Plan Review Details - Permit 15051134
Plan Review Stops For Permit 15051134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-07-17 Time 06:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-11 Cont ID  
Sent By jwitmer Date 2015-06-11 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2015-06-11 Time 07:01 Sent To  
Notes
2015-06-11 07:36:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051134
 ADD: 2461 METROCENTRE BLVD.E.
 CONT: EMERALS CONSTRUCTION
 TEL: (954) 241-2583
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 11/ 2015
 ACTION: DENIED
  
 1) COVERSHEET / SHEET A-1:
 1A) THE COVERSHEET / A-1 SHOWS THE CORRECT ADDRESS IN
 THE TITLE BLOCK, BUT THE CENTER OF THE PLAN THE ADDRESS
 SHOWN IS 1800 NW 49TH ST. SUITE 120, FT. LAUDERDALE,
 FL. PLEASE CORRECT ADDRESS. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE JOBSITE...
  
 1B) THE HEADING CODE RESEARCH/ EFFECTIVE CODES
 INDICATES BROWARD COUNTY AMENDMENTS.
  
 1C) THE OCCUPANT LOAD IS BASED ON 10,193 SQ FT WITH A
 OCCUPANT LOAD OF 101 OCCUPANTS. 10,193/ 100= 102
 OCCUPANTS FBC-B TABLE 1004.1.1 AND DPBR & FLORIDA
 BUILDING CODE INFORMAL INTERPRETATION REPORT 5479. YOU
 ROLL UP TO THE NEXT FULL NUMBER.
  
 2) A-1.1 VERSES A-2. THE DEMO SHEET A-1.1 SHOWS (2)
 ACCESSIBLE STALLS WITH THE LAVATORY IN THE STALL. SHEET
 A-2 THE REMODEL OF THE 2 RESTROOMS SHOW THE REMOVAL OF
 THE LAVATORY FROM THE STALL. PLEASE REVIEW THE 2010
 FBC-ACCESSIBILITY CODE SECTION 202.3.1 PROHIBITED
 REDUCTION IN ACCESS. AN ALTERATION THAT DECREASES OR
 HAS THE EFFECT OF DECREASING THE ACCESSIBILITY OF A
 BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF THE ALTERATION IS
 PROHIBITED.
  
 3) SHEET A-2;
 3A) THE NEW RESTROOM LOCATED IN THE RECEPTION AREA IS
 NOT LARGE ENOUGH IN WIDTH. THE BACKWALL WITH THE
 PLUMBING FIXTURES SHOW A DIMENSION OF 6FT 10 INCHES.
 WITH THE REQUIREMENTS OF THE 2010 FBC-ACCESS. CODE
 604.3.2 THE MINIMUM DIMENSION WOULD BE APPROX. 7 FT 1
 INCH.
  
 3B) DETAIL A OF THIS SHEET SHOW AN ACCESSIBLE CUSTOMER
 SERVICE STATION, IT IS UNKNOWN IF THERE WILL BE CHECK
 WRITING THAT WILL REQUIRE COMPLIANCE WITH
 SECTION 904.3.3 OF THE ACCESSIBILITY CODE, CHEK WRITING
 SURFACES?
  
 3C) DETAIL C SHOWS A MICROWAVE THE BOTTOM OF THE
 MICROWAVE AT A HEIGHT OF 52 INCHES ABOVE FINISH FLOOR.
 PLEAS SHOW COMPLIANCE WITH:
 2010 FBC- ACCESS. CODE 308 REACH RANGES
 2010 FBC-ACCESS. CODE 309 OPERABLE PARTS
  
 3D) THIS SHEET SHOWS INFILL WALL SECTION AT DOORWAYS.
 THIS WALL IS DESIGNED AS A 1 HOUR FIRE RATED TENANT
 SEPARATION WALL. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 713.6 SUGGESTED WORDING. "FIRE & SMOKE BARRIRER-
 PROTECT ALL OPENINGS.
  
 4) SHEET A2-1 IS SHOWN AS THE LIFE SAFETY PLAN, THE
 PLANS DO NOT SHOW THE LONGEST EXIT ACCESS TRAVEL
 DISTANCES (FBC-B T 1016.1) NUMBER OF OCCUPANTS THROUGH
 EACH EXITAND ALLOWABLE, THE PLANS DO NOT SHOW EXIT
 DIRECTIONAL LIGHTING, AND EXIT SIGNS NOR EMERGENCY
 LIGHTING (BATTERY) .
 FBC-B 1006.3.2/ 1006 3.8 & 1006.1.2.
  
 5) SHEET A2-1 DOES NOT SHOW ANY INFORMATION FOR
 COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE 1006.3.4.
 TACTILE SIGNAGE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 14:19 Rev Time 0.00
Received By albarran Date 2015-07-23 Time 13:59 Sent To I
Notes
2015-07-23 14:25:36ALL PREVIOUS COMMENTS HAVE BEEN SATISFACTORILY
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By albarran Date 2015-06-24 Time 19:08 Rev Time 0.00
Received By albarran Date 2015-06-24 Time 14:58 Sent To I
Notes
2015-06-24 19:08:54JOB PERMIT NUMBER: 15051134
 JOB ADDRESS: 2468 METROCENTRE BLVD.
  WEST PALM BEACH, FL
 DATE: JUNE24TH, 2015
  ELECTRICAL PLAN REVIEW COMMENTS
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
 THE INTENT OF THIS REVIEW WAS NOT TO GENERATE A PUNCH
 LIST FOR THE DESIGN PROFESSIONAL, THEREFORE IN ADDITION
 TO THE COMMENTS ENTERED BELOW, THE PLANS AND LIGHTING
 SHOULD BE CAREFULLY REVIEWED FOR COMPLIANCE WITH THE
 2010 EDITION OF THE FBC-B; FBC-E AND THE 2008 EDITION
 OF THE NEC PRIOR TO RESUBMITTING. FOR EASE OF REVIEW,
 PLEASE INDICATE THE ENTRY POINTS INTO THE VARIOUS ROOMS
 ON THE LIGHTING PLAN.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 SHEET E-1:
 1. FBC-B ?1006.2 & NEC 210.70 (F) HAVE SPECIFIC
 REQUIREMENTS FOR EMERGENCY ILLUMINATION IN BLDGS. OVER
 75? HIGH. EMERGENCY LIGHTING IS REQUIRED BUT NOT
 LIMITED TO ROOMS 7, 9, & 25.
 2. FBC-E ? 505 HAS AUTOMATIC LIGHTING CONTROL
 REQUIREMENTS WHICH WAS NOT OBSERVED FOR ROOMS 4, 5, 6,
 9, 11, 23, & 24.
 3. FBC-B ? 1011 HAS SPECIFIC REQUIREMENTS FOR EXIT
 LIGHTING WERE FOUND TO BE MISSING, BUT NOT LIMITED TO
 ROOMS 3, & 5
 SHEET E-2
 1. PER NEC 408.4, PROVIDE A PANEL DIRECTORY FOR PANEL A
 2. PER NEC 422.52, ELECTRIC DRINKING FOUNTAINS SHALL BE
 PROTECTED WITH A GFI CIRCUIT. THERE APPEAR TO BE TWO
 DRINKING FOUNTAINS, ONE IN THE BREAK ROOM, AND ONE IN
 THE RECEPTION AREA.
 3. PER NEC 210.8(B) EVERY OUTLET WITHIN 6? FROM THE
 SINK SHALL BE PROTECTED WITH GFI.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-16 Cont ID  
Sent By pleduc Date 2015-07-16 Time   Rev Time 0.00
Received By pleduc Date 2015-07-16 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 14:27 Sent To  
Notes
2015-06-03 14:28:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND/OR SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 14:26 Rev Time 0.00
Received By albarran Date 2015-07-13 Time 14:40 Sent To  
Notes
2015-07-23 14:29:197/23/15 - PASSED ALL REVIEWS AND READY FOR ISSUANCE.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE READY BIN
 "E". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By albarran Date 2015-06-24 Time 19:09 Rev Time 0.00
Received By albarran Date 2015-05-27 Time 17:31 Sent To  
Notes
2015-06-24 19:18:45FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "E". MA
2015-05-27 17:40:03SENT TO B9 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-11 Cont ID  
Sent By jwitmer Date 2015-06-11 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2015-06-11 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-23 Cont ID  
Sent By ccole Date 2015-07-23 Time 07:57 Rev Time 0.00
Received By ccole Date 2015-07-23 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By ccole Date 2015-06-23 Time 15:40 Rev Time 0.00
Received By ccole Date 2015-06-23 Time 15:40 Sent To E
Notes
2015-06-23 15:55:081ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: THE O/A DUCT FOR AHU-1B AND AHU-3 IS
 SHOWN TO BE CAPPED OFF ON THE PLAN: PLEASE CORRECT.
 2) M-1: RETURN AIR FROM THE TRAINING ROOM SHALL NOT BE
 TRANSFERRED INTO THE CORRIDOR- SECTION 601.2 FBC-10
 MECHANICAL.
 3) SHOW THE DISCHARGE OR DRAINAGE LOCATION OF THE
 AHU-1D CONDENSATE PIPING- SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-23 Cont ID  
Sent By tklarge Date 2015-07-23 Time 09:07 Rev Time 0.00
Received By tklarge Date 2015-07-23 Time 08:45 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By tklarge Date 2015-06-16 Time 05:18 Rev Time 0.00
Received By tklarge Date 2015-06-16 Time 03:39 Sent To  
Notes
2015-06-16 05:17:421) SHEET A-1 - THE ADDRESS IN THE CENTER OF THE PLANS
 REFER TO A LOCATION IN FT. LAUDERDALE. PLACE THE
 CORRECT ADDRESS OF THE JOBSITE ON THE PLANS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) SHT. A-1 - DELETE THE REFERENCE TO BROWARD COUNTY
 AMENDMENTS IN THE "CODE RESEARCH" HEADING.
 3) THE DRINKING FOUNTAINS IN THE RECEPTION AREA SHOW A
 PARALLEL CLEAR FLOOR SPACE. PER THE FACBC SEC.602.2,
 "UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT." SHOW THE REQUIRED FORWARD
 APPROACH CENTERED ON THE UNIT.
 4) SHT. A-2 - THE WIDTH OF RESTROOM #02 IN THE
 RECEPTION AREA IS NOT WIDE ENOUGH. THE MINIMUM WIDTH
 WHERE THE PLUMBING FIXTURES ARE ON THE SAME WALL SHALL
 BE 85 INCHES IF BUILT PERFECT; 86 INCHES ALLOWS FOR
 CONSTRUCTION TOLERANCES.
 5) THE DEMOLITION PLANS (A1.1 ) SHOW AN EXISTING
 LAVATORY IN THE TOILET COMPARTMENTS OF BOTH RESTROOMS.
 THE BUILDOUT PLANS SHOW THIS LAVATORY BEING REMOVED.
 THIS IS REDUCING THE LEVEL OF ACCESSIBILITY AND
 VIOLATES SEC.202.3.1. OF THE 2010 FL. ACCESSIBILITY
 CODE. REVISE THE PLANS TO SHOW THE LAVATORIES AND
 COMPLY WITH 2010 FL. ACCESSIBILITY CODE SEC.604.8.1.6.
 6) THE GRAB BAR HEIGHT SHALL BE MEASURED FROM FINISH
 FLOOR TO THE TOP OF THE GRIPPING SURFACE, NOT THE
 CENTERLINE AS SHOWN PER THE FAC SEC. 609.4.
 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 DRINKING FOUNTAINS SHOWN IN THE RECEPTION AREA (01).
 WPB AMEND. TO FBC SEC. 107.1.
 8) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR
 THE TANKLESS WATER HEATER. A COPY OF THE INSTALLATION
 MANUAL SHALL BE ONSITE FOR THE INSPECTOR.WPB AMEND. TO
 FBC SEC. 107.1.
 9) THE WATER LINE FOR THE COFFEE DISPENSER SHALL BE
 PROTECTED AGAINST BACKFLOW PER 2010 FPC SEC. 608.16.10.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-05 Cont ID  
Sent By ajones Date 2015-06-05 Time 14:55 Rev Time 0.00
Received By ajones Date 2015-06-05 Time 14:55 Sent To  
Notes
***NONE***