Plan Review Details - Permit 15051140
Plan Review Stops For Permit 15051140
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-01-07 Cont ID  
Sent By skennedy Date 2016-01-07 Time 14:24 Rev Time 0.00
Received By skennedy Date 2016-01-07 Time 14:24 Sent To HIST
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-12-12 Cont ID  
Sent By jwitmer Date 2015-12-12 Time   Rev Time 0.00
Received By jwitmer Date 2015-12-11 Time 06:30 Sent To  
Notes
2015-12-11 07:24:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051140
 ADD: 412/ 414 50 TH ST. UNITS A & B
 CONT: BMB SOLUTIONS CORP
 TEL: (561)503-1415
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. DEC. 11/ 2015
 ACTION: DENIED
  
 1-6) COMPLIED.
  
 7) NEW COMMENT!!!!!!
 7A)BOTH THE CONTRACTOR NOTIFIED ME AND ANGELLA JONES
 VAN THAT THE REAR BUILDING THE 1ST FLOOR APPEARS TO BE
 A ILLEGAL CONVERSION OF A GARARE TO APARTMENT UNIT. THE
 CONTRACTOR WILL NEED TO COME IN AND ON THE PERMIT
 APPLICATION INDICATE UNDER THE DESCRIPTION OF WORK THAT
 THE 1ST FLOOR IS A CHANGEOF OCCUPANCY.
  
 7B) THE 2ND ISSUE THAT HAS BEEN BROUGHT TO LIGHT THAT
 ANGELLA JONE VAN GOING THROUGH THE CITY RECORD HASN'T
 BEEN ABLE TO FINE A PERMIT FOR THE CONNECTING CARPORT
 FROM THE FRONT BUILDING TO THE REAR BUILDING.
  
 7C) THE OWNERS WILL NEED TO HIRE A ENGINEER TO VERIFY
 CODE COMPLIANCE FOR BOTH THE 1ST FLOOR CHANGE OF
 OCCUPANCY AS WELL AS THE CARPORT AND WHAT APPEARS AS A
 CONCRETE EXTERIOR STAIR TO VERIFY CODE COMPLIANCE AND
 IF NEEDED WHAT WOULD NEED TO BE COMPLETED IN ORDER TO
 MAKE A CODE COMPLIANT BUILDING.
  
 7D) IN TTHE PERMIT PACKAGE THERE IS A LETTER NOT DATED,
 NOT DATE STAMPED BY THE CITY TO SHOW WHEN SUBMITTED
 CANCEALING PERMIT 15070089TO 15051140 AND THEN ONLY 4X
 FEES OCCUR TO THE FRONT BUILDING. NOTICE !!!! BUILDING
 PLAN REVIEW WAS LED TO BELIEVE NO WORK WAS TO BE
 REVIEWED UNDER THIS PERMIT FOR THE FRONT
 BUILDING!!!!!!!!!
 PLEASE LIST WHAT WORK WAS TO BE COMPLETED IN THE FRONT
 BUILDING UNDER THIS PERMIT!!!!!!
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-08 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2015-10-08 Time 07:15 Sent To  
Notes
2015-10-08 08:24:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051140
 ADD: 412/ 414 50 TH ST. UNITS A & B
 CONT: BMB SOLUTIONS CORP
 TEL: (561)503-1415
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. OCT. 08/ 2015
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3A) 3RD REQUEST. WINDOWS AND DOORS IN THE FOOTPRINT OF
 THE STAIR (VERTICALLY) REQUIRES 1 HOUR OPENING
 PROPECTIVES!!! NO FIRE SHUTTER WAS SUBMITTED FOR 1 HOUR
 OR 3/4 HOUR. SHEET A1.1 IT APPEARS THAT THE WINDOWS AND
 DOORS ARE BEING REPLACED WITHIN 10 FEET OF THE STAIR
 AND LANDING ON BOTH THE FRONT AND REAR BUILDINGS. IT
 APPEARS THAT EACH UPPER APARTMENT IS A SINGLE MEANS OF
 EGRESS, NO ELEVATIONS PROVIDED TO VERIFY. SINGLE MEANS
 OF EGRESS WILL NEED 1 HOUR FIRE SEPARATION,COMPLY UNDER
 SECTION FBC-B 1019.2., FBC-B 1026.6 EXC. # 2 & 2007
 FBC-B COMMENTARY FIGURE 1023.6(1) PROTECTION OF
 EXTERIOR STAIRWAYS. DOORS AND WINDOWS WITHIN THE
 FOOTPRINT OF THE EXTERIOR STAIR REQUIRE 1 HOUR FIRE
 RATING AND WINDOWS AND DOORS WITHIN 10 FT. OF THE
 LANDINGS AND STAIR REQUIRE 3/4 HR. OPENING PROTECTIVES.
 SHOW THE FULL LENGTH OF THE EXTERIOR STAIR AND LANDINGS
 TO DETERMINE WHICH OPENINGS REQUIRE A 1 HOUR FIRE
 RATING AND WHICH REQUIRE 3/4 HOUR FIRE RATING.
  
 3B)2ND REQUEST. NOTE WINDOWS AND DOORS THAT HAVE 3/4 HR
 AND OR 1 HOUR FIRE RATING NORMALLY DO NOT HAVE LARGE
 MISSILE RESISTANT TESTING AND STORM SHUTTERS WILL NEED
 TO BE INSTALLED ON THESE OPENINGS. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR CODE COMPLIANCE:
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5.,
 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE
  
 4) SEMI-COMPLIED, 2 DOOR APPROVALS FROM 2 DIFFERENT
 MANUFACTURERS, 2 WINDOW PRODUCT APPROVALS FROM 2
 DIFFERENT MANUFACTURERS & 2 MULLION PRODUCT APPROVALS
 FROM 2 DIFFERENT MULLION MANUFACTURERS WERE SUBMITTED.
 PLEASE IDENTIFY THEIR LOCATION ON THE PLAN WHERE THEY
 ARE GOING TO BE INSTALLED.
  
 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL ADMINISTRATIVE CODE.
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 NOTE THE JELD-WEN DOORS NOT REVIEWEDD BY THE DESIGNER
 OF RECORD.
 TRULITE DOOR SUBMITTAL NO FLORIDA APPROVAL NUMBER NOR
 NOA. ONLY ONE COPY.
 NO WINDOW REPORT SUBMITTED ONLY THE INTER LAYER OF
 DUPONT BUTACITE PVB INTERLAYER NOA 11-0624.01
 NO MULLION REPORT SUBMITTED.
  
 5) COMPLIED. PLEASE 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS & MULLIONS IDENTIFY WINDOW SIZES, GLAZING
 OPTIONS, MULLION IF REINFORCED, OPTIONS FOR ANCHORING
 AND PRESSURES.
 (E) SHUTTERS
  
 6) 3RD REQUEST THE CONTRACTOR HAS NOT SUBMITTED ANY
 TEST REPORTS FOR REVIEW!!!!!!!! SHEET A.2 INDICATES NEW
 FLOORING BUT NO INFORMATION ON THE 2ND FLOOR
 INSULATION, PLEASE PROVIDE TESTING FOR THE FOLLOWING
 (3) CODE SECTIONS:
  
 NOTE: A UL REPORT WAS SUBMITTED FOR THE REQUIREMENT OF
 1 HOUR FIRE SEPARATION, WITHIN THE REPORT THERE ARE 17
 SUB-SYSTEMS WHICH ARE TO BE INSTALLED? THERE IS ALSO A
 USG REPORT SUBMITTED WITH A 1 HOUR FIRE RATING, IF THIS
 REPORT IS FOR SOUND IT DOES NOT MEET THE REQUIRED STC &
 IIC RATING OF 50.
  
 6A) 2ND REQUEST. FBC-B 2010 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) 2ND REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 6C) 2ND REQUEST. TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION. INSULATING MATERIALS,
 WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE
 OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 10/13/2015 PICTURES SENT BY E-MAIL FROM THE CONTRACTOR
 INDICATE WHAT APPEARS TO BE A 2ND EXTERIOR STAIR NOT
 SHOWN ON THE PLANS THAT APPEARS TO HAVE BEEN
 UNPERMITTED WORK. THIS STAIR MUST BE REMOVED, THE
 HANDRAIL / GUARDRAIL SYSTEM IS NOT IN COMPLIANCE WITH
 THE CODE, FOR A R2 UNIT. THE SECOND ISSUE IS WITH THE
 STAIR UPPER LANDING ENDING WITH THE ROOF TOP FLAT DECK,
 THIS MAKES THIS AREA LIVEABLE SPACE, NEED TO PROVIDE
 LIVE LOADS FOR ROOF DECK AND SIZE AND SPAN FOR ROOF
 JOIST. REMOVE STAIRS OR MAKE CODE COMPLIANT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2015-09-10 Time   Sent To  
Notes
2015-09-10 13:33:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051140
 ADD: 412/ 414 50 TH ST. UNITS A & B
 CONT: BMB SOLUTIONS CORP
 TEL: (561)503-1415
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 10/ 2015
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3A) 2ND REQUEST. SHEET A1.1 IT APPEARS THAT THE WINDOWS
 AND DOORS ARE BEING REPLACED WITHIN 10 FEET OF THE
 STAIR AND LANDING ON BOTH THE FRONT AND REAR BUILDINGS.
 IT APPEARS THAT EACH UPPER APARTMENT IS A SINGLE MEANS
 OF EGRESS, NO ELEVATIONS PROVIDED TO VERIFY. SINGLE
 MEANS OF EGRESS WILL NEED 1 HOUR FIRE SEPARATION,COMPLY
 UNDER SECTION FBC-B 1019.2., FBC-B 1026.6 EXC. # 2 &
 2007 FBC-B COMMENTARY FIGURE 1023.6(1) PROTECTION OF
 EXTERIOR STAIRWAYS. DOORS AND WINDOWS WITHIN THE
 FOOTPRINT OF THE EXTERIOR STAIR REQUIRE 1 HOUR FIRE
 RATING AND WINDOWS AND DOORS WITHIN 10 FT. OF THE
 LANDINGS AND STAIR REQUIRE 3/4 HR. OPENING PROTECTIVES.
 SHOW THE FULL LENGTH OF THE EXTERIOR STAIR AND LANDINGS
 TO DETERMINE WHICH OPENINGS REQUIRE A 1 HOUR FIRE
 RATING AND WHICH REQUIRE 3/4 HOUR FIRE RATING.
  
 3B)2ND REQUEST. NOTE WINDOWS AND DOORS THAT HAVE 3/4 HR
 AND OR 1 HOUR FIRE RATING NORMALLY DO NOT HAVE LARGE
 MISSILE RESISTANT TESTING AND STORM SHUTTERS WILL NEED
 TO BE INSTALLED ON THESE OPENINGS. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR CODE COMPLIANCE:
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5.,
 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE
  
 4) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL ADMINISTRATIVE CODE.
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 NOTE THE JELD-WEN DOORS NOT REVIEWEDD BY THE DESIGNER
 OF RECORD.
 TRULITE DOOR SUBMITTAL NO FLORIDA APPROVAL NUMBER NOR
 NOA. ONLY ONE COPY.
 NO WINDOW REPORT SUBMITTED ONLY THE INTER LAYER OF
 DUPONT BUTACITE PVB INTERLAYER NOA 11-0624.01
 NO MULLION REPORT SUBMITTED.
  
 5) 2ND REQUEST. PLEASE 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS & MULLIONS IDENTIFY WINDOW SIZES, GLAZING
 OPTIONS, MULLION IF REINFORCED, OPTIONS FOR ANCHORING
 AND PRESSURES.
 (E) SHUTTERS
  
 6) 2ND REQUEST THE CONTRACTOR HAS NOT SUBMITTED ANY
 TEST REPORTS FOR REVIEW!!!!!!!! SHEET A.2 INDICATES NEW
 FLOORING BUT NO INFORMATION ON THE 2ND FLOOR
 INSULATION, PLEASE PROVIDE TESTING FOR THE FOLLOWING
 (3) CODE SECTIONS:
  
 6A) 2ND REQUEST. FBC-B 2010 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) 2ND REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 6C) 2ND REQUEST. TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION. INSULATING MATERIALS,
 WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE
 OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 07:30 Rev Time  
Received By jwitmer Date 2015-06-22 Time   Sent To  
Notes
2015-06-22 07:40:29 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051140
 ADD: 412/ 414 50 TH ST. UNITS A & B
 CONT: BMB SOLUTIONS CORP
 TEL: (561)503-1415
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 22/ 2015
 ACTION: DENIED
  
 1) THE PLANS INDICATE WORK BEING COMPLETED IN BOTH THE
 FRONT AND BACK UNITS, BUT NO ADDRESS IS GIVEN TO THE
 BACK UNITS TO BE ABLE TO IDENTIFY THEM. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF WORK
 BEING PREFORMED UNDER THIS PERMIT.
 2010 FBC-B 501.2 ADDRESS IDENTIFICATION.
  
 2) SHEET A1.2 DESIGGN PARAMETERS AND CODE REFERANCES
 BOTH REFERANCE THE 2010 FBC-RESIDENTIAL CODE. PLEASE
 NOTE THE RESIDENTIAL CODE IS FOR 1 & 2 FAMILY ONLY.
 THIS REVIEW IS BEING COMPLETED UNDER THE 2010
 FBC-BUILDING CODE. OCCUPANCY R2.
  
 3A) SHEET A1.1 IT APPEARS THAT THE WINDOWS AND DOORS
 ARE BEING REPLACED WITHIN 10 FEET OF THE STAIR AND
 LANDING ON BOTH THE FRONT AND REAR BUILDINGS. IT
 APPEARS THAT EACH UPPER APARTMENT IS A SINGLE MEANS OF
 EGRESS, NO ELEVATIONS PROVIDED TO VERIFY. SINGLE MEANS
 OF EGRESS WILL NEED 1 HOUR FIRE SEPARATION,COMPLY UNDER
 SECTION FBC-B 1019.2., FBC-B 1026.6 EXC. # 2 & 2007
 FBC-B COMMENTARY FIGURE 1023.6(1) PROTECTION OF
 EXTERIOR STAIRWAYS. DOORS AND WINDOWS WITHIN THE
 FOOTPRINT OF THE EXTERIOR STAIR REQUIRE 1 HOUR FIRE
 RATING AND WINDOWS AND DOORS WITHIN 10 FT. OF THE
 LANDINGS AND STAIR REQUIRE 3/4 HR. OPENING PROTECTIVES.
 SHOW THE FULL LENGTH OF THE EXTERIOR STAIR AND LANDINGS
 TO DETERMINE WHICH OPENINGS REQUIRE A 1 HOUR FIRE
 RATING AND WHICH REQUIRE 3/4 HOUR FIRE RATING.
  
 3B) NOTE WINDOWS AND DOORS THAT HAVE 3/4 HR AND OR 1
 HOUR FIRE RATING NORMALLY DO NOT HAVE LARGE MISSILE
 RESISTANT TESTING AND STORM SHUTTERS WILL NEED TO BE
 INSTALLED ON THESE OPENINGS. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR CODE COMPLIANCE:
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5.,
 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 NOTE THE JELD-WEN DOORS NOT REVIEWEDD BY THE DESIGNER
 OF RECORD.
  
 5) PLEASE 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS & MULLIONS IDENTIFY WINDOW SIZES, GLAZING
 OPTIONS, MULLION IF REINFORCED, OPTIONS FOR ANCHORING
 AND PRESSURES.
 (E) SHUTTERS
  
 6) SHEET A.2 INDICATES NEW FLOORING BUT NO INFORMATION
 ON THE 2ND FLOOR INSULATION, PLEASE PROVIDE TESTING FOR
 THE FOLLOWING (3) CODE SECTIONS:
 6A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 6C)TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION. INSULATING MATERIALS,
 WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE
 OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-01-07 Cont ID  
Sent By skennedy Date 2016-01-07 Time 14:24 Rev Time 0.00
Received By skennedy Date 2016-01-07 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 11:50 Rev Time 0.00
Received By skennedy Date 2016-01-05 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 17:54 Rev Time 0.00
Received By albarran Date 2015-11-05 Time 16:40 Sent To I
Notes
2015-11-05 17:55:02THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC,
 (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE
 DEFICIENCIES NOTED.
  
 1. NEC 210.52(E)(2) THERE SHALL BE AN EXTERIOR GFI
 OUTLET FOR EACH GRADE LEVEL UNIT.
 2. NEC 210.63 THERE SHALL BE A SERVICE OUTLET WITHIN
 25? OF EACH OF THE CONDENSING UNITS.
 3. NEC 210.70(A)(2)(A) PERMITS AUTOMATIC CONTROL FOR
 ILLUMINATION OF EXTERIOR STAIRWAYS.
 4. NEC 215.5 YOU SHALL PROVIDE A SITE SPECIFIC FEEDER
 DIAGRAM SHOWING FEEDER DETAILS, CONDUCTOR SIZING AND
 LOAD CALCS. IN ADDITION TO THE TYPICAL UNIT CALCS,
 CALCS FOR THE COMPLETE SERVICE SHALL BE PROVIDED.
 5. NEC 300.5(B) WIRING CONDITIONS DICTATE CONDUCTOR
 INSULATION. YOUR NOTE 5 CALLS FOR THHN. NOTE: THAT IS
 NOT ACCEPTABLE FOR WET LOCATIONS.
 6. NEC 314.27 HAS SPECIFIC WEIGH REQUIREMENTS FOR
 CEILING LUMINAIRE OUTLETS AND PADDLE FAN OUTLETS.
 7. NEC 406.8(B) RECEPTACLES INSTALLED OUTDOORS IN
 ADDITION TO THE IN-USE TYPE COVERS, SHALL BE LISTED
 ?WR? WEATHER RESISTANT.
 8. FBC-R 302.4.1 REQUIRES THAT ALL PENETRATIONS OF FIRE
 RESISTANCE RATED WALL OR FLOOR ASSEMBLIES BE PROTECTED
 BY AN APPROVED FIRESTOP SEALING SYSTEM. INDICATE HOW
 THE FEEDERS TO THE UPPER LEVEL PANELS WILL BE RUN.
 9. FBC-R 302.13 REQUIRES MINIMUM OF 3? CLEARANCE FROM
 COMBUSTIBLE INSULATION FOR RECESSED LIGHTING.
 10. FBC-R 303.6 ALL EXTERIOR STAIRWAYS SHALL BE
 PROVIDED WITH A MEANS TO ILLUMINATE THE STAIRS,
 INCLUDING THE LANDINGS AND TREADS.
 11. FBC-E 402.4.5 RECESSED LIGHTING INSTALLED IN THE
 BLDG.?S THERMAL ENVELOPE SHALL BE IC RATED AND SEALED
 TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 NON-CONDITIONED SPACE.
 12. FBC-E 404 A MINIMUM OF 50% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 16:45 Rev Time 0.00
Received By dhayes Date 2015-07-09 Time 16:30 Sent To  
Notes
2015-07-09 16:45:35APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) R302.4 DWELLING UNIT RATED PENETRATIONS.
 PENETRATIONS OF WALL OR FLOOR/CEILING ASSEMBLIES
 REQUIRED TO BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH
 SECTION R302.2 OR R302.3 SHALL BE PROTECTED IN
 ACCORDANCE WITH THIS SECTION.
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-12-10 Cont ID  
Sent By pleduc Date 2015-12-09 Time   Rev Time 0.00
Received By pleduc Date 2015-12-09 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-31 Time 12:26 Sent To  
Notes
2015-08-31 12:49:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE FIRE EXTINGUISHERS FOR EACH UNIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 11:46 Sent To  
Notes
2015-08-31 12:48:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE FIRE EXTINGUISHERS FOR EACH UNIT.
2015-06-03 12:01:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE FIRE EXTINGUISHERS FOR EACH UNIT.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-01-08 Cont ID  
Sent By fmittner Date 2016-01-08 Time 15:08 Rev Time 0.00
Received By fmittner Date 2016-01-08 Time 15:08 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By fmittner Date 2016-01-05 Time 16:48 Rev Time 0.00
Received By fmittner Date 2016-01-05 Time 16:48 Sent To  
Notes
2016-01-05 16:48:41AWAITING RESUBMITTAL TO ADDRESS CONCERNS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-11-05 Cont ID  
Sent By fmittner Date 2015-11-05 Time 15:08 Rev Time 0.00
Received By fmittner Date 2015-11-05 Time 15:08 Sent To  
Notes
2015-10-06 10:03:0110/6/15

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-01-08 Cont ID  
Sent By lmarchan Date 2016-01-08 Time 08:09 Rev Time 0.00
Received By lmarchan Date 2016-01-07 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 16:50 Rev Time 0.00
Received By skennedy Date 2015-11-30 Time 15:35 Sent To  
Notes
2015-11-30 15:35:37B33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 17:56 Rev Time 0.00
Received By albarran Date 2015-10-01 Time 13:02 Sent To  
Notes
2015-11-05 17:57:2511/5/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "B". MA
2015-10-02 13:03:13B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2015-08-27 Time 10:33 Sent To  
Notes
2015-08-28 10:33:51B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-09 Cont ID  
Sent By dhayes Date 2015-07-09 Time 16:45 Rev Time 0.00
Received By dhayes Date 2015-05-28 Time 15:08 Sent To  
Notes
2015-05-28 15:08:40B33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-01-13 Cont ID  
Sent By skennedy Date 2016-01-13 Time 11:17 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-11 Cont ID  
Sent By jwitmer Date 2015-12-11 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2015-12-11 Time 07:26 Sent To  
Notes
2015-12-11 07:26:26BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-01-07 Cont ID  
Sent By skennedy Date 2016-01-07 Time 14:24 Rev Time 0.00
Received By skennedy Date 2016-01-07 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-12-08 Cont ID  
Sent By ccole Date 2015-12-08 Time 07:02 Rev Time 0.00
Received By ccole Date 2015-12-04 Time 14:50 Sent To  
Notes
2015-12-08 07:19:424TH REVIEW 2014 MECHANICAL
 PERMIT #15051140
 12/8/15
  
 1) I HAVE REMOVED THE AC CHANGEOUT FORMS AND AHRI
 CERTIFICATES FROM THE SUBMITTAL PACKAGE FOR THIS
 PROJECT PER ARCHITECT JAIMES PAINE'S DIRECTION- THEY
 ARE NOT RELEVANT TO THE PROPOSED PROJECT.
 2) PLEASE PROVIDE ENERGY CALCULATIONS AND AC COOLING
 AND HEATING CALCULATIONS FOR UNITS 412A AND 414A. THESE
 ARE THE TWO MAIN BUILDINGS WITH THE 16 SEER RHEEM AC
 SYSTEMS- THE CALCULATIONS FOR THE REAR RENTAL UNITS
 412B AND 414B HAVE BEEN SUBMITTED AND ARE APPROVED FOR
 THE AC INSTALLATIONS.
 3) SHOW THE LOCATIONS OF THE THE REAR BUILDING
 CONDENSER UNITS AND PROVIDE INSTALLATION DETAILS.
 PLEASE NOTE THAT ALL EXTERIOR CONDENSERS SHALL BE
 INSTALLED AT OR ABOVE THE FLOOD ELEVATION HEIGHT AS
 REQUIRED BY SECTION 1612.4 FBC-10 BUILDING.
 4) PROVIDE THE DIMENSIONS OF THE TRANSFER GRILLS IN
 UNITS 412A AND 412B.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 11:57 Rev Time 0.00
Received By ccole Date 2015-10-07 Time 11:57 Sent To  
Notes
2015-10-07 12:38:473RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15051140
 10/7/15
  
 1) THE SUBMITTED ENERGY AND AC COOLING AND HEATING
 CALCULATIONS INDICATE 18-SEER 1.5- TON TRANE SYSTEMS
 FOR UNITS 412 AND 414, HOWEVER THE PLANS INDICATE
 13-SEER 2-TON RHEEM SYSTEMS. IN ADDITION TWO AC
 CHANGEOUT FORMS FOR UNIT 414 HAVE BEEN SUBMITTED
 SPECIFYING A NEW 13-SEER 2-TON RUUD SYSTEM TO BE
 INSTALLED. I AM CONFUSED: PLEASE CORRECT THE PLANS TO
 MATCH THE SUBMITTED DOCUMENTS, OR VICE-VERSA. PLEASE
 NOTE THAT NO DOCUMENTS HAVE BEEN SUBMITTED FOR THE NEW
 MINI-SPLIT SYSTEMS SHOWN IN THE REAR BUILDING 1ST AND
 2ND FLOOR, IF THESE ARE NEW SYSTEMS (NOT REPLACED)
 ENERGY AND AC LOAD CALCULATIONS ARE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-08 Cont ID  
Sent By ccole Date 2015-09-08 Time 09:59 Rev Time 0.00
Received By ccole Date 2015-09-08 Time 09:59 Sent To  
Notes
2015-09-08 10:04:542ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15051140
 9/8/15
  
 1) AC CHANGE OUT COMPLIANCE FORMS: PLEASE SUBMIT TWO
 FORMS FOR UNIT 412, AND TWO FORMS FOR UNIT 414 AS SHOWN
 ON THE AC PLANS, AND MATCH THE MAKE OF THE REPLACED AC
 SYSTEMS WITH THE MAKE LISTED ON THE PLANS.
 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE
 SUBMIT AHRI CERTIFICATES FOR THE REPLACEMENT AC
 SYSTEMS.
 3) REFER TO SECTION 403.2.4 FBC-10 ENERGY CONSERVATION
 AND PLACE NOTES ON THE PLAN ACCORDINGLY TO VERIFY
 COMPLIANCE: 403.2.4 AIR-HANDLING UNITS.
 AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE
 AIR-CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM
 IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A
 DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN
 IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT
 THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT
 WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO
 AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU
 ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE
 EACH SEASON OF PEAK OPERATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By ccole Date 2015-07-09 Time 11:22 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 11:22 Sent To  
Notes
2015-07-09 11:49:511ST REVIEW: FBC 2010 MECHANICAL
 7/9/15
  
 1) CLARIFY THE SCOPE OF WORK FOR HVAC. IT APPEARS THAT
 AC SYSTEMS REPLACEMENTS ARE PROPOSED IN EACH OF THE
 FOUR UNITS, INCLUDING NEW DUCTWORK IN UNITS 412 AND
 414. PLEASE CONFIRM WITH NOTES ON THE PLAN. PLEASE NOTE
 THAT COOLING AND HEATING CALUCLATIONS, AND ENERGY
 CALCULATIONS ARE REQUIRED FOR ANY PREVIOUSLY
 UNCONDTIONED BUILDINGS THAT ARE NOW BEING CONDITIONED-
 TABLE 101.4.1 AND SECTION 403.6.1 FBC-10 ENERGY
 CONSERVATION.
 2) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS LISTING
 MAKES AND MODELS, COOLING AND HEATING CAPACITES,
 EFFICIENCY RATINGS, AND ELECTRICAL REQUIEMENTS.
 3) SUBMIT AHRI CERTIFICATES FOR EACH NEW AC SYSTEM-
 SECTION 101.4.7 FBC-10 ENERGY CONSERVATION
 4) PROVIDE CONDENSATE DISPOSAL DETAILS FOR EACH SYSTEM-
 TYPE AND SIZE OF PIPING, PIPING RUNS, AND DISCHARGE
 LOCATIONS. INDICATE HOW SECONDARY OR AUXILIARY DISPOSAL
 IS BEING ACCOMPLISHED- SECTION 307.2.3 FBC-10 MECH.
 5) THE PLAN SHOWS AIR HANDLERS IN THE ATTICS OF UNITS
 412 & 414, HOWEVER NO ACCESS IS SHOWN ON THE PLANS- SEE
 SECTIONS 306.3 AND 306.3.2 AND PROVIDE DETAILS
 INDICATING COMPLIANCE WITH ALL REQUIREMENTS.
 6) SHEET 3.1: THE CU MOUNTING DETAIL HAS INCOMPLETE
 DETAILS: PROVIDE THE DEPTH OF ANCHOR EMBEDMENT INTO THE
 SLAB, INDICATE WHICH TIE-DOWN CLIP TO BE INSTALLED, AND
 THE WIND LOAD DESIGN CRITERIA- SECTION 301.12.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-01-07 Cont ID  
Sent By skennedy Date 2016-01-07 Time 14:24 Rev Time 0.00
Received By skennedy Date 2016-01-07 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-12-06 Cont ID  
Sent By gjohnson Date 2015-12-06 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2015-12-06 Time 12:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By tklarge Date 2015-09-18 Time 09:25 Rev Time 0.00
Received By tklarge Date 2015-09-09 Time 05:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-04 Cont ID  
Sent By tklarge Date 2015-06-01 Time 10:34 Rev Time 0.00
Received By tklarge Date 2015-06-01 Time 10:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By fmittner Date 2016-01-08 Time 15:08 Rev Time 0.00
Received By fmittner Date 2016-01-08 Time 15:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By fmittner Date 2016-01-05 Time 16:48 Rev Time 0.00
Received By fmittner Date 2016-01-05 Time 16:48 Sent To  
Notes
2016-01-05 16:49:12AWAITING DETACHED STRUCTURE PLANS