Plan Review Details - Permit 15051022
Plan Review Stops For Permit 15051022
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-28 Cont ID  
Sent By jwitmer Date 2015-10-28 Time 06:48 Rev Time 0.00
Received By jwitmer Date 2015-10-28 Time 06:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 16:40 Sent To  
Notes
2015-10-01 17:08:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051022
 ADD: 1517 CAMERON SAMUELS LANE
 CONT: A& G CONCRETE POOLS, INC
 TEL: ( 772)878-7752
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!!!!!: CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
  
  
 3RD REVIEW
 DATE: THURS. OCT. 01/2015
 ACTION: DENIED
  
 1) 3RD REVIEW ONLY ONE SET OF AQUATIC ACCESS SALES
 BROCHURE WAS SUBMITTED. COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE CAN NOT BE DETERMINED PLEASE
 SHOW COMPLIANCE WITH:
 2010 FBC-ACCESSIBILITY COCE;
  
 1009.2.2 SEAT LOCATION OK
 .
 1009.2.4 SEAT HEIGHT THE LOW HEIGHT RANGE DOES NOT MEET
 THE REQUIREMENT OF 16 INCHES.
  
 1009.2.5 SEAT WIDTH OK
  
 1009.2.6 FOOT REST AND ARMREST DOES NOT INDICATE CODE
 COMPLIANCE. FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE
 WITH THE SEAT. IF PROVIDED, THE ARMREST POSITIONED
 OPPOSITE THE WATER SHALL BE REMOVABLE OR SHALL FOLD
 CLEAR OF THE SEAT WHEN THE SEAT IS IN THE RAISED (LOAD)
 POSITION.
  
 1009.2.7 OPERATION POOL LIFTS MUST BE CAPABLE OF
 UNASSISTED OPERATION FROM BOTH THE DECK AND WATER
 LEVELS. THIS WILL PERMIT A PERSON TO CALL THE POOL LIFT
 WHEN THE POOL LIFT IS IN THE OPPOSITE POSITION. IT IS
 EXTREMELY IMPORTANT FOR A PERSON WHO IS SWIMMING ALONE
 TO BE ABLE TO CALL THE POOL LIFT WHEN IT IS IN THE UP
 POSITION SO HE OR SHE WILL NOT BE STRANDED IN THE WATER
 FOR EXTENDED PERIODS OF TIME AWAITING ASSISTANCE. THE
 REQUIREMENT FOR A POOL LIFT TO BE INDEPENDENTLY
 OPERABLE DOES NOT PRECLUDE ASSISTANCE FROM BEING
 PROVIDED.
  
 1009.2.8 SUBMERGED DEPTH. OK
  
 1009.2.9 LIFTING CAPACITY. SINGLE PERSON POOL LIFTS
 MUST BE CAPABLE OF SUPPORTING A MINIMUM WEIGHT OF 300
 POUNDS (136 KG) AND SUSTAINING A STATIC LOAD OF AT
 LEAST ONE AND A HALF TIMES THE RATED LOAD. POOL LIFTS
 SHOULD BE PROVIDED THAT MEET THE NEEDS OF THE
 POPULATION THEY SERVE. PROVIDING A POOL LIFT WITH A
 WEIGHT CAPACITY GREATER THAN 300 POUNDS (136 KG) MAY BE
 ADVISABLE.
  
 2) COMPLIED SOLAR BLANKET.
  
 3) PUT YOUR PLANS AND SUBMITTALS TOGETHER IN 2
 PACKAGES!!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2015-09-21 Time 10:44 Sent To  
Notes
2015-09-21 10:54:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051022
 ADD: 1517 CAMERON SAMUELS LANE
 CONT: A& G CONCRETE POOLS, INC
 TEL: ( 772)878-7752
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!!!!!: CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
  
  
 2ND REVIEW
 DATE: MON. SEPT. 21/2015
 ACTION: DENIED
  
 1) 2ND REVIEW ONLY ONE SET OF AQUATIC ACCESS SALES
 BROCHURE WAS SUBMITTED. COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE CAN NOT BE DETERMINED PLEASE
 SHOW COMPLIANCE WITH:
 2010 FBC-ACCESSIBILITY COCE;
 1009.2.2 SEAT LOCATION
 1009.2.4 SEAT HEIGHT
 1009.2.5 SEAT WIDTH
 1009.2.6 FOOT REST AND ARMREST
 1009.2.7 OPERATION
 1009.2.8 SUBMERGED DEPTH
 1009.2.9 LIFTING CAPACITY
  
 2) 2ND REQUEST. SHEET 1 INDICATES THE USE OF (3) POOL
 HEATERS. PLEASE PROVIDE CODE COMPLIANCE WITH 2010
 FBC-ENERGY CODE 504.7.3 HEATED SWIMMING POOLS AND
 INGROUND PERMANENTLY INSTALLED SPAS SHALL BE EQUIPED
 WITH A VAPOR RETARDANT COVER ON THE WATER OR AT THE
 WATER SURFACE OR A LIQUID COVER OR OTHER MEANS PROVEN
 TO REDUCE HEAT LOSS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By jwitmer Date 2015-06-06 Time 14:15 Rev Time  
Received By jwitmer Date 2015-06-06 Time 13:30 Sent To E
Notes
2015-06-06 14:18:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051022
 ADD: 1517 CAMERON SAMUELS LANE
 CONT: A& G CONCRETE POOLS, INC
 TEL: ( 772)878-7752
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 06/2015
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE USE OF A BATTERY OPERATED
 HANDICAPPED CHAIRLIFT. PLEASE PROVIDE THE MANUFACTURERS
 SPECS ON THIS PRODUCT AND FOR THE INSTALATION OF THE
 LIFT. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET 1 INDICATES THE USE OF (3) POOL HEATERS.
 PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-ENERGY
 CODE 504.7.3 HEATED SWIMMING POOLS AND INGROUND
 PERMANENTLY INSTALLED SPAS SHALL BE EQUIPED WITH A
 VAPOR RETARDANT COVER ON THE WATER OR AT THE WATER
 SURFACE OR A LIQUID COVER OR OTHER MEANS PROVEN TO
 REDUCE HEAT LOSS.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-03 Time 10:28 Rev Time 0.00
Received By albarran Date 2015-11-03 Time 09:49 Sent To I
Notes
2015-11-03 10:29:56ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-10-23 Cont ID  
Sent By albarran Date 2015-10-23 Time 10:58 Rev Time 0.00
Received By albarran Date 2015-10-23 Time 10:30 Sent To B
Notes
2015-10-23 11:11:54THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 THE PREVIOUS REVIEW MENTIONED REQUIREMENTS STATED ON
 THE PLANS INITIALLY SUBMITTED FOR PERMITTING. THESE
 PLANS THOUGH INCLUDE A GENERIC RISER DIAGRAM AND
 CONDUCTOR SIZING SCHEDULE, CLEARLY STATE THAT A
 LICENSED ELECTRICAL CONTRACTOR IS TO PROVIDE ACCURATE
 LOAD CALCS, FEEDER SCHEDULES, PANEL SCHEDULES AND ALL
 DATA ASSOCIATED WITH THIS INSTALLATION. FURTHERMORE, AS
 I INDICATED IN THE PREVIOUS REVIEW COMMENTS, WHAT IS
 BEING DONE ABOUT THE SITE LIGHTING FOR THIS AREA? IS
 THE LIGHTING ALREADY IN PLACE? IF SO, INDICATE THAT
 OTHERWISE SITE LIGHTING DRAWINGS SHALL BE PROVIDED.
 THESE SHALL COMPLY WITH THE FBC-ENERGY CONSERVATION
 CODE. THE SCOPE OF THE PERMIT SHALL BE CLEARLY DEFINED
 TO INCLUDE ALL OF THE PROPOSED WORK.
 YOU NEED TO SUBMIT SITE PLANS SHOWING THE LOCATION OF
 THE MAIN DISCONNECT, AND THE LOCATION OF ANY AND ALL
 EQUIPMENT ASSOCIATED WITH THIS PERMIT. YOU WILL HAVE TO
 PROVIDE A DIAGRAM OF THE PROPOSED EQUIPMENT RACK IF
 ANY. SUBMIT LOAD CALCS AND A PANEL SCHEDULE. WHO WILL
 BE RESPONSIBLE FOR THE EQUI-POTENTIAL BONDING?
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 10:12 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 09:07 Sent To B
Notes
2015-09-17 11:15:29PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER NOTE ON PAGE 5, THE FEED TO THE AQUAWORX PANEL
 IS BEING PERFORMED BY THE EC (ELECTRICAL CONTRACTOR)
 UNDER A SEPARATE PERMIT. THAT WOULD EXCLUDE THE
 EQUIPOTENTIAL BONDING, POOL AND SITE LIGHTING IN
 ADDITION TO INCIDENTAL ELECTRICAL WORK REQUIRED.
 ACCORDING TO THE ELECTRICAL DRAWINGS, THE SCOPE
 TERMINATES AT THE POOL EQUIPMENT DISCONNECT.
 2. PROVIDE DETAIL OF AQUAWORX EQUIPMENT WITH LOAD CALCS
 TO EQUIPMENT DISCONNECT.
 3. YOU SHALL INDICATE THE EC FOR THE REMAINDER OF THE
 WORK AS DESCRIBED ABOVE.
 4. AREA LIGHTING SHALL COMPLY WITH THE FBC-E SECTION
 505.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By albarran Date 2015-06-08 Time 17:04 Rev Time 0.00
Received By albarran Date 2015-06-08 Time 16:54 Sent To G
Notes
2015-06-08 17:03:25ACCORDING TO THE SUBMITTED PLANS, THE NOTE ON PAGE 5 OF
 5 STATES THAT ELECTRICAL DATA WILL BE SUBMITTED UNDER
 SEPARATE COVER. PROVIDE ELECTRICAL SPECS AND DRAWINGS
 OF THE PROPOSED ELECTRICAL WORK FOR THIS POOL ALONG
 WITH AN EQUIPMENT SPEC SHEET.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-06-20 Time 06:49 Sent To  
Notes
2015-06-20 06:55:001) GAS TO BE UNDER SEPARATE PERMIT.SEE 15051024 FOR GAS
 REVIEW COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-03 Time 10:31 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 13:57 Sent To  
Notes
2015-11-03 10:33:3211/3/15 ALL ALL TRADE REVIEWS SUCCESSFULLY AND IS READY
 TO BE ISSUED. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 LARGE READY BIN "A". MA
2015-11-02 13:57:58RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-28 Cont ID  
Sent By jwitmer Date 2015-10-28 Time 06:48 Rev Time 0.00
Received By jwitmer Date 2015-10-13 Time 14:52 Sent To  
Notes
2015-10-14 14:53:26ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 09:36 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2015-08-05 Time 13:20 Sent To  
Notes
2015-08-05 13:20:21RESUB ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 06:56 Rev Time 0.00
Received By tklarge Date 2015-06-20 Time 06:56 Sent To  
Notes
2015-05-22 11:53:52ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-10-22 Cont ID  
Sent By tklarge Date 2015-10-22 Time 08:23 Rev Time 0.00
Received By tklarge Date 2015-10-22 Time 08:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 17:12 Rev Time 0.00
Received By tklarge Date 2015-10-01 Time 08:54 Sent To  
Notes
2015-10-01 09:29:39NONE OF THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS HAVE
 BEEN ADDRESSED FROM THE REVIEW DONE ON 8/10/15.
 1) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND
 ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER
 2010 FBC SEC.424.1.6.5.9.4. 2ND REQUEST.
 2) INDICATE ON THE PLAN HOW WATER WILL BE SUPPLIED TO
 THE AQUATIC ACCESS LIFT.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. 1 OF 5 SHOWS THE POOL WATER DRAINING TO THE
 SANITARY SYSTEM.POOL WATER CANNOT DRAIN TO THE SANITARY
 SYSTEM OR TO THE STORM WATER SYSTEM PER CITY ORDINANCE
 SEC.90-126 (5). PLEASE CONTACT MANNY GONZALEZ IN THE
 CWPB ENGINEERING DEPT. 561-494-1040 FOR FURTHER
 DIRECTION.
 4) THE POOL HEATERS SHALL COMPLY WITH THE 2010
 FBC-ENERGY TABLE 504.2 & SHALL HAVE A THERMAL
 EFFICIENCY OF 82% AND COMPLY WITH ASHRAE 146. SUBMIT
 CONFIRMATION OF COMPLIANCE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-10 Cont ID  
Sent By tklarge Date 2015-08-10 Time 11:03 Rev Time 0.00
Received By tklarge Date 2015-08-10 Time 05:28 Sent To  
Notes
2015-08-10 08:49:361) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND
 ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER
 2010 FBC SEC.424.1.6.5.9.4. 2ND REQUEST.
 2) INDICATE ON THE PLAN HOW WATER WILL BE SUPPLIED TO
 THE AQUATIC ACCESS LIFT.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. 1 OF 5 SHOWS THE POOL WATER DRAINING TO THE
 SANITARY SYSTEM.POOL WATER CANNOT DRAIN TO THE SANITARY
 SYSTEM OR TO THE STORM WATER SYSTEM PER CITY ORDINANCE
 SEC.90-126 (5). PLEASE CONTACT MANNY GONZALEZ IN THE
 CWPB ENGINEERING DEPT. 561-494-1040 FOR FURTHER
 DIRECTION.
 4) THE POOL HEATERS SHALL COMPLY WITH THE 2010
 FBC-ENERGY TABLE 504.2 & SHALL HAVE A THERMAL
 EFFICIENCY OF 82% AND COMPLY WITH ASHRAE 146. SUBMIT
 CONFIRMATION OF COMPLIANCE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By tklarge Date 2015-06-01 Time 14:24 Rev Time 0.00
Received By tklarge Date 2015-06-01 Time 06:10 Sent To  
Notes
2015-06-01 14:24:361) SUBMIT MANUF. SPECS. FOR THE WHEELCHAIR LIFT. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. 1 OF 5 SHOWS THE 3" WASTE LINE DISCHARGING TO
 THE STORM DRAINAGE SYSTEM.ONLY STORMWATER SHALL DRAIN
 TO THE STORM DRAINAGE SYSTEM PER CITY ORDINANCE SEC. 90
 - 203.
 3) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND
 ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER
 2010 FBC SEC.424.1.6.5.9.4.
 4) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED AT
 THE CITY METER.CONTACT STEPHEN HUNTER IN THE CWPB
 UTILITIES AT 561-822-2242 FOR TYPE OF BFP DEVICE
 REQUIRED. MINIMUM PROTECTION SHALL BE A REDUCED
 PRESSURE ZONE (RPZ) TYPE DEVICE.
 5) SUBMIT MANUF. SPECS. FOR THE POOL HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SUBMIT PIPING DETAILS FOR THE POOL HEATERS. DETAILS
 SHALL INCLUDE VALVES, THERMOMETER, PIPE SIZES, AND
 MATERIAL SPECIFICATIONS PER THE 2010 FBC SEC.
 424.1.6.5..14.
 7) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION RATE
 OF 2 GPM PER SQUARE FOOT OF FILTER AREA IS NOT
 EXCEEDED. FBC 424.1.6.5.5.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-20 Cont ID  
Sent By sgraham Date 2015-10-20 Time 09:24 Rev Time 0.00
Received By sgraham Date 2015-10-20 Time 09:17 Sent To B
Notes
2015-10-20 09:26:053RD CHECKLIST 10/20/15 ZONING FAILED
  
 1.SUBMIT A COMPLETE SIGNED AND SEALED SITE PLAN OF THE
 PROPERTY.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-07 Cont ID  
Sent By sgraham Date 2015-08-07 Time 12:14 Rev Time 0.00
Received By sgraham Date 2015-08-07 Time 12:14 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By sgraham Date 2015-05-27 Time 14:02 Rev Time 0.00
Received By sgraham Date 2015-05-27 Time 14:02 Sent To B
Notes
2015-05-27 14:07:345/27/15 ZONING FAILED
  
 1. SUBMIT SIGN AND SEALED SITE PLAN, LANDSCAPE
 CONCEPTUAL PLAN WILL NOT BE ACCEPTED.