015-08-31 Time 14:20 Rev Time 0.00
Received By tklarge Date 2015-08-28 Time 14:00 Sent To  
Notes
2015-08-28 14:03:411) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER THE 2010 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.
 2) SUBMIT TWO COPIES OF MANUF. INSTALLATION
 INSTRUCTIONS FOR THE CONCENTRIC VENT FOR GWH-2. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT FACTORY SIZING CALCULATIONS DONE BY SCHIER
 FOR THE GREASE TRAPS PER THE 2010 FBC-PLUMBING
 SEC.1003.2.CONTACT LEE SCHNEEWEISS AT 1-800-538-4792.
 2ND REQUEST.
 4) THE BRANCH VENT CONNECTING THE VENTS FROM THE MEN'S
 AND WOMEN'S RESTROOM EXCEEDS 40 FT. IN DEVELOPED LENGTH
 AND SHALL BE INCREASED ONE PIPE SIZE FOR IT'S ENTIRE
 LENGTH PER FBC-PLUMBING SEC.916.4.1.
 (NOTE: THE PREVIOUS COMMENT HAD A TYPO ERROR. IT READ
 "OR IT'S ENTIRE LENGTH" WHEN IT SHOULD HAVE READ "FOR
 IT'S ENTIRE LENGTH." )
 5) SHT.P0.1 - THE TOTAL FLOW- THRU FOR THE INTERCEPTORS
 IS SHOWN AS 85 GPM BUT THE TOTAL GPM IS SHOWN AS
 95.08.PLEASE CLARIFY THE DIFFERENCE WITH THESE TWO
 NUMBERS. I WOULD THINK THEY SHOULD BE THE SAME.
 6) SHT. P3.1 - MY TABULATION OF THE SECTIONS OF GAS
 PIPE FOR THE DEVELOPED LENGTH IS 143 FT. THE GAS
 INFORMATION BOX NOTES 125 FT.THE PIPING IS SIZED
 CORRECTLY IN ITS ENTIRETY.PLEASE CHECK YOUR TABULATION
 AND MAKE ANY NECESSARY CORRECTION TO THE INFFORMATION.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR BOTH OF THE
 WATER HEATERS AND KITCHEN EQUIPMENT PER THE 2010 FBC-
 FUEL GAS CODE SEC.304. NOTE #18 ON SHT.M1.1 REFERS TO
 SEC.306.6.2 OF 2010 FGC. THERE IS NO SUCH CODE SECTION.
 REFER TO 2010 FGC SEC.304.6.2 FOR COMBUSTION AIR FOR
 THE WATER HEATERS. PER SEC.304.10, THE NET FREE AREA OF
 METAL LOUVERS IS ASSUMED TO BE 75%,
 8) PER 2010 FBC TABLE 403.1 FOOTNOTE G, A UNISEX TOILET
 ROOM SHALL BE PROVIDED. THE ROUTE TO PUBLIC TOILET
 FACILITIES SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS PER 2010 FBC-PLUMBING SEC.403.3.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By tklarge Date 2015-06-23 Time 10:32 Rev Time 0.00
Received By tklarge Date 2015-06-23 Time 04:32 Sent To  
Notes
2015-06-23 09:35:111) THIS FACILITY SHALL COMPLY WITH THE EXCEPTION LISTED
 IN THE 2010 FBC-PLUMBING, SEC.403.1.3 - 403.1.3 POTTY
 PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THERE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
 2) SHT. A1.01 - SHOW THE CLEAR INSIDE DIMENSIONS OF THE
 EMPLOYEE RESTROOM #115. (L X W) . WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) SHT. A1.02 - PLEASE LABEL THE EMPLOYEE RESTROOM AS
 "UNISEX" IN LIEU OF "BOTH". THE TERM "BOTH" IS NOT CODE
 LANGUAGE.
 4) SHT. A2.01 -ELEVATION DETAIL #8 & 15 - THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 FROM THE FINISH FLOOR, NOT TO THE CENTERLINE AS SHOWN.
 2010 FBC- ACCESSIBILITY, SEC. 609.4.
 5) SHT. A2.01 - SHOW THE REQUIRED KNEE AND TOE
 CLEARANCES FOR THE LAVATORIES. COMPLY WITH THE FAC
 SEC.306.
 6) SHT.P.0 - GENERAL PLUMBING NOTES #38 - AIR SHALL NOT
 BE USED TO TEST PLASTIC PIPE PER 2010 FPC SEC.312.1.
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE FUEL GAS CODE SEC. 301.3.
 8) SUBMIT DETAILS FOR THE VENT FOR GWH-2. THE VENT
 SHALL COMPLY W/2010 FUEL GAS CODE SEC. 502.THE NOTE ON
 P0.1 REFERS TO MECHANICAL PLANS FOR LAYOUT. THERE IS NO
 LAYOUT ON THE MECHANICAL PLANS. CLARIFY.
 9) THE GREASE TRAP CALCULATIONS SHALL BE REVIEWED BY
 SHIER TO ENSURE CORRECT SIZING OF THE INTERCEPTORS PER
 2010 FPC SEC.1003.2.CONTACT LEE SCHNEEWEISS AT
 1-800-538-4792.
 10) SHT. P0.1 - MIXING VALVE DETAIL - INDICATE THE SIZE
 OF THE COLD WATER SUPPLY.
 11) SHT. P1.2 - THE PLUMBING DRAWINGS SHALL BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD PER THE
 FL. ADMIN. CODE. RULE 61G15-23.002.
 12) INDICATE THE PSI OF THE GAS SYSTEM ON SHT.P3.1.
 13) SHT.P3.2 - THE HANDICAP WATER CLOSET IN THE WOMEN'S
 RESTROOM SHALL BE INDIVIDUALLY VENTED OR THE SYSTEM
 SHALL BE DESIGNED AS A CIRCUIT VENT SYSTEM IN
 ACCORDANCE PER 2010 FPC SEC. 911.
 14) IT APPEARS THAT THE BRANCH VENT CONNECTING THE
 VENTS FROM THE MEN'S & WOMEN'S RESTROOM EXCEEDS 40 FT.
 IN DEVELOPED LENGTH AND SHALL BE INCREASED ONE PIPE
 SIZE PER FPC SEC. 916.4.1 FOR IT'S ENTIRE LENGTH.
 15) SUBMIT A RISER DETAIL FOR ALL THE CONDENSATE
 PIPING. THE MECHANICAL PLANS APPEAR TO SHOW ALL NEW
 RTU'S & SHT. P2.1.ONLY SHOWS RTU 5 AS BEING NEW.
 CLARIFY.
 16) SHOW ALL THE GREASE TRAPS AND PIPE SIZING ON THE
 SANITARY RISER. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 17) SHT. P0.1 - THERE ARE CALCULATIONS FOR THE GREASE
 INTERCEPTORS BASED ON THE PDI G101 STANDARD AND ALSO ON
 THE FL. ADMIN. CODE RULE 64E-6. THE F.A.C. 64E-6 IS FOR
 GRAVITY TYPE INTERCEPTORS AND THE PDI G101 IS FOR THE
 HYDROMECHANICAL TANKS WHICH ARE ON THE PLANS. YOU
 CANNOT USE BOTH.CLARIFY.
 18) SHT. P0.1 - CHECK YOUR FLOW THROUGH CALCULATIONS. I
 CALCULATE 95.08 GPM.
 19) SHT. P0.1 - IN THE FLOW THROUGH (GPM) CALCULATIONS,
 THE TOTAL GPM HAS BEEN MULTIPLIED BY 24. WHERE IS THIS
 NUMBER FROM? CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 12:28 Sent To  
Notes
2015-10-01 12:29:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: THURS. OCT.01/2015
 ACTION: BUILDING PROVISO
  
 1) ALL PRODUCT APPROVALS HAVE BEEN REQUESTED BY THE
 DESIGNER OF RECORD TO BE DEFERRED SUBMITTALS UNTIL
 AFTER PERMIT ISSUANCE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 NOTE: MANY OF THE PRODUCT APPROVALS HAVE MORE THAN ONE
 TYPE OF GLAZING, IDENTIFY TYPE OF GLAZING, WIDTH,
 HEIGHT, TYPE OF ANCHORS AND ASSOCIATED PRESSURES.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS, & ROOF TOP EXHAUST FANS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-09-02 Cont ID  
Sent By jwitmer Date 2015-09-02 Time 16:02 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 15:15 Sent To  
Notes
2015-09-02 16:02:40ROOFING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETEMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 02/2015
 ACTION: DENIED
  
 1A) A ROOFING PERMIT WILL BE REQUIRED FOR THE NEW
 STANDING SEAM METAL ROOFING AND FLAT ROOF REPAIRS. THE
 SUBMITTED PRODUCT APPROVALS WERE NOT REVIEWED BY THE
 DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 FLAT ROOF NOA SUBMITTED 12-0307.02 FIRESTONE ULTRAPLY
 TPO SINGLE PLY ROOF SYSTEMS OVER WOOD DECK. NOTE NO
 SUB-SYSTEM WAS IDENTIFIED, VARIOUS SUB-SYSTEMS HAVE
 VARYING PRESSURES. WILL NEED RAS 117 CALCULATIONS BY A
 SIGNED & SEALED BY A DESIGN PROFESSIONAL.
  
 STEEL ROOF PANELS NOA 10-1018.04 ONCE REVIEWED BY
 DESIGN PROFESSIONAL AND SHOP DRAWING STAMP OF APPROVAL
 IS AFFIXED WE WILL BE ABLE TO REVIEW FOR CODE
 COMPLIANCE.
  
 (G) PRE-ENGINEERED CURBS, EXHAUST FANS & CURB NOR A/C
 STANDS
 NOTE, THE ROOF TOP CURB FOR THE RTU UNITS PRODUCT
 APPROVAL CAN NOT BE VERIFIED, IT IS A OLDER REVSION AND
 NOT WHAT IS ON THE FLORIDA WEBSITE UNDER FL 1503.1.
 PLEASE UPDATE AND ALSO INCLUDE THE FLORIDA PRODUCT
 APPROVAL COVERSHEET IDENTIFING WHICH REVISION IT IS.
  
 NO PRE-ENGINEERED A/C STANDS OR EXHAUST FANS SUBMITTED
 SHOWN ON SHEET A1.08 & M0.1.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By jwitmer Date 2015-06-06 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2015-06-06 Time 12:14 Sent To  
Notes
2015-06-06 12:17:24ROOFING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETEMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 06/2015
 ACTION: DENIED
  
 1) A ROOFING PERMIT WILL BE REQUIRED FOR THE NEW
 STANDING SEAM METAL ROOFING AND FLAT ROOF REPAIRS. NO
 PRODUCT APPROVALS WERE SUBMITTED UNDER THE FIRST
 REVIEW,COMPONENTS & CLADDING
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  