| Plan Review Stops For Permit 15050992 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-10 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-10 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-01 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-01 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2016-03-01 18:21:16 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT SURVEY/SITE PLAN FOR LOT 20. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-03-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-03-14 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-03-14 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2016-03-14 18:12:32 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY CORRECTED. PLANS REVIEWED UNDER PERMIT | | | 15030466. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-02 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-03-02 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-03-02 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2016-03-02 13:44:01 | 3/2/16 FAILED ELECTRICAL REVIEW AS NOTED. PLANS | | | REVIEWED UNDER 15030466. CP, LEM & SAK NOTIFIED VIA | | | EMAIL. MA | | | 1. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN | | | EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE | | | TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS. | | | THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL | | | SITE PLAN. TYPICAL | | | 2. FBC?E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50 OF | | | THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES BE HIGH | | | EFFICIENCY LAMPS. TYPICAL | | | 3. NEC 314.27(A) REQUIRES THAT BOXES IN CEILING FOR | | | LUMINAIRES BE LISTED TO SUPPORT A MINIMUM OF 50LBS. | | | TYPICAL | | | 4. NEC 314.27(D) STATES THAT OUTLET BOXES INTENDED FOR | | | THE SOLE SUPPORT OF PADDLE FANS BE LISTED AND MARKED BY | | | THE MANUFACTURER FOR THE PURPOSE. TYPICAL | | | 5. NEC 210.52(C)1 STATES THAT EVERY COUNTER SPACE | | | GREATER THAN 12? SHALL BE AN OUTLET. | | | 6. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR | | | CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM. | | | 7. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN | | | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT | | | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. | | | 8. RELOCATE SMOKE DETECTORS SO THEY ARE NO LESS THAN | | | 36? FROM THE TIP OF A PADDLE FAN BLADE. TYPICAL | | | 9. FBC?E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING | | | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC | | | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | | CONDITIONED & UNCONDITIONED SPACES. TYPICAL | | | 10. ADJUST THE ELECTRICAL LEGEND SO THE DISCONNECT | | | SYMBOL MATCHES THAT USED ON THE FLOOR PLAN (TYPICAL) | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-03-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-03-22 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-03-15 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-03-15 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-03-03 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2016-03-03 16:55:18 | PLANS UNDER 15030466 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-03-02 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-01-22 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2016-01-22 13:19:28 | PLANS UNDER 15030466 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2016-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-15 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-15 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2016-03-15 08:16:36 | MU2016-5930, IMPACT FEE PAID $43,965.00. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-10 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-10 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2016-03-10 15:50:41 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-02 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-02 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2016-03-02 09:34:29 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2016-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-02 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-02 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-01-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-31 |
Time |
04:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-31 |
Time |
04:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-03-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2016-03-17 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-03-17 11:31:51 | SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR | | | LANDACAPING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-03-11 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2016-03-11 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-03-11 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2016-03-11 13:57:35 | ** FAILED - REPEAT COMMENT FROM 2/2/16 ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR | | | ON THE PLANS WHERE APPLICABLE: | | | | | | 1.) BUILDING PERMIT ARCHITECTURAL ELEVATIONS DO NOT | | | MATCH THE FLOOR PLANS FROM THE APPROVED PLANS WITH THE | | | PLANNING DIVISION. MODIFICATIONS HAVE BEEN DETECTED. | | | PLEASE ENSURE ALL ELEVATIONS MATCH THE FLOOR PLANS FOR | | | CONSISTENCY. | | | | | | ADDITIONAL NOTES: | | | | | | * SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR | | | LANDSCAPING. | | | | | | * REVISIONS TO PLANS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-02-02 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2016-02-02 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-02-02 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2016-02-02 10:44:59 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR | | | ON THE PLANS WHERE APPLICABLE: | | | | | | 1.) BUILDING PERMIT ARCHITECTURAL ELEVATIONS DO NOT | | | MATCH THE FLOOR PLANS FROM THE APPROVED PLANS WITH THE | | | PLANNING DIVISION. MODIFICATIONS HAVE BEEN DETECTED. | | | PLEASE ENSURE ALL ELEVATIONS MATCH THE FLOOR PLANS FOR | | | CONSISTENCY. | | | | | | ADDITIONAL NOTES: | | | | | | * SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR | | | LANDSCAPING. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|