| 2015-05-12 12:36:26 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| | PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 2) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH |
| | CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING |
| | UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT |
| | INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT. |
| | NEC 210.12 |
| | |
| | 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 4) QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. WPB |
| | AMENDMENTS TO FBC 107.2.1.4 |
| | |
| | 5) THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| | APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| | PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| | CONSTRUCTION. WPB AMENDMENTS FBC 107.2.1 |
| | |
| | 6) 110.26 SPACES ABOUT ELECTRICAL EQUIPMENT. |
| | SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED |
| | AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT |
| | READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| | EQUIPMENT. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |