Plan Review Details - Permit 15051275
Plan Review Stops For Permit 15051275
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By dhayes Date 2015-06-19 Time 11:41 Rev Time 0.00
Received By dhayes Date 2015-06-19 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By dhayes Date 2015-06-02 Time 08:52 Rev Time 0.00
Received By dhayes Date 2015-06-02 Time 08:52 Sent To  
Notes
2015-06-02 09:46:236/2/2015
 PROJECT: SOLAR EATER HEATER
 PERMIT#: 15051275
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE PLANS DO NOT SHOW THAT THE PUMP IS A PLUG IN
 UNIT. PROVIDE THE MANUFACTURER DOCUMENTATION ON THE
 PUMP. INDICATE ON THE PLAN IF THERE IS AN EXISTING
 RECEPTACLE FOR THE PUMP TO PLUG INTO. IF NOT REVISE THE
 PLAN TO INDICATE REQUIRED RECEPATCLE OUTLET(S). A
 SEPARATE ELECTRIC PERMIT IS REQUIRED FOR THE
 INSTALATION OF ANY ELECTRICAL CIRCUITRY THAT IS
 REQUIRED AND NOT CURRENTLY EXISTING TO REMAIN. WPB
 AMEND. TO 2010 FBC SEC.107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-19 Cont ID  
Sent By dhayes Date 2015-06-19 Time 11:41 Rev Time 0.00
Received By dhayes Date 2015-06-18 Time 06:52 Sent To  
Notes
2015-06-18 06:52:42SENT TO T LARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By dhayes Date 2015-06-02 Time 09:46 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By tklarge Date 2015-06-19 Time 06:33 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 05:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By tklarge Date 2015-06-02 Time 04:41 Rev Time 0.00
Received By tklarge Date 2015-06-02 Time 03:53 Sent To E
Notes
2015-06-02 04:43:44SENT TO ELEC. TO DETERMINE IF ELECTRIC PERMIT IS
 REQUIRED.
2015-06-02 04:41:291) SUBMIT A PIPING DIAGRAM SHOWING THE PIPING, PUMP,
 VALES, TYPE OF PIPE MATERIAL, ETC.FROM THE COLLECTOR TO
 THE WATER STORAGE TANK. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) THE HAND DRAWN PLANS SHOW THE COLLECTOR LOCATED ON A
 FLAT ROOF BUT DRAWING SL-3C SSHOWS THE PLANS FOR A
 SLOPED ROOF. SUBMIT SIGNED AND SEALED PLANS FOR THE
 COLLECTOR LOCATED PN A FLAT ROOF.
 3) SUBMIT WIND LOAD ENGINEERING FOR THE COLLECTOR
 LOCATED ON A FLAT ROOF. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 4) THE CONNECTION FROM THE POTABLE WATER SYSTEM SHALL
 BE EQUIPPED WITH BACKFLOW PROTECTION PER 2010 FBCR,
 SEC.M2301.5, P2902.5.5. (SEE EXCEPTION).
 5) THE PLANS DO NOT SHOW THAT THE PUMP IS A PLUG IN
 UNIT OR AN EXISTING REPTACLE IF IT IS, AND THERE IS
 ALSO A SPEC SHEET FOR A TEMPERATURE CONTROL DEVICE. A
 SEPARATE ELECTRIC PERMIT MAY BE REQUIRED. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 6) SECTION 403.4.3.2.3 OF 2010 FL. ENERGY CODE REQUIRES
 THAT THE SOLAR COLLECTORS BE TESTED IN ACCORDANCE WITH
 ISO STANDARD 9806 AND SRCC STANDARD TM-1. SUBMIT
 VERIFICATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  