Plan Review Details - Permit 15051090
Plan Review Stops For Permit 15051090
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-15 Cont ID  
Sent By rmcdouga Date 2015-09-15 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2015-09-15 Time 13:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 07:13 Sent To  
Notes
2015-08-13 07:23:24PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING (PREVIOUS COMMENTS HAVE NOT BEEN
 ADDRESSED)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLOOR OF THE SUNKEN BAR IS MORE THAN 30" BELOW
 GRADE. PROVIDE GUARDS AROUND THE SUNKEN BAR AS REQUIRED
 BY FBC - R312.
  
 2) PROVIDE A SURVEY/SITE PLAN INDICATING THE LOCATION
 OF THE POOL AND SUNKEN BAR AREA IN RELATION TO THE
 STRUCTURES LOCATED ON THE PROPERTY AND PROPERTY LINES.
 FBC 107.2.1
  
 3) NEW COMMENT. THE INFORMATION AND DRAWINGS THAT WAS
 SUBMITTED CONTAIN CONFLICTING INFORMATION. SUBMIT TWO
 SETS OF SIGNED AND SEALED DRAWINGS WITH COMPLETE
 DIMENSIONS AND ELEVATIONS THAT SHOW THE LOCATION AND
 DIMENSIONS OF ALL STAIRS, GUARDS (GUARD RAILS),
 EQUIPMENT, ELECTRICAL AND PLUMBING. FBC 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-26 Cont ID  
Sent By rmcdouga Date 2015-06-26 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2015-06-26 Time 08:24 Sent To  
Notes
2015-06-26 08:40:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLOOR OF THE SUNKEN BAR IS MORE THAN 30" BELOW
 GRADE. PROVIDE GUARDS AROUND THE SUNKEN BAR AS REQUIRED
 BY FBC - R312.
  
 2) PROVIDE A SURVEY/SITE PLAN INDICATING THE LOCATION
 OF THE POOL AND SUNKEN BAR AREA IN RELATION TO THE
 STRUCTURES LOCATED ON THE PROPERTY AND PROPERTY LINES.
 FBC 107.2.1
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-15 Cont ID  
Sent By rmcdouga Date 2015-09-15 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2015-09-15 Time 13:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 07:24 Sent To Z
Notes
2015-08-13 10:25:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 406.8 (B) WET LOCATIONS. OUTDOOR RECEPTACLES ARE
 REQUIRED TO BE WEATHER PROOF.
  
 2) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 3) NEC 680.22 RECEPTACLES ARE REQUIRED TO BE LOCATED
 NOT LESS THAN 6 FT. FROM THE INSIDE POOL WALL.
  
 4) NEC 680.26 BOND ALL METAL PARTS WITHIN 5 FT. OF THE
 INSIDE POOL WALL.
  
 5) FBC-R 303.6 AND 303.6.1 STAIRWAY ILLUMINATION AND
 LIGHT ACTIVATION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-06-26 Cont ID  
Sent By rmcdouga Date 2015-06-26 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2015-06-26 Time 08:16 Sent To  
Notes
2015-06-26 08:21:02NO ELECTRICAL WORK IS INDICATED ON THE PLANS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-08-12 Cont ID  
Sent By tklarge Date 2015-08-12 Time 13:25 Rev Time 0.00
Received By tklarge Date 2015-08-11 Time 09:37 Sent To  
Notes
2015-08-12 13:26:05SEE PERMIT APPLICATION # 15051092.TKL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 06:05 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 05:51 Sent To  
Notes
2015-06-12 05:52:481) AN APPLICATION FOR GAS INSTALLATION HAS BEEN
 SUBMITTED BUT THERE IS NO GAS WORK SHOWN ON THE PLANS.
 CLARIFY.
 2) SUBMIT A GAS RISER DRAWING FOR REVIEW. WPB AMEND. TO
 FBC SEC. 107.3.5.3.
 3) SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS
 EQUIPMEENT.ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER 2010 FBC SEC.G2404.3.
 4) SHOW THE LOCATION OF ALL GAS EQUIPMENT/APPLIANCES ON
 THE PLAN. WPB AMEND. TO FBC SEC. 107.3.5.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By fmittner Date 2015-10-19 Time 10:00 Rev Time 0.00
Received By fmittner Date 2015-10-19 Time 10:00 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By fmittner Date 2015-09-04 Time 09:38 Rev Time 0.00
Received By fmittner Date 2015-09-04 Time 09:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 10:21 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-15 Cont ID  
Sent By rmcdouga Date 2015-09-15 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2015-09-01 Time 11:05 Sent To  
Notes
2015-09-14 11:05:33R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-01 Cont ID  
Sent By cpuell Date 2015-09-01 Time 16:11 Rev Time 0.00
Received By cpuell Date 2015-08-07 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-26 Cont ID  
Sent By rmcdouga Date 2015-06-26 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2015-06-10 Time 15:29 Sent To  
Notes
2015-06-10 15:29:29TO POOL BOX
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-09-18 Cont ID  
Sent By tklarge Date 2015-09-18 Time 04:16 Rev Time 0.00
Received By tklarge Date 2015-09-18 Time 03:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-09-14 Cont ID  
Sent By tklarge Date 2015-09-14 Time 14:26 Rev Time 0.00
Received By tklarge Date 2015-09-14 Time 14:17 Sent To  
Notes
2015-09-14 14:26:28SHT. 1 & SHT. 2 OF THE PLANS FROM JASON HANCHUK SHOW A
 1 FT. X 1 FT. SUMP IN THE SUNKEN BAR AREA. THE SUMP
 DETAIL DOES NOT SHOW ANY PIPING TO OR FROM THE SUMP AND
 ON SHT.3 THERE IS A DRAWING OF A 3 INCH FLOOR DRAIN
 DISCHARGING TO A SUMP TANK WITH A PUMP.WHAT KIND OF
 PIPING CONNECTION ARE YOU PUTTING IN THE SUNKEN BAR
 AREA? IS THE SUMP DRAINING INTO THE PUMP BASIN? NOTHING
 MATCHES ON THESE PLANS.CLARIFY.
  
 I AM CONFUSED AS TO WHAT IS BEING INSTALLED . PLEASE
 CALL TO DISCUSS OR SET UP AN APPOINTMENT.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-11 Cont ID  
Sent By tklarge Date 2015-08-11 Time 09:37 Rev Time 0.00
Received By tklarge Date 2015-08-11 Time 06:59 Sent To  
Notes
2015-08-11 08:30:031) SHT. 2 OF 2 OF THE PLANS FROM J.HANCHUK SHOWS A
 3"PVC PIPE WITH A NOTE STATING "SLOPE TO DRYWELL" BUT
 IT IS SHOWN DISCHARGING TO A 150 GALLON TANK, THE
 SUBMITTED SPECS ARE FOR A 41 GALLON TANK. CLARIFY.
 2) SUBMIT TWO COPIES OF THE PUMP SPEC SHEETS, DRYWELL
 SPEC SHEETS, AND THE DRAWINGS FOR THE DRYWELL PIPING.
 WPB AMEND. TO FBC SEC. 107.1.
 3) SHOW THE PIPE SIZES FOR THE VENT AND ALSO FOR THE
 DISCHARGE LINE FROM THE SUMP TO THE DRYWELL AND ALSO
 THE PIPING BETWEEN THE DRYWELLS. WPB AMEND. TO FBC SEC.
 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 05:53 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 05:20 Sent To  
Notes
2015-06-12 05:51:291) SHT. 2 OF 2 SHOWS A 3"PVC PIPE WITH A NOTE STATING
 "SLOPE TO DRYWELL" BUT IT IS SHOWN DISCHARGING TO A 150
 GALLON TANK. WHERE IS THIS WATER BEING DISCHARGED? HOW
 IS THE TANK BEING DRAINED/PUMPED OUT. WHERE IS THE
 TERMINATION POINT? CLARIFY.
 2) SUBMIT 2 COPIES OF MANUFACTURER SPECIFICATION SHEETS
 AND INSTALLATION INSTRUCTIONS FOR THE TANK. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 3) AN OVERFLOW/RELIEF VENT SHOULD BE PROVIDED ON THIS
 SYSTEM. WHEN THE TANK FILLS IT WILL BACK UP IN THE BAR
 AREA CREATING AND UNSANITARY CCONDITION.
 4) SHOW THE LOCATION OF THE TANK ON THE SITE PLAN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By fmittner Date 2015-10-19 Time 10:01 Rev Time 0.00
Received By fmittner Date 2015-10-19 Time 10:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By fmittner Date 2015-09-04 Time 09:39 Rev Time 0.00
Received By fmittner Date 2015-09-04 Time 09:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 10:21 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 10:21 Sent To  
Notes
2015-06-01 10:21:59NEEDS 2 SURVEYS TO SHOW LOCATION.