Plan Review Details - Permit 15050328
Plan Review Stops For Permit 15050328
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-05-21 Cont ID  
Sent By jwitmer Date 2015-05-21 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2015-05-21 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-02 Cont ID  
Sent By rlecky Date 2015-06-02 Time 13:36 Rev Time 0.00
Received By rlecky Date 2015-06-02 Time 13:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-18 Cont ID  
Sent By scaldero Date 2015-05-18 Time 13:51 Rev Time 0.00
Received By scaldero Date 2015-05-18 Time 13:47 Sent To  
Notes
2015-05-18 13:49:03PERMIT #15050328
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-19 Cont ID  
Sent By lmarchan Date 2015-06-19 Time 13:50 Rev Time 0.00
Received By lmarchan Date 2015-06-17 Time   Sent To  
Notes
2015-06-18 10:06:22SENT TO E SCHNEIDER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-15 Cont ID  
Sent By   Date 2015-06-15 Time   Rev Time  
Received By   Date 2015-05-11 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-06-15 Cont ID  
Sent By ccole Date 2015-06-15 Time 12:00 Rev Time 0.00
Received By ccole Date 2015-06-15 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 14:39 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 10:32 Sent To  
Notes
2015-06-11 14:39:55NO CHANGES TO EXISTING PLUMBING SYSTEM.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By eschneid Date 2015-06-19 Time 10:00 Rev Time 0.25
Received By eschneid Date 2015-06-19 Time 09:59 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By eschneid Date 2015-05-26 Time 16:32 Rev Time 0.25
Received By eschneid Date 2015-05-26 Time 16:32 Sent To  
Notes
2015-05-26 16:37:38FAILED
  
 1) PALM BEACH OUTLETS MANAGEMENT APPROVAL STAMP NOT
 INCLUDED ON PLANS.
  
 2) PLANS THEMSELVES MEET ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.