Plan Review Details - Permit 15050330
Plan Review Stops For Permit 15050330
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By skennedy Date 2015-06-24 Time 11:19 Rev Time 0.00
Received By skennedy Date 2015-06-24 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By skennedy Date 2015-05-18 Time 16:23 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-05-18 16:23:191ST REVIEW: FBC 2010
  
 MET WITH RAINER GEBAUER, HUSBAND OF OWNER, HE INDICATED
 THE DRAWING DOES NOT DEPICT THE ACTUAL SCOPE OF WOTK SO
 HE WILL RESUBMIT AN ACCURATE DRAWING AT A LATER DATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By dhayes Date 2015-06-17 Time 14:00 Rev Time 0.00
Received By dhayes Date 2015-06-17 Time 13:22 Sent To  
Notes
2015-06-17 14:14:576/17/2015
 PROJECT: KITCHEN RENNOVATION
 PERMIT#: 15050330
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INSTAL SMOKE DETECTORS WHERE REQUIRED. SEE FBC-R
 314-315 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL.
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS.
  
 4) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
  
 5) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER
  
 6) FBC-E 708.3 RESIDENTIAL OCCUPANCIES.
 IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7
 SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A
 DWELLING UNIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By rlecky Date 2015-05-14 Time 14:57 Rev Time 0.00
Received By rlecky Date 2015-05-14 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By pleduc Date 2015-06-22 Time   Rev Time 0.00
Received By pleduc Date 2015-06-22 Time 14:49 Sent To  
Notes
2015-06-22 14:54:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
  
 EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER, SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-13 Cont ID  
Sent By pleduc Date 2015-05-13 Time   Rev Time 0.00
Received By pleduc Date 2015-05-13 Time 13:00 Sent To  
Notes
2015-05-13 13:11:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE.
  
 EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER, SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-24 Cont ID  
Sent By skennedy Date 2015-06-24 Time 11:19 Rev Time 0.00
Received By skennedy Date 2015-06-15 Time   Sent To  
Notes
2015-06-17 14:15:28B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-18 Cont ID  
Sent By skennedy Date 2015-05-18 Time 16:23 Rev Time  
Received By skennedy Date 2015-05-11 Time   Sent To  
Notes
2015-05-12 09:22:36SENT TO B-26.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-05-18 Cont ID  
Sent By skennedy Date 2015-05-18 Time 16:20 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-05-18 16:22:281ST REVIEW: FBC 2010
  
 MET WITH RAINER GEBAUER, HUSBAND OF OWNER, HE INDICATED
 THE DRAWING DOES NOT DEPICT THE ACTUAL SCOPE OF WOTK SO
 HE WILL RESUBMIT AN ACCURATE DRAWING AT A LATER DATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-18 Cont ID  
Sent By skennedy Date 2015-05-18 Time 16:22 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-05-18 16:22:541ST REVIEW: FBC 2010
  
 MET WITH RAINER GEBAUER, HUSBAND OF OWNER, HE INDICATED
 THE DRAWING DOES NOT DEPICT THE ACTUAL SCOPE OF WOTK SO
 HE WILL RESUBMIT AN ACCURATE DRAWING AT A LATER DATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  