Plan Review Details - Permit 15050530
Plan Review Stops For Permit 15050530
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-13 Cont ID  
Sent By ccole Date 2015-07-13 Time 11:06 Rev Time 0.00
Received By ccole Date 2015-07-13 Time 11:06 Sent To  
Notes
2015-07-13 11:10:16PERMIT #15050530
 500 BELVEDERE RD.
 7/13/15
  
 PROVISOS: THE RE-SUBMITTED PLANS WERE RETURNED WITHOUT
 ADDRESSING ALL 1ST REVIEW COMMENTS. I AM APPROVING THE
 PLANS WITH EXCEPTION, HOWEVER REVISIONS TO THE
 PERMITTED PLANS ARE REQUIRED. PLEASE PROVIDE:
 1) SHEET R8: ENLARGED MECHANICAL CENTER LAYOUT PLANS
 IDENTIFYING ALL COMPONENTS OF THE STRUCTURE, AND
 EQUIPMENT CONTAINED WITHIN.
 2) UPDATED SHOP DRAWINGS FOR THE MECHANICAL CENTER TO
 MEET THE CURRENT WIND LOAD DESIGN CRITERIA IN
 ACCORDANCE WITH SECTION1609 FLORIDA BUILDING CODE 2010.
 THE DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE
 ARCHITECT OF RECORD.
 3) CERTIFICATION OR OTHER DOCUMENTATION TO VERIFY
 INSPECTION APPROVAL OF THE PRE-MANUFACTURED CENTER.
 4) MECHANICAL CENTER VENTILATION DETAILS AND
 CALCULATIONS VERIFYING COMPLIANCE WITH SECTIONS
 1105.5.6.3 FBC-10 MECHANICAL FOR NORMAL OPERATION, AND
 1105.6.4 FOR EMERGENCY CONDITIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By ccole Date 2015-05-27 Time 08:38 Rev Time 0.00
Received By ccole Date 2015-05-27 Time 08:38 Sent To  
Notes
2015-05-27 08:42:291ST REVIEW: FBC 2010 MECHANICAL
  
 1) ALL PLANS , INCLUDING SHEETS A-1 AND EQ-1, SHALL BE
 SIGNED AND SEALED BY THE ENGINEER OF RECORD- SECTION
 105.3.1.2(5) WPB AMENDMENTS TO THE FBC-10 BUILDING.
 2) SHEETS R-1& R-3: INDICATE THE DISCHARGE OR
 TERMINATION LOCATIONS OF THE CONDENSATE PIPING FROM ALL
 COMPONENTS OF THE REFRIGERATION SYSTEMS INCLUDING THE
 WALK-IN BOXES, CASES, CONDENSERS, CHILLERS, ETC. PLEASE
 NOTE THAT CONDENSATE FROM COOLING COILS IS PROHIBITED
 TO DISCHARGE INTO THE SANITARY SYSTEM PER SEC. 90-126
 WPB CODE OF ORDINANCES.
 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN
 EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND
 SECTION 1104.2 FMC-10.
 4) SHEET R-8: THE REFRIGERATION ROOF PLAN DETAIL, AND
 THE MECHANICAL CENTER DIAGRAM ON THE SHEET NEED TO BE
 ENLARGED FOR CLARITY: PLEASE COMPLY.
 5) SHEET R-8: PLEASE REVIEW AND UPDATE THE WIND LOAD
 DESIGN CRITERIA FOR THE MECHANICAL CENTER TO 170 MPH
 PER SECTION 1609 FBC-10 BUILDING.
 6) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 CONDENSERS AND MECHANICAL CENTER TO THE MAIN STRUCTURE-
 SECTION 301.12 FMC-10. SUBMIT NOA?S OR FL. PRODUCT
 APPROVALS FOR THE ROOF STANDS.
 7) PROVIDE THE EFFICIENCY RATINGS FOR CHILLERS 1 & 2-
 TABLE 503.2.3(7) FBC-10 ENERGY CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  