| 2015-05-12 05:20:38 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED |
| | PER FBC- FUEL GAS SEC.301.3. |
| | 2) IS THE WATER HEATER A STORAGE TANK OR TANKLESS? |
| | INDICATE SUCH ON THE GAS RISER. IF TANKLESS, A SEPARATE |
| | ELECTRIC PERMIT WILL BE REQUIRED AND GAS/PLUMBING |
| | INSPECTIONS WILL BE PLACED ON HOLD UNTIL AN ELECTRIC |
| | PERMIT APPLICATION AND PLANS ARE SUBMITTED, REVIEWED, |
| | APPROVED AND A PERMIT ISSUED. |
| | 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE |
| | WITH 2010 FBC-FUEL GAS SEC.304.1. |
| | 4) SUBMIT VENT DETAILS FOR ALL APPLIANCES.2010 FBC-FUEL |
| | GAS SEC.501.2, 502.1, 503.1. |
| | 5) THE TABLE YOU SUBMITTED FOR THE CSST NOTES A |
| | PRESSURE DROP OF 3.0 IN. WATER COLUMN. THERE IS NO |
| | CORRESPONDING TABLE FOR THIS PRESSURE DROP FOR METALLIC |
| | (GALV.) PIPE. PLEASE CONFIRM THAT THIS IS THE CORRECT |
| | TABLE AND SUBMIT COPY OF SIZING TABLE FOR THE METALLIC |
| | PIPE. |
| | 6) IF THE TABLE FOR THE METALLIC PIPE IS 402.4 (2), THE |
| | MAX.BTU LOAD FOR 3/4" PIPE AT 80 FEET IS 117,000. THE |
| | MIN. PIPE SIZE AT THE METER WILL HAVE TO BE 1". |
| | 7) SIZE THE BRANCH LINE TO THE WATER HEATER. WPB AMEND. |
| | TO 2010 FBC SEC. 107.3.5.3. |
| | 8) SIZE THE LINE AT THE METER. WPB AMEND. TO 2010 FBC |
| | SEC. 107.3.5.3. |
| | 9) THE DRAWING SHOWS THE EHD FOR THE CSST CHANGING FROM |
| | 23 TO 25 . IS THIS CORRECT? CLARIFY. |
| | |