| 2015-05-27 08:42:29 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | |
| | 1) ALL PLANS , INCLUDING SHEETS A-1 AND EQ-1, SHALL BE |
| | SIGNED AND SEALED BY THE ENGINEER OF RECORD- SECTION |
| | 105.3.1.2(5) WPB AMENDMENTS TO THE FBC-10 BUILDING. |
| | 2) SHEETS R-1& R-3: INDICATE THE DISCHARGE OR |
| | TERMINATION LOCATIONS OF THE CONDENSATE PIPING FROM ALL |
| | COMPONENTS OF THE REFRIGERATION SYSTEMS INCLUDING THE |
| | WALK-IN BOXES, CASES, CONDENSERS, CHILLERS, ETC. PLEASE |
| | NOTE THAT CONDENSATE FROM COOLING COILS IS PROHIBITED |
| | TO DISCHARGE INTO THE SANITARY SYSTEM PER SEC. 90-126 |
| | WPB CODE OF ORDINANCES. |
| | 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN |
| | EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND |
| | SECTION 1104.2 FMC-10. |
| | 4) SHEET R-8: THE REFRIGERATION ROOF PLAN DETAIL, AND |
| | THE MECHANICAL CENTER DIAGRAM ON THE SHEET NEED TO BE |
| | ENLARGED FOR CLARITY: PLEASE COMPLY. |
| | 5) SHEET R-8: PLEASE REVIEW AND UPDATE THE WIND LOAD |
| | DESIGN CRITERIA FOR THE MECHANICAL CENTER TO 170 MPH |
| | PER SECTION 1609 FBC-10 BUILDING. |
| | 6) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE |
| | CONDENSERS AND MECHANICAL CENTER TO THE MAIN STRUCTURE- |
| | SECTION 301.12 FMC-10. SUBMIT NOA?S OR FL. PRODUCT |
| | APPROVALS FOR THE ROOF STANDS. |
| | 7) PROVIDE THE EFFICIENCY RATINGS FOR CHILLERS 1 & 2- |
| | TABLE 503.2.3(7) FBC-10 ENERGY CONSERVATION. |
| | |