Plan Review Details - Permit 15051314
Plan Review Stops For Permit 15051314
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-20 Cont ID  
Sent By jwitmer Date 2015-07-20 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-07-20 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2015-07-17 Time   Sent To  
Notes
2015-07-17 09:35:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051314
 ADD: 400 N. FLAGLER DR. SUITE # 703
 CONT: CUSTOM CONSTRUCTION
 TEL: (561)670-0779
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 17/2015
 ACTION: DENIED
  
 1A) SEMI-COMPLIED. THE PRODUCT APPROVALS HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD AS FAR AS PRESSURES.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 1B) THE CONCERN IS WITH THE EASTERN FD 8100 SLIDING
 GLASS DOOR SYSTEM PAGE 4 OF 6 IN THE PRODUCT APPROVAL
 THE DESIGN PRESSURE IS +/- 60 PSF FOR AN OPENING SIZE
 OF 240 IN. X 120 IN. PLEASE HAVE EASTERNS ENGINEER
 PROVIDE A RATIONAL ANALYSIS FOR THE PRESSURES FOR THE
 VAROIUS SIZE OPENINGS. FOR SMALLER OPENINGS THE
 PRESSURES RISE AS WELL AS THE POSITIVE PRESSURES, THE
 BUILDING IS A 23 STORY HIGH RISE IN AN EXPOSURE D.
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE.THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS THAT PROVIDE
 SUPPORTING DOCUMENTATION THAT THE PROPOSED PENETRATION
 AND OPENING DETAILS DESCRIBED IN THE CONSTRUCTION
 DOCUMENTS MAINTAIN THE WEATHER RESISTANCE OF THE
 EXTERIOR WALL ENVELOPE. THE SUPPORTING DOCUMENTATION
 SHALL FULLY DESCRIBE THE EXTERIOR WALL SYSTEM WHICH WAS
 TESTED, WHERE APPLICABLE, AS WELL AS THE TEST PROCEDURE
 USED.
  
 2) COMPLIED. FLOOR INSULATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 08:44 Rev Time  
Received By jwitmer Date 2015-06-22 Time   Sent To  
Notes
2015-06-22 08:44:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051314
 ADD: 400 N. FLAGLER DR. SUITE # 703
 CONT: CUSTOM CONSTRUCTION
 TEL: (561)670-0779
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 22/2015
 ACTION: DENIED
  
 1) SHEET # 1 INDICATES NEW SLIDDING GLASS DOORS AND THE
 EXPOSURE GIVEN IS A C EXPOSURE. THIS EXPOSURE IS
 CONSIDERED A D EXPOSURE 2010 FBC-B 1609.4.3. PLEASE
 PROVIDE THE PRESSURES FOR THE 240 FT. HIGH, HIGH RISE
 IN EXPOSURE D. THE UNKNOWN VARIABLE IS THIS UNIT IN A
 WALL ZONE 4 OR A WALL ZONE 5, A END ZONE?
  
 2) THE PLANS ALSO INDICATE THE REMOVAL OF FLOOR
 COVERINGS AND THE USE OF SAM 3 90, PLEASE SUBMIT THE
 ACTUAL TEST REPORTS FOR THIS PRODUCT AND FOR THE FLOOR
 THICKNESS AT 6 INCHES, UNLESS VERIFIED BY AN ENGINEER.
 THE TEST REPORTS NEED TO BE APPROVED TO:
  
 2FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-16 Cont ID  
Sent By skennedy Date 2015-07-16 Time 08:01 Rev Time 0.00
Received By skennedy Date 2015-07-16 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-30 Cont ID  
Sent By dhayes Date 2015-05-30 Time 13:10 Rev Time 0.00
Received By dhayes Date 2015-05-30 Time 13:10 Sent To  
Notes
2015-05-30 13:58:165/30/2015
 PROJECT: GIBB RENNOVATION
 PERMIT#: 15051314
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) CHANGE THE "CODE" NOTE ATE THE BOTTOM RIGHT ON SHEET
 1 TO READ THE 2008 EDITION OF THE NFPA 70 (NEC)
 NATIONAL ELECTRICAL CODE.
  
 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET. NEC 210.52
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 5) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)
  
 6) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. PROVIDE THE OCPD AND
 CORRESPONDING WIRE SIZE FOR NEC 408.4
  
 7) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING.
  
 8) INDICATE OR VERIFY THE INSTALLATION OF SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 9))BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL
 BE USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C)
  
 10) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. NEC 210.52 (D)
  
 11) PROVIDE A LIGHTING FIXTURE SCHEDULE TO IN CLUDE THE
 UNDER CABINET LIGHTING MENTIONED IN THE NOTE ON SHEET
 1. ALL LIGHTING TO BE IN COMPLIANCE WITH THE FBC-E, NEC
 410, AND NEC 110.3
  
 12) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC
 210.52(E)(3).
  
 13) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, FIRE SPRINKLER, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-09 Cont ID  
Sent By pleduc Date 2015-07-09 Time   Rev Time 0.00
Received By pleduc Date 2015-07-09 Time 11:18 Sent To  
Notes
2015-07-09 11:24:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 13:31 Sent To  
Notes
2015-06-03 13:40:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2015-07-07 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-23 Cont ID  
Sent By hmoser Date 2015-06-23 Time 14:53 Rev Time  
Received By hmoser Date 2015-05-29 Time   Sent To  
Notes
2015-05-30 14:03:58B06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-06-23 Cont ID  
Sent By hmoser Date 2015-06-23 Time 14:52 Rev Time 0.00
Received By hmoser Date 2015-06-23 Time 14:52 Sent To  
Notes
2015-06-23 14:53:29NO MECHANICAL WORK BEING DONE AT THIS TIME HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-16 Cont ID  
Sent By skennedy Date 2015-07-16 Time 08:01 Rev Time 0.00
Received By skennedy Date 2015-07-16 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By tklarge Date 2015-06-16 Time 06:15 Rev Time 0.00
Received By tklarge Date 2015-06-16 Time 05:54 Sent To  
Notes
2015-06-16 05:40:32THE PLANS ARE VAGUE AS TO THE SCOPE OF PLUMBING WORRK
 TO BE DONE UNDER THIS PERMIT. INDICATE ON THE PLANS
 WHAT IS EXISTING TO REMAIN AND WHAT IS TO BE REPLACED.
 WPB AMEND. TO FBC 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  