| 2015-06-10 10:17:10 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050482 |
| | ADD: 915 NORTH DIXIE HWY. |
| | CONT: CONSTRUCTION REMODELING 1 |
| | TEL: (561)714-0696 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 10/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 THE COVER SHEET: |
| | 1A) BUILDING DATA: |
| | 1A)(1) THE OCCUPANCY TYPE IS LISTED AS BUSINESS WITH A |
| | SQUARE FOOTAGE OF 4173 SQ. FT. PLEASE NOTE THE LAST |
| | KNOWN USE WAS UNDER PERMIT # 08030500 |
| | A MIXED USE BUILDING, BUSINESS: LAW OFFICES & S2 |
| | PARKING GARAGE. THE WORK TO BE COMPLETED UNDER THIS |
| | PERMIT IS IN THE PORTION OF THE MIXED USE KNOWN TO BE A |
| | S2 OCCUPANCY THE PARKING GARAGE, WITH AN AREA OF 4173 |
| | SQ. FT. THIS WILL BE A CHANGE OF OCCUANCY TO AN A3 A |
| | GYM. SEE THE 2010 FBC-B 303.1 IS THE GYM WITHOUT |
| | SPECTATOR SEATING? IF NO SPECTATOR SEATING THE |
| | OCCUPANCY CLASSIFICATION WOULD BE A A-3. IF THERE IS |
| | SPECTATOR SEATING THE OCCUPANCY CLASSIFICATION WILL BE |
| | A A-4. |
| | |
| | 1A)(2) OCCUPANT LOAD IS TAKEN FOR A BUSINESS OCCUPANCY |
| | @ 100 SQ. FT. PER OCCUPANT. SHEET A-1 DOES NOT SHOW ANY |
| | EQUIPMENT FOR THE GYM SO THE OCCUPANT LOAD IS TAKEN @ |
| | 15 SQ. FT. PER OCCUPANT. FBC-B TABLE 1004.1.1, THE |
| | OCCUPANT LOAD WILL BE 4173/ 15= 279 OCCUPANTS. |
| | |
| | 2) PLEASE REVIEW THE 2010 FBC-B TABLE 508.4 REQUIRED |
| | OCCUPANCY SEPARATION, FOR NON-SPRINKLERED BUILINGS |
| | BETWEEN A BUSINESS OCCUPANCY AND A ASSEMBLY OCCUPANCY |
| | THE OCCUPANY SEPARATION WALLS REQUIRE A 2 HOUR FIRE |
| | SEPARATION. UNDER THE PERMIT # 08030500 THE DRESSING |
| | ROOM, SHOWER AND THE (2) ACCESSIBLE RESTROOMS WERE PART |
| | OF THE REQUIRED PLUMBING FIXTURE COUNT FOR THE LAW |
| | OFFICES. |
| | |
| | 2A) PLEASE INDICATE HOW THE OTHER EXISTING TENANT |
| | (BUSINESS OCCUPANCY) SPACE WILL REMAIN CODE COMPLIANT |
| | WITH THE REMOVAL OF THESE RESTROOMS FROM THAT TENANTCY? |
| | FBC-B 102.6 EXISTING STRUCTURES THAT WERE CODE |
| | COMPLIANT ARE STILL CODE COMPLIANT WHEN NO WORK IS |
| | COMPLETED. UNDER THE SCOPE OF THIS PERMIT YOU MAY BE |
| | CREATING A NON-CONFORMITY IN THE CODE BY NOT HAVING |
| | ENOUGH RESTROOMS FOR THE OCCUPANT LOAD. |
| | |
| | 2B) WITH THE NEW TENANCY DELINEATION BETWEEN THE |
| | BUSINESS OCCUPANCY AND ASSEMBLY OCCUPANCY AND THE |
| | OCCUPANCY SEPARATION WALL CHANGING LOCATION AT THE |
| | DRESSING ROOM, SHOWER, RESTROOMS AND INFILL DOOR |
| | OPENINGS, PLEASE PROVIDE DOCUMENTATION OF HOW THE NEW |
| | WALLS WILL BE BUILT TO MAINTAIN A 2 HOUR FIRE |
| | SEPERATION BETWEEN THE (2) OCCUPANCIES. 2010 FBC-B |
| | TABLE 508.4 & 707.3.8 FIRE BARRIERS SEPARATING MIXED |
| | OCCUPANCIES. |
| | |
| | 3) SHEET A1 EXTERIOR WALL DETAIL INDICATES WITHIN THE |
| | NOTES THE STRUCTURAL PLANS ARE DESIGNED TO THE 2010 |
| | FLORIDA RESIDENTIAL CODE, PLEASE CORRECT, THIS IS UNDER |
| | THE 2010 FLORIDA BUILDING CODE- BUILDING CODE. |
| | |
| | 4) PLEASE PROVIDE A SITE PLAN OR SURVEY WITH THE REAR |
| | PROPERTY LINE INDICATED, TO VERIFY THE NEW REAR EXIT |
| | DOOR DOES NOT ROSS OVER THE PROPERTY LINE. |
| | 2010 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC REIGHT -OF-WAY. |
| | |
| | 5) SHEET A1 THE WIND DESIGN INDICATES THE WIND DESIGN |
| | AS 170 MPH, EXPOSURE B, PLEASE PROVIDE THE MEAN ROOF |
| | HEIGHT AND PRESSURES IN VASD. FBC-B 1609.1.5/ |
| | 1609.1.2.3.1. |
| | |
| | 6) SHEET A1 DETAIL # 3 INDICATES THERE TO BE A NEW |
| | LINTEL AND A # 5 24 INCHES LONG VERTICALLY DOWELLED |
| | INTO EVERY EXISTING FILLED CELL ABOVE. THE PLANS DO NOT |
| | INDICATE HOW THE NEW #5 REINFORCING BARS ARE TO TIE |
| | INTO THE FOOTING AND TO THE BEAM ABOVE TO BE PART OF |
| | THE MWFRS MAIN WIND FORCE RESISTING SYSTEM, NOR HOW |
| | MUCH EMBEDDMENT INTO THE FOUNDATION AND BEAM ABOVE IS |
| | REQUIRED. |
| | |
| | 7) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW |
| | EXTERIOR SWING DOOR. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) THE A-1 SHEET DOESN'T SHOW THE LOCATION OF THE |
| | REQUIRED FIRE EXTINGUISHERS PER FBC-B 906.1.1. |
| | |
| | 10) MISSING ON THE PLANS THE INTERIOR FINISH |
| | CLASSIFICATION EXIST. BLDG CODE.912.3. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |