| 2015-05-15 12:28:03 | 5/15/2015 |
| | PROJECT: ELECTRICAL BUILDOUT |
| | PERMIT#: 14060946 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW REVISION#15050566 |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) TWO COMPLETE COPIES OF PLANS INDICATING CLEARLY, |
| | ONLY THE CHANGES IN THE SCOPE OF WORK FOR |
| | CLARIFICATION. WPB AMENDMENTS TO THE FBC 107.3.1 |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2) PROVIDE A COMPLETE PANEL SCHEDULE INDICATING EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | 3) INDICATE THE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL |
| | SCHEDULE. WPB AMENDMENTS TO THE FBC 107.3.5.1.2 |
| | ELECTRICAL |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |