Plan Review Details - Permit 15050362
Plan Review Stops For Permit 15050362
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2015-06-08 Time 09:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By jwitmer Date 2015-05-26 Time 16:53 Rev Time  
Received By jwitmer Date 2015-05-26 Time   Sent To  
Notes
2015-05-26 16:53:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050362
 ADD: 1641 WORTHINGTON RD. SUITE # 100
 CONT: DPR CONSTRUCTION
 TEL: ( 561)951-0524
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 26/2015
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE NEWLY FORMED TENANT
 SPACE TO BE 1035 SQ. FT. TENANT SPACE SUITE 100. THE
 PLANS DO NOT IDENTIFY IF THE NEW TENANT SPACE IS THE
 VANILLA BOX BEING FORMED OR THE TENANT TO THE RIGHT OF
 THE NEWLY FORMED 1 HOUR TENANT SEPARATION WALL. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) THE COVERSHEET INDICATES A TENANT SPACE OF 1035 SQ.
 FT./ 100= 11 YOU ROUND UP, THERE ARE NO PARTS OF
 OCCUPANTS, 2010 FBC-B TABLE 1004.1.1.
  
 3) SHEET A1.0. THE ROOM/ SUITE WITH THE NEW FIRE RATED
 DOOR TO THE CORRIDOR IS TO BE CONSIDERED FOR THIS
 REVIEW THE NEW TENANT SPACE. THE NEW WALL TO THE RIGHT
 IS SHOWN AS A 1 HOUR FIRE RATED WALL. THE WALL TO THE
 LEFT SIDE IS INDICATED TO STOP 6 INCHES ABOVE THE
 CEILING LINE? THE 2010 FBC-B 709.6 TENANT SEPERATION
 WALLS EXCEPTION # 1 ALLOWS FOR A SUITE OF OFFICES AND
 NO TENANT SEPARATION WALLS WOULD NEED TO BE RATED
 WITHIN THE 3,000 SQ. FT AREA. EXCEPTION # 4 ALLOWS FOR
 FULLY SPRINKLERED BUILDINGSW TH A BUSINESS OCCUPANCY
 THE TENANT SEPARATION WALLS WOULD NOT NEED TO BE FIRE
 RATED.
  
 4) SHEET A1.0 DETAIL # 5 INDICATES THIS BUILDING HAS A
 RAISED FLOOR SYSTEM WHERE THE DUCTWORK IS RUN BENEATH
 THE FLOOR WITH THE TENANT SEPARATION WALLS HAVING
 DAMPERS AS WELL AS THE PLENUM RETURNS. THE PLANS DO NOT
 MENTION THE 1 HOUR FIRE RATING CONTINUING BENEATH THE
 RAISED FLOOR SYSTEM? 2010 FBC-B 709.4. CONTINUITY.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By pleduc Date 2015-05-15 Time   Rev Time 0.00
Received By pleduc Date 2015-05-15 Time 16:42 Sent To  
Notes
2015-05-15 16:50:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED PROJECT CREATESA NEW OCCUPANCY. THE WALLS
 SEPARATING THE OCCUPACIES SHALL BE 1 HOUR FIRE RATED.
 ONLY ONE OF THE SIDE OCCUPANCY WALSS SHOWS THE RATING,
 THE OTHER SHOWS ONLY AN INTERIOR PARTITION. THIS
 PARTITION WALL IS REQUIRED TO BE 1 HOUR FIRE RATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2015-05-28 Time 17:47 Sent To  
Notes
2015-05-28 17:48:23B37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-26 Cont ID  
Sent By jwitmer Date 2015-05-26 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2015-05-12 Time 09:15 Sent To  
Notes
2015-05-13 09:15:47SENT TO B2 SHELF FOR REVIEW. JG.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved