Plan Review Details - Permit 15051008
Plan Review Stops For Permit 15051008
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time   Sent To E
Notes
2015-07-27 16:44:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051008
 ADD: 1801 S FLAGLER DR SUITE # 1709
 CONT: ARTISAN DESIGN & CONSTRUCT
 TEL: (954)364-8544
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JUNE 27/2015
 ACTION: DENIED
  
 1) 2ND REQUEST. THE CONTRACTOR IS TO SUBMIT THE ACTUAL
 TEST REPORTS FOR THE FLOOR INSULATION THAT IS TO BE
 INSTALLED THE SUBMITTED SHEET FROM US FLOORS IS JUST A
 TECHNICAL SHEET. THE OTHER ISSUE IS THERE IS NO FLAME
 SPREAD TESTING FOR THIS PRODUCT. SHEET A1.01 SHOWS NEW
 WOOD AND TILE FLOORS BEING INSTALLED IN VARIOUS ROOMS
 OF THE SUITE. PLEASE PROVIDE TESTING REPORTS FOR THE
 FLOOR INSULATION THAT COMPLIES WITH THE (3) FOLLOWINGS
 CODE SECTIONS:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2-3) COMPLIED.
  
 4-6) EXTERIOR WINDOWS AND DOORS REMOVED FROM PROJECT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-11 Cont ID  
Sent By jwitmer Date 2015-06-11 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2015-06-11 Time 05:56 Sent To  
Notes
2015-06-11 06:32:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051008
 ADD: 1801 S FLAGLER DR SUITE # 1709
 CONT: ARTISAN DESIGN & CONSTRUCT
 TEL: (954)364-8544
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 11/2015
 ACTION: DENIED
  
 1) SHEET A1.01 SHOWS NEW WOOD AND TILE FLOORS BEING
 INSTALLED IN VARIOUS ROOMS OF THE SUITE. LEASE PROVIDE
 TESTING REPORTS FOR THE FLOOR INSULATION THAT COMPLIES
 WITH THE (3) FOLLOWINGS CODE SECTIONS:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) BATHROOM LABELED ROOM 003 SHOWS A NEW SHOWER
 ENCLOSURE, PLEASE PROVIDE THE TYPE OF BACKING BOARD
 THAT WILL BE INSTALLED IN THE SHOWER ENCLOSURE AND
 CEILING ABOVE, SHOW COMPLIANCE WITH 2010 FBC-B 2509.2
 BASE FOR TILE & 2509.3 LIMITATIONS.
  
 3) SHEET A1.01 NOTE # 8 INDICATES NEW SOFFITS, PLEASE
 PROVIDE A DETAIL SHOWING THE FRAMING TYPE & SIZE,
 SPACING, ATTACHMENT TO WALL & DECK ABOVE, AND THE TYPE
 OF FINISH MATERIAL AND THICKNESS.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FORCOMMERCIAL
 BUILDINGS. STRUCTURAL ELEMENTS.
  
 4) SHEET A1.01 NOTES INDICATE THE REPLACEMENT OF
 EXTERIOR WINDOW AND SLIDDING GLASS DOORS. SHEET A2.02
 PROVIDES WIND PRESSURES BUT THERE IS NO WIND DESIGN
 CRITERIA TO BASE THESE PRESSURES ON? NOTE IF THIS SUITE
 IS LOCATED IN A ZONE 4 OR ZONE 5.
  
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH ASCE 7-10 NOTE: HIGHRISE OF 200 FT.
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM ASCE 7-10. EXPOSURE D
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE ASCE 7-10.
  
 5) ON THE PRODUCT APPROVALS. PLEASE CIRCLE THE
 FOLLOWING INFORMATION. THE WIDTH & HEIGHT OF THE UNIT,
 TYPE OF GLAZING IF THERE IS OPTIONS, SILL HEIGHT OF
 SLIDDING GLASS DOOR UNITS, MULLIONS, RE-INFORCED OR
 NOT, HEIGHT AND WIDTH OF TRIBUTARY AREA, AND AMOUNT OF
 ANCHORS PER END PLATE AND TYPE OF ANCHORS TO BE
 INSTALLED. WITHOUT THIS INFORMATION A REVIEW CAN NOT
 TAKE PLACE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By albarran Date 2015-08-03 Time 18:58 Rev Time 0.00
Received By albarran Date 2015-08-03 Time 18:45 Sent To I
Notes
2015-08-03 18:59:51ALL ITEMS PREVIOUSLY REQUESTED AS PART OF THE FIRST
 REVIEW HAVE BEEN ADDRESSED SATISFACTORILY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By dhayes Date 2015-06-24 Time 15:39 Rev Time 0.00
Received By dhayes Date 2015-06-24 Time 13:23 Sent To  
Notes
2015-06-24 15:39:546/24/2015
 PROJECT: CONDO RENNOVATION
 PERMIT#: 15051008
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) NOTE 8 CALLS FOR NEW LED LIGHTING IN A NEW SOFFIT.
 1A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED LED LIGHTING INDICATING COMPLIANCE WITH NEC
 110.3 AND NEC 410
 1B) INDICATE HOW THE NEW LIGHTING IS TO BE CONTROLED.
  
 2) NOTE 10 INDICATES A NEW RECEPATACLE TO BE INSTALLED.
 2A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW
 RECEPTACLE ASSOCIATED WITH NOTE 10. NEC 210.52
 2B) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) NOTE 12 CALLS FOR A NEW GROUND FAULT OUTLET.
 3A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW
 RECEPTACLE ASSOCIATED WITH NOTE 12. NEC 210.8
  
 4) NOTE 13 CALLS FOR THE INSTALLATION OF NEW SMOKE
 DETECTORS.
 4A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW SMOKE
 DETECTORS ASSOCIATED WITH NOTE 13. FBC-R 314, 315
 4B) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 5) NOTE 16 CALL FOR THE INSTALLATION OF NEW RECESSED
 LIGHTING.
 5A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED RECESSED LIGHTING INDICATING COMPLIANCE WITH
 NEC 110.3 AND NEC 410
 5B) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8
  
 6) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED MIRROR LIGHTING INDICATING COMPLIANCE WITH NEC
 110.3 AND NEC 410
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2015-08-07 Time 14:17 Sent To B
Notes
2015-08-07 14:18:17JWITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-03 Cont ID  
Sent By albarran Date 2015-08-03 Time 19:01 Rev Time 0.00
Received By albarran Date 2015-07-09 Time 12:59 Sent To  
Notes
2015-08-03 19:27:158/3/15 - ALL TRADE REVIEWS OF SECOND SUBMITTAL
 COMPLETED AND READY FOR FURTHER CORRECTIONS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "A". MA
2015-07-09 13:03:22B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By dhayes Date 2015-06-24 Time 15:40 Rev Time  
Received By dhayes Date 2015-05-22 Time   Sent To  
Notes
2015-05-22 18:32:12B36

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-20 Cont ID  
Sent By ccole Date 2015-07-20 Time 12:12 Rev Time 0.00
Received By ccole Date 2015-07-20 Time 12:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By ccole Date 2015-06-22 Time 16:55 Rev Time 0.00
Received By ccole Date 2015-06-22 Time 16:55 Sent To  
Notes
2015-06-22 17:00:321ST REVIEW: FBC 2010 MECHANICAL
  
 1) CLARIFY THE SCOPE OF THE MECHANICAL WORK FOR THE
 PROJECT: WILL THE AC SUPPLY AND RETURN SYSTEM BE
 ALTERED DUE TO THE CONSTRUCTION OF THE NEW SOFFITS?
 PROVIDE AN ITEMIZED SCOPE OF WORK AND CORRELATING
 DETAILS ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-14 Cont ID  
Sent By tklarge Date 2015-06-14 Time 08:26 Rev Time 0.00
Received By tklarge Date 2015-06-14 Time 08:11 Sent To  
Notes
***NONE***