Plan Review Details - Permit 15050392
Plan Review Stops For Permit 15050392
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 16:18 Rev Time 0.00
Received By jgomez Date 2015-08-31 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-08-12 Cont ID  
Sent By jgomez Date 2015-08-12 Time 16:27 Rev Time 0.00
Received By jgomez Date 2015-08-12 Time 16:26 Sent To  
Notes
2015-08-12 16:30:40FITH BUILDING REVIEW COMMENTS:
  
  
 NOTE: THE FOLLOWING COMMENTS MAY BE APPROVED WITH
 PROVISO. WAITING FOR CONTRACTOR'S CONFIRMATION ON
 PROVISO. FEES MAY APPLY.
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 NOTE ON DRAWING A201 PARTIALLY ADDRESSES THE
 REQUIREMENT. IT ONLY MENTION GUTTERS AND LEADERS. THE
 PURPOSE OF THIS CODE SECTION IS TO PROVIDE A LOT
 GRADING PLAN SHOWING HOW DIVERTING ALL THE SURFACE
 DRAINAGE TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION.
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 MARK FROM DELCREST WILL GET THE SOIL TEST REPORT WITH
 ALL THE INFORMATION.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. SPECIFY
 TYPE AND NUMBER OF NAILS OR SCREWS.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 REVISED DRAWING A801 WAS NOT SUBMITTED TO THE CITY YET.
 E-MAIL ATTACHMENT SHOWS TYPICAL 1-STORY WALL SECTION
 DETAIL D1 WITH THE FOLLOWING SPECIFICATIONS: "ENTEGRA
 FLAT ROOF TILE (NAIL W/ (2) 8D GALV RINGSHANK COIL
 NAILS PER TILE. SEE ROOFING PERMIT". ROOF TILE FLORIDA
 PRODUCT APPROVAL FL7804-R7 SUBMITTED DOESN'T HAVE ANY
 INFORMATION SHOWING THE PROPOSED FASTENING. WITHOUT THE
 ATTACHMENT RESISTANCE INFORMATION I CAN NOT VERIFY IF
 THE PROPOSED NAILS WILL MEET THE DESIGN PRESSURES OF
 SEC. R301 OF 2010 FBC-RESIDENTIAL. ARCHITECT TO PROVIDE
 CALCULATIONS SHOWING THAT THE PROPOSED NAIL-ON SYSTEM
 WILL MEET THE DESIGN CRITERIA OF SEC. R301. (NOTE:
 TYPICALLY MIAMI-DADE NOA'S LIST ALL THIS INFORMATION.
 FLORIDA PRODUCT APPROVALS DON'T. THAT'S WHY THE
 ARCHITECT NEEDS TO PROVIDE THE INFORMATION).
  
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 REVISED DRAWING A202 WAS NOT SUBMITTED TO THE CITY YET.
 E-MAIL ATTACHMENT SHOWS REVISED DOOR SCHEDULE WITH
 ENTRY DOOR #102 SIZE AS FOLLOWS 3'-4" WD X 8'-0" HGT.
 PGT SERIES "FD-750" OUTSWING ALUMINUM FRENCH DOOR NOA
 14-1117.05 SUBMITTED DOESN'T COVER DOORS WITH THE WIDTH
 SPECIFIED ON THE DOOR SCHEDULE. PROVIDE NEW PRODUCT
 APPROVAL THAT COVERS THIS SIZE OR REVISE DOOR SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  
  
 JULIO,
 I WANT TO APOLOGIZE AS I AM NOT SURE WHAT IS HAPPENING
 BUT IT SEEMS YOU AREN?T GETTING THE CORRECTION INFO I
 HAVE PROVIDED ON THIS JOB.
 ATTACHED IS MY 2ND RESPONSE LETTER TO YOU FOR THE
 COMMENTS FROM 7/22/15.
 ALSO ANY SHEETS THAT WERE REVISED AND CLOUDED REGARDING
 YOUR COMMENTS BELOW
 MY RESPONSES TO YOUR COMMENTS ARE IN GREEN BELOW
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
 FOR THE DRAINAGE PLAN I ADDED THE ROOF GUTTER/DRAINAGE
 NOTE TO SHEET A201 (SEE ATTACHED SHEET A201)
 THIS IS WHAT I HAVE DONE ON OTHER IBIS JOBS FOR SHELLEY
 FRIEFELD (SOUTHERN HOMES)
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE
 INFORMATION AS REQUIRED BY SEC. 1803.6 FBC-2010.
 MARK FROM DELCREST IS TRYING TO GET THE SOIL TEST INFO
 CORRECTED.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC.
 107.2.1.2 CITY AMENDMENTS. SPECIFY TYPE AND NUMBER OF
 NAILS OR SCREWS.
 WE CHANGED TO NAIL DOWN ROOF ON 1ST COMMENTS AND I HAD
 ADDED THE NOTE TO ATTACH PER ROOFING PERMIT.
 I HAVE ADDED THE NAILING SPECIFIED BY THE ROOFING
 PERMIT (SEE ATTACHED SHEET A901)
  
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND
 ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
 MAHOGANY DOOR WAS CHANGED TO PGT FD-750 OUTSWING DOOR &
 SIDELIGHTS ON 1ST COMMENTS (SEE ATTACHED SHEET A202)
 I REVIEWED & APPROVED THE NOA FOR THIS WITH ALL THE
 OTHER SUBMITTED NOA?S.
  
 B) ROOF TILE ADHESIVE AS SPECIFIED ON DETAIL D1 ON
 SHEET A801.
  
 ROOF CHANGED TO NAIL DOWN TILE ON 1ST COMMENTS
  
 C) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.
  
 PEEL & STICK WAS ELIMINATED ON THE 1ST COMMENTS
  
  
 GARY STOFFT
  
 - LOT 15 BP BLDG COMMENTS 02.PDF - 1501021 LOT 15 BP
 A201 FL REV02.PDF - 1501021 LOT 15 BP A202 FL REV01.PDF

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-08-12 Cont ID  
Sent By jgomez Date 2015-08-10 Time 12:46 Rev Time 0.00
Received By jgomez Date 2015-08-10 Time 12:41 Sent To  
Notes
2015-08-10 12:46:47 
 NOTE: THE FOLLOWING COMMENTS MAY BE APPROVED WITH
 PROVISO. WAITING FOR CONTRACTOR'S CONFIRMATION ON
 PROVISO. FEES MAY APPLY.
  
 FOURTH BUILDING REVIEW COMMENTS:
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. SPECIFY
 TYPE AND NUMBER OF NAILS OR SCREWS.
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
 B) ROOF TILE ADHESIVE AS SPECIFIED ON DETAIL D1 ON
 SHEET A801. C) PEEL & STICK CONCRETE ROOF TILE
 UNDERLAYMENT AS SPECIFIED ON DETAIL D1 OF SHEET A801.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-30 Cont ID  
Sent By jgomez Date 2015-07-30 Time 10:42 Rev Time 0.00
Received By jgomez Date 2015-07-30 Time 10:42 Sent To  
Notes
2015-07-30 10:51:58 
  
 *****NOTES:
 A) THE COMMENTS BELOW ARE BASED ONLY ON THE
 RE-SUBMITTAL PACKAGE I HAVE IN FRONT OF ME TO DO THE
 REVIEW. WHATEVER I AM ASKING FOR IS BECAUSE IS NOT
 HERE.
  
 B) I ALSO NOTICED THAT THERE IS ONLY ONE SET OF PRODUCT
 APPROVALS IN THIS PACKAGE: THE OTHER SET OF PRODUCT
 APPROVALS WAS SIGNED OUT ON 7/24/15. THE FOLLOWING ARE
 THE NOA'S THAT WE HAVE IN THIS PACKAGE: GARAGE DOOR NOA
 12-0517.16, FRENCH DOORS NOA 14-1117.05, SLIDING GLASS
 DOORS NOA 14-0128.11, MULLIONS NOA 14-1105.01, FIXED
 WINDOWS NOA 13-0502.03 AND HORIZONTAL SLIDING WINDOWS
 NOA 11-1114.04. THEREFORE, WE NEED THE SECOND SET
 RE-SUBMITTED. THE PRODUCT APPROVALS THAT WERE SIGNED
 OUT AND THE PRODUCT APPROVALS LISTED BELOW NEED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
  
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
 B) ROOF TILE. (REPEAT COMMENT. NOT ADDRESSED)
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE. (REPEAT COMMENT. NOT ADDRESSED)
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801. (REPEAT COMMENT.
 NOT ADDRESSED)
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 IN WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: REVIEW AND
 APPROVE ALSO ALL PRODUCT APPROVALS THAT WERE ALREADY
 SUBMITTED. (REPEAT COMMENT. NOT ADDRESSED)
  
 5- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED)
  
 6- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 7- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED)
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS. (REPEAT COMMENT.
 RESPONSE LETTER NOT SUBMITTED. REVIEW TOOK LONGER
 LOOKING FOR THE INFORMATION).
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-22 Cont ID  
Sent By jgomez Date 2015-07-22 Time 10:55 Rev Time 0.00
Received By jgomez Date 2015-07-22 Time 10:55 Sent To  
Notes
2015-07-22 11:01:34 
 ****NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. COMMENTS
 BELOW MAY BE ADDRESSED AFTER PERMIT IS PRINTED.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE
 PROVISO OPTION IS ACCEPTABLE. OTHERWISE, RESUBMIT
 REQUIRED INFORMATION BEFORE ISSUING PERMIT.
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
 B) ROOF TILE. (REPEAT COMMENT. NOT ADDRESSED)
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE. (REPEAT COMMENT. NOT ADDRESSED)
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801. (REPEAT COMMENT.
 NOT ADDRESSED)
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 IN WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: REVIEW AND
 APPROVE ALSO ALL PRODUCT APPROVALS THAT WERE ALREADY
 SUBMITTED. (REPEAT COMMENT. NOT ADDRESSED)
  
 5- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED)
  
 6- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 7- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED)
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS. (REPEAT COMMENT.
 RESPONSE LETTER NOT SUBMITTED. REVIEW TOOK LONGER
 LOOKING FOR THE INFORMATION).
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By jgomez Date 2015-06-27 Time 16:42 Rev Time 0.00
Received By jgomez Date 2015-06-27 Time 14:09 Sent To  
Notes
2015-06-27 16:59:53NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- NEED TO SPECIFY CARBON MONOXIDE ALARMS. SEC R315 OF
 2010 FBC-RESIDENTIAL.
  
 3- SHEET A901: REVISE THE SLIDING GLASS DOORS AND
 WINDOWS HEAD AND JAMB NOTES. BEVELED BUCKS ARE NOT
 ALLOWED. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 4- SHEET S2:
 A) DETAIL 1/S2 IS MISSING THE ROOF SHEATHING NAIL TYPE,
 SIZE AND SPACING. SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM #5 BELOW.
  
 B) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
  
 5- DETAIL 12/S3: SEC R803.2.3.1 OF 2010 FBC-RESIDENTIAL
 REQUIRES 8D RING SHANK NAILS MIN. PLYWOOD BLOCKING
 DETAIL CALLS FOR 10D NAILS. REVISE AS REQUIRED OR
 PROVIDE CALCULATIONS SHOWING THAT 10D NAILS ARE EQUAL
 OR BETTER THAN 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY
 AMENDMENTS. NOTE: COORDINATE WITH ITEM # 4(A) ABOVE.
  
 6- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 7- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 8- REVISE THE ENERGY CALCULATIONS. SEC 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION:
 A) PROVIDE CORRECT BUILDER'S NAME, CORRECT PERMIT
 OFFICE AND CORRECT JURISDICTION NUMBER ON TOP OF FORM.
  
 B) IDENTIFY WHERE ARE THE INSULATED DOORS SHOWN ON PAGE
 4 OF 6. IT DOESN'T MATCH PLANS AND PRODUCT APPROVALS.
  
 C) REVISE THE BUILDING ORIENTATION TO MATCH PLANS. AND,
 REVISE THE WALLS AND WINDOWS ORIENTATION ACCORDINGLY.
  
 D) REVISE THE OVERHANG DEPTH AND SEPARATION OF EACH
 WINDOW/DOOR TO MATCH PLANS.
  
 ***NOTE: WINDOWS AND DOORS LABELS WILL BE REQUIRED
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM
 #7.
  
 9- PROVIDE STRUCTURAL FRAMING DETAIL FOR OVAL WINDOWS
 AS SHOWN ON PLANS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE ASSEMBLY AS SHOWN ON PLANS.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE.
  
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS IN WRITING (NOT SIGNING AND SEALING)
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS.
  
 14- SLIDING GLASS DOORS NOA 14-0128.11. PAGE 6 OF 22
 WAS HIGHLIGHTED WITH TABLE 1A WITH LOWER SILL HEIGHT.
 DOORS WITH LOW SILL HEIGHT DON'T MEET THE DESIGN
 PRESSURES FOR OPENING #110. REVISE AS REQUIRED.
  
 15- TRUSS PACKAGE:
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $568,741. THE
 PERMIT FEE BALANCE IS $8938.19.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-27 Cont ID  
Sent By albarran Date 2015-07-27 Time 16:52 Rev Time 0.00
Received By albarran Date 2015-07-27 Time 12:30 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-02 Cont ID  
Sent By albarran Date 2015-07-02 Time 10:36 Rev Time 0.00
Received By albarran Date 2015-07-02 Time 09:05 Sent To I
Notes
2015-07-02 10:36:36PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. ELECTRICAL NOTES, GENERAL #6, PLEASE NOTE THAT ROMEX
 IS A BRAND NAME AND NOT A CABLE TYPE. CORRECT THE NOTE
 TO REFLECT THE CABLE TYPE INTENDED FOR USE.
 2. ELECTRICAL NOTES, GENERAL #13, ANY CONDUCTOR EXPOSED
 TO WET LOCATIONS, REGARDLESS OF SIZE SHALL BE LISTED
 ACCORDINGLY.
 3. ELECTRICAL NOTES, OUTLETS #3, TAMPER-RESISTANT
 OUTLETS REQUIREMENTS IS AT NEC 406.11 AND NOT AT NEC
 210.52. CORRECT NOTE ACCORDINGLY.
 4. ELECTRICAL NOTES, SMOKE DETECTOR #2, SHALL BE
 AMENDED TO INCLUDE THE TIP OF A CEILING/PADDLE FAN
 BLADE.
 5. REVISE THE ELECTRICAL RISER DIAGRAM TO INCLUDE THE
 INTER-SYSTEM BONDING TERMINAL REQUIRED BY NEC 520.94
 6. IF AHU #1 IN GARAGE 1 IS TO BE INSIDE THE ATTIC OR
 ON A PLATFORM, THE REQUIREMENTS OF NEC 110.33(B) SHALL
 APPLY. THIS MAY ALSO APPLY TO AHU #2 IN GARAGE 2.
 7. FBC-R SECTION 315 STATES THAT YOU SHALL HAVE CARBON
 MONOXIDE (CO) DETECTION WITHIN 10? OF EVERY SLEEPING
 AREA. THEREFORE, THOSE DETECTORS OUTSIDE THE BEDROOM
 USED TO COMPLY W/FBC-R 314 SHALL BE COMBINATION TYPE
 DETECTORS.
 8. NEC 210.52(E)(1) REQUIRES THAT THERE BE A GFCI
 PROTECTED RECEPTACLE INSTALLED AT THE FRONT & BACK OF
 THE RESIDENCE.
 9. NEC 406.8 REQUIRES THAT ALL RECEPTACLES INSTALLED IN
 WET LOCATIONS NOT ONLY HAVE AN IN-USE TYPE COVE BUT
 ALSO BE LISTED AS WEATHER RESISTANT ?WR?.
 10. FBC-ENERGY CONSERVATION REQUIRES THAT AT LEAST 50%
 OF ALL LAMPS IN PERMANENTLY INSTALLED FIXTURES BE
 HIGH-EFFICIENCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 18:01 Rev Time 0.00
Received By jgomez Date 2015-08-24 Time 13:23 Sent To  
Notes
2015-08-24 13:23:19RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-08-12 Cont ID  
Sent By jgomez Date 2015-08-12 Time 16:26 Rev Time 0.00
Received By jgomez Date 2015-08-12 Time 16:24 Sent To  
Notes
2015-08-12 16:26:29RECEIVED E-MAIL FROM GARY STOFFT (ARCHITECT). SEE
 BELOW:
  
 JULIO,
  
 I WANT TO APOLOGIZE AS I AM NOT SURE WHAT IS HAPPENING
 BUT IT SEEMS YOU AREN?T GETTING THE CORRECTION INFO I
 HAVE PROVIDED ON THIS JOB.
  
 ATTACHED IS MY 2ND RESPONSE LETTER TO YOU FOR THE
 COMMENTS FROM 7/22/15.
  
 ALSO ANY SHEETS THAT WERE REVISED AND CLOUDED REGARDING
 YOUR COMMENTS BELOW
  
 ?
  
 MY RESPONSES TO YOUR COMMENTS ARE IN GREEN BELOW
  
 ?
  
 1-??? PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 FOR THE DRAINAGE PLAN I ADDED THE ROOF GUTTER/DRAINAGE
 NOTE TO SHEET A201 (SEE ATTACHED SHEET A201)
  
 THIS IS WHAT I HAVE DONE ON OTHER IBIS JOBS FOR SHELLEY
 FRIEFELD (SOUTHERN HOMES)
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE
 INFORMATION AS REQUIRED BY SEC. 1803.6 FBC-2010.
  
 MARK FROM DELCREST IS TRYING TO GET THE SOIL TEST INFO
 CORRECTED.
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC.
 107.2.1.2 CITY AMENDMENTS. SPECIFY TYPE AND NUMBER OF
 NAILS OR SCREWS.
  
 WE CHANGED TO NAIL DOWN ROOF ON 1ST COMMENTS AND I HAD
 ADDED THE NOTE TO ATTACH PER ROOFING PERMIT.
  
 I HAVE ADDED THE NAILING SPECIFIED BY THE ROOFING
 PERMIT (SEE ATTACHED SHEET A901)
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND
 ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
  
 MAHOGANY DOOR WAS CHANGED TO PGT FD-750 OUTSWING DOOR &
 SIDELIGHTS ON 1ST COMMENTS (SEE ATTACHED SHEET A202)
  
 I REVIEWED & APPROVED THE NOA FOR THIS WITH ALL THE
 OTHER SUBMITTED NOA?S.
  
 B) ROOF TILE ADHESIVE AS SPECIFIED ON DETAIL D1 ON
 SHEET A801.
  
 ROOF CHANGED TO NAIL DOWN TILE ON 1ST COMMENTS
  
 C) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.
  
 PEEL & STICK WAS ELIMINATED ON THE 1ST COMMENTS
  
  
 ?
  
 ?????????????GARY STOFFT
  
  
  
 ????????????????? 42?? N? SWINTON AVENUE
  
 ????????????????? DELRAY??? BCH FL???? 33444
 ????????????????? OFFICE? 561-243-0799 EXT?108
 ????????????????? FAX??????????????????? 561-243-0299
  
 ?
  
 DELRAY BEACH - NAPLES ? CARIBBEAN
  
  
 CONFIDENTIALITY NOTICE: THIS EMAIL MESSAGE, INCLUDING
 ANY AND ALL ATTACHMENTS, IS FOR THE SOLE USE OF THE
 INTENDED RECIPIENTS AND MAY CONTAIN CONFIDENTIAL,
 COPYRIGHTED AND PRIVILEGED INFORMATION. ANY
 UNAUTHORIZED REVIEW, USE, DISCLOSURE AND OR
 DISTRIBUTION IS PROHIBITED. WRITTEN PERMISSION FROM THE
 SENDER IS REQUIRED PRIOR FORWARDING THIS MESSAGE TO
 ANYONE NOT REFERENCED TO AS EITHER THE RECIPIENT OR A
 COPIED ENTITY.? IF YOU ARE NOT THE INTENDED RECIPIENT,
 PLEASE CONTACT THE SENDER BY EMAIL AND IMMEDIATELY
 DELETE ALL COPIES OF THE ORIGINAL AND COPIED MESSAGE.
  
 ?
  
 DISCLAIMER:?DOWNLOADING FROM THE ABOVE SITE OR USING
 THE FILES IN ANY MANNER INDICATES YOUR ACCEPTANCE OF
 TERMS AND CONDITIONS AS SET FORTH BELOW. IF YOU DO NOT
 AGREE TO ALL OF THE TERMS AND CONDITIONS, PLEASE
 CONTACT OUR OFFICE PRIOR TO ANY DOWNLOADING OF THE
 REFERENCED INFORMATION. PLEASE BE ADVISED THAT THE
 ATTACHED FILES ARE IN A FORMAT THAT CAN BE ALTERED BY
 THE USER. DUE TO THIS FACT, ANY REUSE OF THE DATA WILL
 BE AT THE USER'S SOLE RISK WITHOUT LIABILITY OR LEGAL
 EXPOSURE TO RANDALL STOFFT ARCHITECTS AND USER SHALL
 INDEMNIFY AND HOLD HARMLESS RANDALL STOFFT ARCHITECTS
 FROM ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES INCLUDING
 ATTORNEY'S FEES ARISING OUT OF OR RESULTING FROM USING
 THE DIGITAL FILE. IN ADDITION, IT IS THE RESPONSIBILITY
 OF THE USER TO COMPARE ALL DATA WITH THE SIGNED AND
 SEALED DRAWING(S). IN THE EVENT THERE IS A CONFLICT
 BETWEEN THE SIGNED AND SEALED DRAWING(S) AND THE
 ELECTRONIC FILE, THE SIGNED AND SEALED DRAWING(S) SHALL
 PREVAIL.
  
 ? - LOT 15 BP BLDG COMMENTS 02.PDF - 1501021 LOT 15 BP
 A201 FL REV02.PDF - 1501021 LOT 15 BP A202 FL REV01.PDF

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-10 Time 12:47 Rev Time 0.00
Received By jgomez Date 2015-08-04 Time 09:09 Sent To  
Notes
2015-08-04 09:09:49RE-SUBMITTAL SENT TO JULIO GOMEZ FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-29 Cont ID  
Sent By ccole Date 2015-07-29 Time 13:34 Rev Time 0.00
Received By ccole Date 2015-07-28 Time 09:55 Sent To  
Notes
2015-07-29 09:55:37CCOLE DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-27 Cont ID  
Sent By albarran Date 2015-07-27 Time 17:08 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 16:35 Sent To  
Notes
2015-07-27 17:15:337/27/15 - PASSED ELECTRICAL BUT FAILED OTHER TRADES.
 CONTRACTOR NOTIFIED VIA VOICE MAIL. SENT TO LARGE
 DENIED BIN "D". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-02 Cont ID  
Sent By albarran Date 2015-07-02 Time 10:38 Rev Time 0.00
Received By albarran Date 2015-05-12 Time 10:52 Sent To  
Notes
2015-07-02 10:40:37CONTRACTOR NOTIFIED OF FAILED REVIEWS VIA EMAIL. SENT
 TO LARGE DENIED BIN "D".
2015-05-13 10:53:19SENT TO R26 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-09-01 Cont ID  
Sent By skennedy Date 2015-09-01 Time 09:50 Rev Time 0.00
Received By skennedy Date 2015-09-01 Time 09:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 18:03 Rev Time 0.00
Received By jgomez Date 2015-08-31 Time 18:03 Sent To  
Notes
2015-08-31 18:05:021- NEED COPY OF THE IMPACT FEES PAID RECEIPT. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-07-22 Cont ID  
Sent By jgomez Date 2015-07-22 Time 11:21 Rev Time 0.00
Received By jgomez Date 2015-07-22 Time 11:21 Sent To  
Notes
2015-07-22 11:21:221- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By jgomez Date 2015-06-29 Time 07:59 Rev Time 0.00
Received By jgomez Date 2015-06-29 Time 07:59 Sent To  
Notes
2015-06-29 08:24:341- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-29 Cont ID  
Sent By ccole Date 2015-07-29 Time 13:34 Rev Time 0.00
Received By ccole Date 2015-07-29 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-27 Cont ID  
Sent By ccole Date 2015-07-27 Time 11:45 Rev Time 0.00
Received By ccole Date 2015-07-27 Time 11:44 Sent To  
Notes
2015-07-27 12:02:382ND REVIEW: FBC 2010 MECHANICAL
 7/27/15
  
 1) THE CORRECTED AC PLAN IS INCOMPLETE- SHOW THE DUCT
 RUNS AND DUCT SIZES FOR THE SUPPLY REGISTERS AT THE
 MASTER BEDROOM, MASTER BATH, MASTER WALK-IN CLOSETS,
 BATH-2, BEDROOM-2 WALK-IN CLOSET, POWDER ROOM, STORAGE
 ROOM, AND WALK-IN CLOSET-3. SHOW THE MASTER BEDROOM
 TRANSFER RETURN DUCT AND SIZE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By ccole Date 2015-06-30 Time 12:39 Rev Time 0.00
Received By ccole Date 2015-06-30 Time 12:39 Sent To  
Notes
2015-06-30 12:59:441ST REVIEW: FBC 2010 RESIDENTIAL
  
 1) PROVIDE A MEANS OF RETURN AIR FROM THE MASTER
 BEDROOM- SECTION M1602.4 FBC-10 RESIDENTIAL.
 2) INDICATE THE DIMENSIONS OF THE RETURN GRILLS IN
 BEDROOMS 2 & 3, AND THE LIBRARY- M1602.4.
 3) INDICATE THE DIMENSIONS OF THE RETURN AIR PLENUM
 DUCTS, AND PLACE A NOTE THAT NO FLEX DUCTS ARE
 PERMITTED TO BE INSTALLED IN THE GARAGE PER SECTION
 R302.5.2.
 4) PROVIDE CONDENSATE DISPOSAL DETAILS- M1411.3 &
 M1411.3.1.
 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PADS, AND TIE-DOWN ENGINEERING FOR THE
 CONDENSERS- M1307.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 11:49 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 10:37 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2015-08-31 Cont ID  
Sent By jgomez Date 2015-08-31 Time 18:06 Rev Time 0.00
Received By jgomez Date 2015-08-31 Time 18:06 Sent To  
Notes
2015-08-31 18:07:05ROOF TILE NOA 14-1120.04.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-10 Time 16:47 Rev Time 0.00
Received By jgomez Date 2015-08-10 Time 16:47 Sent To  
Notes
2015-08-10 16:48:08 
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-07-22 Cont ID  
Sent By jgomez Date 2015-07-22 Time 15:47 Rev Time 0.00
Received By jgomez Date 2015-07-22 Time 15:47 Sent To  
Notes
2015-07-22 15:48:351 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF TILE.
  
 B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE.
  
 C) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By jgomez Date 2015-06-29 Time 16:27 Rev Time 0.00
Received By jgomez Date 2015-06-29 Time 12:27 Sent To  
Notes
2015-06-29 16:28:371 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF TILE.
  
 B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE.
  
 C) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By dkittred Date 2015-06-17 Time 10:37 Rev Time 0.00
Received By dkittred Date 2015-06-17 Time 10:36 Sent To  
Notes
2015-06-17 10:37:426/17/15 - REQUIRED LANDSCAPE PLAN SUBMITTED 6/16/15 FOR
 REVIEW (15060679). DK

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-19 Cont ID  
Sent By dkittred Date 2015-05-19 Time 16:04 Rev Time 0.00
Received By dkittred Date 2015-05-19 Time 15:07 Sent To  
Notes
2015-06-02 13:19:536/2/15 - APPLICANT SUBMITTED MISSING SURVEYS 6/1/15.
 COMMENT #1 BELOW HAS BEEN BEEN MET. DK
  
2015-05-19 15:57:55PLANNING AND ZONING COMMENTS: ***FAILED***
  
 5/19/2015
  
 ITEMS TO BE ADDRESSED:
  
 1. THERE WAS NO PROPERTY SURVEY INCLUDED IN THE
 SUBMITTAL. PLEASE SUBMIT TWO COPIES OF THE PROPERTY
 SURVEY.
  
 2. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF. PLEASE ADJUST
 CALCULATIONS TABLE.)
  
 GENERAL COMMENTS:
  
 3. SEPARATE PERMITS ARE REQUIRED FOR THE POOL AND
 DRIVEWAY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  