Plan Review Details - Permit 15050961
| Plan Review Stops For Permit 15050961 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-07-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-17 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-08 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-29 |
Time |
20:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-29 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2015-06-29 20:39:15 | APPROVED WITH THE FOLLOWING NOTATIONS:1 | | | IMPORTANT NOTICE: | | | IN ADDITION TO THE REQUIRED DISCONNECT, LUMINAIRE | | | W/SWITCH BY THE ENTRY AND THE SERVICE OUTLET FOR THE | | | AHU INSIDE THE ATTIC. NEC 110.34 ALSO STATES THAT A | | | PERMANENT LADDER OR STAIRWAY SHALL BE PROVIDED TO GIVE | | | SAVE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL | | | EQUIPMENT INSTALLED IN ATTICS. | | | CEILING LUMINAIRE OUTLETS SHALL;L SUPPORT 50# PER NEC | | | 314.27 | | | INSTALL INTER-SYSTEM BONDING TERMINAL AS IN NEC 250.94 | | | FEEDER TO EXISTING 60A PANEL SHALL NOT BE W/NM CABLE AS | | | IT IS NOT LISTED FOR WET LOCATIONS NEC 300.5(B) | | | ALL NEW DEVICES SHALL BE TAMPER-RESISTANT AS IN NEC | | | 406.11 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-30 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-27 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2015-07-27 15:29:14 | SKENNEDY DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-07-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-17 |
Time |
14:23 |
Rev Time |
|
| Received By |
skennedy |
Date |
2015-05-21 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-30 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-30 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2015-07-30 10:43:24 | FBC 2010 2ND REVUEW | | | | | | PROVISIONALLY APPROVED AS FOLLOWS: | | | | | | PROVIDE REVISION FOR: | | | | | | FBC-R M1305.1.3 APPLIANCES IN ATTICS. | | | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN | | | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE | | | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT | | | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES | | | (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG | | | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM | | | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE | | | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 | | | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE | | | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES | | | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE | | | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS | | | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY | | | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW | | | REMOVAL OF THE LARGEST APPLIANCE. | | | | | | FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE | | | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN | | | ACCORDANCE WITH CHAPTER 34. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-17 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-17 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2015-07-17 14:28:34 | 1ST REVIEW: FBC 2010 | | | | | | THE MECHANICAL PLAN IS TOO SMALL TO READ. THE SIZING | | | CALCULATION IS DIFFICULT TO READ. PROVIDE THE EQUIPMENT | | | SCHEDULE AND LEGIBLE SIZING CALCUATION SUCH THAT PROPER | | | SIZING MAY BE DETERMINED. THE SCHEDULE PROVIDED DOES | | | NOT INCLUDE CAPACITY. THE SIZING CALCULATION DOES NOT | | | LIST EQUIPMENT. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-06-13 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-13 |
Time |
05:16 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-13 |
Time |
02:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2015-06-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-08 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-08 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy