Plan Review Details - Permit 15050391
Plan Review Stops For Permit 15050391
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-05 Cont ID  
Sent By jgomez Date 2015-06-05 Time 14:07 Rev Time 0.00
Received By jgomez Date 2015-06-05 Time 14:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-03 Cont ID  
Sent By jgomez Date 2015-06-03 Time 12:07 Rev Time 0.00
Received By jgomez Date 2015-06-03 Time 12:07 Sent To  
Notes
2015-06-03 12:10:20RESIDENTIAL (R2) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE TWO COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF 2010 FBC_BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 ***INFORMATION SUBMITTED IS NOT A COPY OF THE TEST.
 IT'S THE SAME INFORMATION THAT WAS SUBMITTED
 ORIGINALLY. THE TECHNICAL DATA TABLE SUBMITTED SHOWS
 IMPACT INSULATION CLASS (IIC) OF 68 AND SOUND
 TRANSMISSION CLASS (STC) OF 72. FOOTNOTE BELOW TABLE
 STATES THAT THE TEST WAS CONDUCTED ON 8" CONCRETE SLAB
 WITH ACOUTIC CEILING. THIS TYPE OF ASSEMBLY DOESN'T
 MATCH ACTUAL TYPE OF ASSEMBLY ON THIS BUILDING. THIS
 BUILDING HAS A 7" CONCRETE SLAB AND THERE IS NOT
 ACOUSTICAL CEILING ASSEMBLY.
  
 C) PROVIDE TWO COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF 2010 FBC-BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 ***INFORMATION SUBMITTED IS NOT A COPY OF THE TEST.
 IT'S THE SAME INFORMATION THAT WAS SUBMITTED
 ORIGINALLY. THE TECHNICAL DATA TABLE SUBMITTED SHOWS
 IMPACT INSULATION CLASS (IIC) OF 68 AND SOUND
 TRANSMISSION CLASS (STC) OF 72. FOOTNOTE BELOW TABLE
 STATES THAT THE TEST WAS CONDUCTED ON 8" CONCRETE SLAB
 WITH ACOUTIC CEILING. THIS TYPE OF ASSEMBLY DOESN'T
 MATCH ACTUAL TYPE OF ASSEMBLY ON THIS BUILDING. THIS
 BUILDING HAS A 7" CONCRETE SLAB AND THERE IS NOT
 ACOUSTICAL CEILING ASSEMBLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-13 Cont ID  
Sent By jgomez Date 2015-05-13 Time 14:32 Rev Time 0.00
Received By jgomez Date 2015-05-13 Time 14:31 Sent To  
Notes
2015-05-13 14:48:20RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM
 E 84 OR UL 723 AS REQUIRED BY SEC. 719.1 OF 2010
 FBC-BUILDING.
  
 B) PROVIDE TWO COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF 2010 FBC_BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE TWO COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF 2010 FBC_BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-05 Cont ID  
Sent By jgomez Date 2015-06-05 Time 14:26 Rev Time 0.00
Received By jgomez Date 2015-06-04 Time 14:52 Sent To  
Notes
2015-06-04 14:53:20RE-SUBMITTAL SENT TO JULIO GOMEZ FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-03 Cont ID  
Sent By jgomez Date 2015-06-03 Time 12:07 Rev Time 0.00
Received By jgomez Date 2015-06-02 Time 17:17 Sent To  
Notes
2015-06-02 17:17:22TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-13 Cont ID  
Sent By jgomez Date 2015-05-13 Time 14:31 Rev Time 0.00
Received By jgomez Date 2015-05-13 Time 14:31 Sent To  
Notes
***NONE***