| 2015-05-26 16:53:16 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050362 |
| | ADD: 1641 WORTHINGTON RD. SUITE # 100 |
| | CONT: DPR CONSTRUCTION |
| | TEL: ( 561)951-0524 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 26/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET INDICATES THE NEWLY FORMED TENANT |
| | SPACE TO BE 1035 SQ. FT. TENANT SPACE SUITE 100. THE |
| | PLANS DO NOT IDENTIFY IF THE NEW TENANT SPACE IS THE |
| | VANILLA BOX BEING FORMED OR THE TENANT TO THE RIGHT OF |
| | THE NEWLY FORMED 1 HOUR TENANT SEPARATION WALL. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2) THE COVERSHEET INDICATES A TENANT SPACE OF 1035 SQ. |
| | FT./ 100= 11 YOU ROUND UP, THERE ARE NO PARTS OF |
| | OCCUPANTS, 2010 FBC-B TABLE 1004.1.1. |
| | |
| | 3) SHEET A1.0. THE ROOM/ SUITE WITH THE NEW FIRE RATED |
| | DOOR TO THE CORRIDOR IS TO BE CONSIDERED FOR THIS |
| | REVIEW THE NEW TENANT SPACE. THE NEW WALL TO THE RIGHT |
| | IS SHOWN AS A 1 HOUR FIRE RATED WALL. THE WALL TO THE |
| | LEFT SIDE IS INDICATED TO STOP 6 INCHES ABOVE THE |
| | CEILING LINE? THE 2010 FBC-B 709.6 TENANT SEPERATION |
| | WALLS EXCEPTION # 1 ALLOWS FOR A SUITE OF OFFICES AND |
| | NO TENANT SEPARATION WALLS WOULD NEED TO BE RATED |
| | WITHIN THE 3,000 SQ. FT AREA. EXCEPTION # 4 ALLOWS FOR |
| | FULLY SPRINKLERED BUILDINGSW TH A BUSINESS OCCUPANCY |
| | THE TENANT SEPARATION WALLS WOULD NOT NEED TO BE FIRE |
| | RATED. |
| | |
| | 4) SHEET A1.0 DETAIL # 5 INDICATES THIS BUILDING HAS A |
| | RAISED FLOOR SYSTEM WHERE THE DUCTWORK IS RUN BENEATH |
| | THE FLOOR WITH THE TENANT SEPARATION WALLS HAVING |
| | DAMPERS AS WELL AS THE PLENUM RETURNS. THE PLANS DO NOT |
| | MENTION THE 1 HOUR FIRE RATING CONTINUING BENEATH THE |
| | RAISED FLOOR SYSTEM? 2010 FBC-B 709.4. CONTINUITY. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |