Plan Review Details - Permit 15050960
| Plan Review Stops For Permit 15050960 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-02 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-02 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2015-06-02 09:45:02 | ENTERED THIS STOP BY MISTAKE. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-02 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-02 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2015-06-02 09:46:04 | RECEIVED E-MAIL FROM KARI NEVILLE: | | | | | | SIZE OF THE DUCT FOR BEDROOM NUMBER TWO IS 8 INCHES | | | | | | A&J BUSINESS SOLUTIONS, INC. | | | KARI NEVILLE | | | 611 COMMERCE WAY SUITE G JUPITER, FL. 33458? | | | OEXPERTS IN COMMERCIAL/RESIDENTIAL PERMITTING AND | | | BUSINESS LICENSING | | | C: 561-373-3902 | | | O:561.348.4805 | | | F:561.575.1879 | | | 611 COMMERCE WAY SUITE G | | | JUPITER,?FL. 33458 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-02 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-05-21 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2015-05-22 08:31:27 | SENT TO J GOMEZ |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-02 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-02 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2015-06-02 09:51:41 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- IF THE SUPPLY DUCT FOR BEDROOM #2 IS 8", THEN THE 9" | | | TRANSFER DUCT SIZE DOESN'T COMPLY WITH THE BALANCE | | | RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | NOTE: THE APPROVED PLANS SHOWED 7" SUPPLY DUCT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-02 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-02 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2015-06-02 08:35:31 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- A/C PLAN DOESN'T SHOW THE SIZE OF SUPPLY DUCT FOR | | | BEDROOM #2. UNABLE TO VERIFY IF THE TRANSFER DUCT SIZE | | | SHOWN IS IN COMPLIANCE WITH THE BALANCE RETURN AIR SEC. | | | M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
|