Plan Review Details - Permit 15050531
Plan Review Stops For Permit 15050531
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2015-07-13 Cont ID  
Sent By ccole Date 2015-07-13 Time 12:25 Rev Time 0.00
Received By ccole Date 2015-07-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By jwitmer Date 2015-06-30 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2015-06-29 Time   Sent To  
Notes
2015-06-30 11:40:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050531
 MASTER PERMIT: 14100350
 ADD: 10130 NORTHLAKE BLVD.
 CONT: SOURCE REFRIGARATION
 TEL: (904)486-3927
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1) THE SUBMITTED PLANS SHEETS, THE COVERSHEET, D-1,
 EQ-1, S1,S2 & S3 ARE ALL DATED 8/18/14 AND THERE IS NO
 REVISION INDICATED ON THE PLANS. THESE PLANS ARE THE
 SAME PLANS APPROVED BY THE CITY AND ON FILE IN THE CITY
 RECORDS. PLEASE NOTE THESE ARE PLANS DESIGNED BY
 DOUGLAS A. RAMIREZ WITH THE ATKINS .
  
 NONE OF THESE PLANS ARE SIGNED NOR SEALED BY THE
 ENGINEER OF RECORD. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-07-13 Cont ID  
Sent By ccole Date 2015-07-13 Time 12:25 Rev Time 0.00
Received By ccole Date 2015-07-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-07-06 Cont ID  
Sent By dhayes Date 2015-07-06 Time 12:49 Rev Time 0.00
Received By dhayes Date 2015-07-06 Time 12:49 Sent To  
Notes
2015-07-06 13:03:57ELECTRICAL REVIEW PERFORMED UNDER MASTER:14100350
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-06 Cont ID  
Sent By dhayes Date 2015-07-06 Time 13:04 Rev Time 0.00
Received By dhayes Date 2015-05-14 Time 15:07 Sent To  
Notes
2015-05-14 13:58:40ROUTED TO MECHANICAL OVER $ 5000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-13 Cont ID  
Sent By ccole Date 2015-07-13 Time 12:10 Rev Time 0.00
Received By ccole Date 2015-07-13 Time 12:10 Sent To  
Notes
2015-07-13 12:22:42PERMIT #15050531
 7/13/15
  
 MECHANICAL PROVISO:
  
 EXISTING REFRIGERANT LEAK DETECTION SYSTEM IN
 MECHANICAL CENTER MUST BE VERIFIED IN FIELD TO BE
 OPERATIONAL, OR A REVISION TO THE APPROVED PLANS IS
 REQUIRED FOR ALL NECESSARY MODIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By ccole Date 2015-05-27 Time 12:38 Rev Time 0.00
Received By ccole Date 2015-05-27 Time 12:37 Sent To  
Notes
2015-05-27 12:58:131ST REVIEW: FBC 2010 MECHANICAL
  
 1) PLEASE REVISE THE INDEX OF DRAWINGS TO MATCH THE
 PLAN SETS.
 2) THE PLANS SHALL BE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD- SECTION 105.3.1.2(5) WPB AMENDMENTS TO THE
 FBC-10 BUILDING.
 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN
 EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND
 SECTION 1104.2 FMC-10. IDENTIFY WHICH SYSTEMS ARE R22
 AND WHICH ARE R404A.
 4) SHEET S-2 INDICATES INSTALLATION OF NEW AC SYSTEMS:
 PLEASE PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND
 SUBMIT AC LOAD CALCULATIONS IN ACCORDANCE WITH ACCA
 MANUAL N- SECTION 503.2.1 FBC-10 ENERGY.
 5) CONCERNING THE NEW AC UNITS: WILL NEW DS DETECTORS
 BE INSTALLED. PROVIDE DETAILS ON THE PLANS IF
 APPLICABLE.
 6) SHEET S-2 INDICATES A NEW ROOF HATCH. CLARIFY IF A
 NEW ACCESS LADDER IS BEING INSTALLED AND PROVIDE
 DETAILS IF APPLICABLE PER SECTION 306.5 FMC-10.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  