| 2015-05-16 12:22:27 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050533 |
| | ADD: 622 N. FLAGLER DR. SUITE # 903 |
| | CONT: BRANCH |
| | TEL: (561)833-6206 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 16/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2.0 HAS 25 NOTES ON THE SHEET RELATING TO THE |
| | SCOPE OF WORK THAT IS RELATED TO THIS PROJECT. 20 OF |
| | THESE NOTES REFER TO THE INTERIOR DESIGNERS DRAWINGS. |
| | THERE WERE NO SUCH PLANS SUBMITTED UNDER THIS REVIEW. |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2) THE MISSING INTERIOR DESIGNER DRAWINGS MUST MEET THE |
| | FOLLOWING FLORIDA STATUTE: 481.2131?INTERIOR DESIGN; |
| | PRACTICE REQUIREMENTS; DISCLOSURE OF COMPENSATION FOR |
| | PROFESSIONAL SERVICES.? (1)?A REGISTERED INTERIOR |
| | DESIGNER IS AUTHORIZED TO PERFORM ?INTERIOR DESIGN? AS |
| | DEFINED IN S. 481.203. INTERIOR DESIGN DOCUMENTS |
| | PREPARED BY A REGISTERED INTERIOR DESIGNER SHALL |
| | CONTAIN A STATEMENT THAT THE DOCUMENT IS NOT AN |
| | ARCHITECTURAL OR ENGINEERING STUDY, DRAWING, |
| | SPECIFICATION, OR DESIGN AND IS NOT TO BE USED FOR |
| | CONSTRUCTION OF ANY LOAD-BEARING COLUMNS, LOAD-BEARING |
| | FRAMING OR WALLS OF STRUCTURES, OR ISSUANCE OF ANY |
| | BUILDING PERMIT, EXCEPT AS OTHERWISE PROVIDED BY LAW. |
| | INTERIOR DESIGN DOCUMENTS THAT ARE PREPARED AND SEALED |
| | BY A REGISTERED INTERIOR DESIGNER MAY, IF REQUIRED BY A |
| | PERMITTING BODY, BE SUBMITTED FOR THE ISSUANCE OF A |
| | BUILDING PERMIT FOR INTERIOR CONSTRUCTION EXCLUDING |
| | DESIGN OF ANY STRUCTURAL, MECHANICAL, PLUMBING, |
| | HEATING, AIR-CONDITIONING, VENTILATING, ELECTRICAL, OR |
| | VERTICAL TRANSPORTATION SYSTEMS OR THAT MATERIALLY |
| | AFFECT LIFE SAFETY SYSTEMS PERTAINING TO FIRE SAFETY |
| | PROTECTION SUCH AS FIRE-RATED SEPARATIONS BETWEEN |
| | INTERIOR SPACES, FIRE-RATED VERTICAL SHAFTS IN |
| | MULTISTORY STRUCTURES, FIRE-RATED PROTECTION OF |
| | STRUCTURAL ELEMENTS, SMOKE EVACUATION AND |
| | COMPARTMENTALIZATION, EMERGENCY INGRESS OR EGRESS |
| | SYSTEMS, AND EMERGENCY ALARM SYSTEMS. |
| | 3) SHEET A2.0 NOTES 4,5,13,14 & 17 ALL DEAL WITH THE |
| | INTERIOR DESIGNERS PLANS, PLEASE NOTE THIS BUILDING WAS |
| | BUILT AFTER MARCH 13. 1991 AND MUST MEET THE FAIR |
| | HOUSING REQUIREMENTS, PLEASE REVIEW REQUIREMENT 3 FOR |
| | USABLE DOORS ARE THE MINIMUM REQUIRED WIDTH. WITH NOT |
| | HAVING THE INTERIOR DESIGNERS PLANS CODE COMPLIANCE |
| | CANNOT BE VERIFIED. |
| | 4) SHEET A2.0 NOTES 3,6,12 & 24 DEAL WITH EITHER |
| | DROPPED CEILINGS AND OR SOFFITS. BOTH OF THESE ELEMENTS |
| | ARE LOAD BEARING. THE INTERIOR DESIGNER CAN SUBMIT |
| | DRAWINGS FOR THE CONCEPT BUT THE ARCHITECT OR AN |
| | FLORIDA P. E. CAN DESIGN THE STRUCTURAL ELEMENTS TO |
| | MAKE UP THE SOFFITS AND DROPPED CEILINGS. DESIGN |
| | CRITERIA TO CONSIDER IN THE PLANS ARE THE FOLLOWING: |
| | ATTACHMENT METHOD TO THE DECK ABOVE, FROM THE FRAMING |
| | MEMBERS TO FRAMING MEMBERS & FRAMING MEMBERS TO WALL |
| | ATTACHMENT. NOTE THIS IS HIGH RISE CONSTRUCTION, AND |
| | NONCOMBUSTIBLE MATERIALS TO BE INSTALLED FBC-B 603. |
| | PLEASE PROVIDE FRAMING MEMBER SIZE, THICKNESS (GAUGE) |
| | SPACING BETWEEN FRAMING MEMBERS, THE PSF DESIGNED FOR, |
| | ALLOWABLE CEILING SPANS AS WELL AS DEFLECTION |
| | LIMITATION. PROVIDE IF THE FRAMING MEMBERS WILL NEED A |
| | STIFF BACK AT MID SPAN OR NOT. FBC-B TABLE 2508.1 STEEL |
| | FRAMING FOR GYPSUM BOARD. |
| | 5) PLEASE NOTE THE ELEVATOR LOBBY WALLS ARE FIRE RATED |
| | WALLS AND NOTE 24 INDICATES MODIFICATIONS TO THE |
| | CEILING PLAN. THE ARCHITECT OF RECORD WILL ALSO NEED TO |
| | PROVIDE THE THROUGH PENETRATION FOR ANY FIRE STOPPING |
| | ASSEMBLIES REQUIRED FOR PENETRATIONS. 2010 FBC-B |
| | 713.3.1 THROUGH PENETRATIONS. |
| | 6) WITHIN THE PERMIT PACKAGE WAS ALSO SUBMITTED A SALES |
| | BROCHURE FOR SUPER SAM 125 SOUND INSULATION AND A FLAME |
| | SPREAD TEST ASTM E 84. THIS IS THE CORRECT TESTING FOR |
| | FLAME SPREAD BUT NO TESTING REPORTS WERE SUBMITTED FOR |
| | SOUND. PLEASE PROVIDE COMPLIANCE WITH; |
| | 6A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | FA THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |