| 2015-05-20 15:48:12 | |
| | WEST PALM BEACH MUNICIPAL CODE SECTION 38-46(B)(1) - |
| | TENT PERMIT: A PERMIT IS REQUIRED PRIOR TO ERECTION OF |
| | A TENT. |
| | |
| | NFPA 1 SECTION - 25.1.10.1.6 FLAMMABLE GAS: CONTAINERS |
| | FOR LIQUEFIED PETROLEUM GASES SHALL BE PLACED A MINIMUM |
| | OF 5 FEET FROM ANY TENT. TANKS SHALL BE SECURED IN THE |
| | UPRIGHT POSITION AND PROTECTED FROM VEHICULAR TRAFFIC. |
| | |
| | NFPA 1 SECTION - 25.1.12 GENERATORS: GENERATORS AND |
| | OTHER INTERNAL COMBUSTION ENGINES SHALL BE SEPARATED |
| | FROM TENTS BY A MINIMUM OF 5 FEET AND SHALL BE |
| | PROTECTED FROM CONTACT BY FENCING, ENCLOSURE OR OTHER |
| | APPROVED MEANS. |
| | |
| | NFPA 1 SECTION - 25.1.5.4 UNAUTHORIZED OPEN FLAME: |
| | UNAUTHORIZED OPEN FLAMES SHALL BE PROHIBITED IN ANY |
| | TENT OR TEMPORARY MEMBRANE STRUCTURE. |
| | |
| | NFPA 1 SECTION - 25.1.9 ELECTRICAL CORDS: CABLES ON THE |
| | GROUND IN AREAS TRAVERSED BY THE PUBLIC SHALL BE PLACED |
| | IN TRENCHES OR PROTECTED BY APPROVED COVERS. |
| | |
| | NFPA 1 SECTION - 25.2.1.2 TENT COVERAGE: TENTS SHALL BE |
| | ERECTED TO COVER NOT MORE THAN 75 PERCENT OF THE |
| | PREMISES. |
| | |
| | NFPA 1 SECTION - 25.2.2.1 FLAME SPREAD: ALL TENT FABRIC |
| | SHALL MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA |
| | CONTAINED IN NFPA 701, STANDARD METHODS OF FIRE TESTS |
| | FOR FLAME PROPAGATION OF TEXTILES AND FILMS. THE FLAME |
| | SPREAD CERTIFICATE MUST BE PROVIDED OR THE TENT CANNOT |
| | BE USED OR MUST BE REMOVED. |
| | |
| | NFPA 1 SECTION - 25.2.3.5 TENT PLACEMENT: THE PLACEMENT |
| | OF TENTS RELATIVE TO OTHER STRUCTURES SHALL BE AT THE |
| | DISCRETION OF THE AHJ. TENT TO BE LOCATED A MINIMUM OF |
| | 10 FEET FROM ANY BUILDING, STRUCTURE, OR ADJACENT STAKE |
| | LINE UNLESS PREVIOUSLY AND DIRECTLY APPROVED BY THE |
| | FIRE MARSHAL. |
| | |
| | NFPA 1 SECTION - 25.2.4 FIRE HAZARDS: THE GROUND |
| | ENCLOSED BY ANY TENT AND THE GROUND FOR A REASONABLE |
| | DISTANCE BUT FOR NOT LESS THAN 10 FEET OUTSIDE OF SUCH |
| | A TENT, SHALL BE CLEARED OF ALL FLAMMABLE OR |
| | COMBUSTIBLE MATERIAL OR VEGETATION THAT IS NOT USED FOR |
| | NECESSARY SUPPORT EQUIPMENT. THE PREMISES SHALL BE KEPT |
| | FREE FROM SUCH FLAMMABLE OR COMBUSTIBLE MATERIALS |
| | DURING THE PERIOD FOR WHICH THE PREMISES ARE USED BY |
| | THE PUBLIC. |
| | |
| | NFPA 1 SECTION - 25.2.4.2 NO SMOKING SIGNS: SMOKING |
| | SHALL NOT BE PERMITTED IN ANY TENT. THE POSTING OF |
| | WEATHERPROOF NO SMOKING SIGNS IS REQUIRED. |
| | |
| | NFPA 1 SECTION - 25.2.5 FIRE-EXTINGUISHING EQUIPMENT: |
| | PORTABLE FIRE EXTINGUISHING EQUIPMENT OF APPROVED TYPES |
| | SHALL BE FURNISHED AND MAINTAINED IN TENTS IN SUCH |
| | QUANTITY AND IN SUCH LOCATIONS AS APPROVED BY THE AHJ. |
| | LARGE EVENTS SHALL HAVE EXTINGUISHERS WITHIN 75FT OF |
| | EACH OTHER; MINIMUM 10LB ABC, THIRD PARTY CERTIFIED AND |
| | TAGGED. |
| | |
| | NFPA 1 SECTION - 50.2.1.9 COOKING EQUIPMENT: COOKING |
| | EQUIPMENT USED IN FIXED, MOBILE, OR TEMPORARY |
| | CONCESSIONS, SUCH AS TRUCKS, BUSES, TRAILERS, |
| | PAVILIONS, TENTS, OR ANY FORM OF ROOFED ENCLOSURE, |
| | SHALL COMPLY WITH NFPA 96. |
| | |
| | NFPA 101 SECTION - 12.2.8 ILLUMINATION OF MEANS OF |
| | EGRESS & EXIT SIGNS: MEANS OF EGRESS, FOR TENTS |
| | EXCEEDING 1200 SQUARE FEET, SHALL BE ILLUMINATED AND |
| | PROVIDED WITH EMERGENCY LIGHTING. |
| | |