Plan Review Details - Permit 15050292
Plan Review Stops For Permit 15050292
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time   Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 08:00 Sent To  
Notes
2016-03-10 10:16:21THE BRISTOL
 BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561)832-1616
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 4TH REVIEW
 DATE: THURS. MARCH 10/2016
 ACTION: BUILDING PROVISO
  
 NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION ONLY,
 PLEASE PROVIDE AN APPENDIX TO THE PERMIT APPLICATION,
 DESCRIPTION OF WORK, AS TO WHAT WORK IS TO BE
 ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY
 CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED
 UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDERS OWN RISK WITH
 THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT A
 PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 1) PROVISO: FBC-B 3306.9 ADJACENT TO EXCAVATIONS. EVERY
 EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS
 FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
  
 2) PROVISO: PERIMETER FENCING UNDER A SEPARATE PERMIT.
 PLEASE PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 3) PROVISO: 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 FBC-B 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 4) PROVISO: [F] 3311.1 WHERE REQUIRED. IN BUILDINGS
 REQUIRED TO HAVE STANDPIPES BY SECTION 905.3.1, NOT
 LESS THAN ONE STANDPIPE SHALL BE PROVIDED FOR USE
 DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED
 WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40
 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 5) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) IMPACT FEES: PALM BEACH COUNTY IMPACT FEE OFFICE
 DEFERRED UNTIL THE ISSUANCE OF THE BUILDING PERMIT.
 E-MAIL DATED 11/13/2015 WILLIE SWOOPE TO: FLORIAN
 HUTTL.
  
 7) PROVISO: UNDER A SEPARATE PERMIT. ALL CONSTRUCTION
 TRAILERS (MOBILE OR MODULAR BUILDINGS) THAT ARE GOING
 TO HAVE MEETING IN THEM WILL BE REQUIRED TO GET A
 PERMIT, 102.2( E ) MOBILE OR MODULAR STRUCTURES USED AS
 TEMPORARY OFFICES, EXCEPT THAT THE PROVISIONS OF PART V
 (SECTION 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 8) PROVISO: UNDER A SEPARATE PERMIT. DEPENDING ON THE
 SIZE OF THE CONSTRUCTION TRAILERS, CLOSENESS TO
 BUILDINGS AND OR OTHER CONSTRUCTION TRAILERS THE FIRE
 DEPARTMENT THROUGH THE FIRE PREVENTION CODE MAY REQUIRE
 FIRE SPRINKLERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-01-26 Cont ID  
Sent By jwitmer Date 2016-01-26 Time 17:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-01-26 17:58:24THE BRISTOL
 BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561)832-1616
 E-MAIL: [email protected]
  
  
  
 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 4TH REVIEW / 1ST REVIEW AS A POSSIBLE MIXED USE
 BUILDING.
 DATE: TUES. JAN. 26/2016
 ACTION: DENIED
  
 1) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY
 CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED
 UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 2) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) 4TH REQUEST. A FLOOD ZONE CERTIFICATE IS REQUIRED AS
 PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT. ON THE SUBMITTED FLOOD ZONE
 CERTIFICATE THE LINE ITEM FOR ATTACHED GARAGE WAS
 MARKED N/A. THERE IS 2 STORIES OF PARKING
  
 4) IN GOING TO THE 2010 FBC-B SECTION 1612.4 THE DESIGN
 AND CONSTRUCTION OF BUILDINGS LOCATED IN THE FLOOD
 HAZARD AREAS THE DESIGN SHALL BE IN ACCORDANCE WITH
 ASCE 24. BEFORE GOING TO THE ASCE 24 I HAD REVIEWED THE
 SUBMITTED COASTAL A ZONE REPORT AND THE WAVE HEIGHT
 ANALYSIS FOR FLOOD INSURANCE STUDIES V4.0 (WHAFIS). I
 CONCUR THAT THE PROPERTY IS NOT LOCATED IN A COASTAL A5
 ZONE BUT AN A5 FLOOD ZONE. COASTAL A ZONE.
  
 5) IN REVIEWING ASCE 24 SECTION 6.2.1 DRY FLOOD
 PROOFING LIMITATIONS STATES THAT IN NONRESIDENTIAL
 AREAS OF MIXED USE STRUCTURES SHALL NOT BE ALLOWED
 UNLESS SUCH STRUCTURES ARE LOCATED OUTSIDE OF THE HIGH
 RISK FLOOD HAZARD AREAS, COASTAL HIGH HAZARD AREAS, AND
 COASTAL A ZONES. THE WHAFIS STUDY DOES TAKE THE
 BUILDING OUT OF THE COASTAL A ZONE TO AN A5 FLOOD ZONE.
 TO CONSIDER THIS BUILDING A MIXED USE BUILDING, THERE
 ARE AREAS OF THE BUILDING THAT NEED TO BE REVIEWED TO
 DETERMINE IF THE BUILDING QUALIFIES AS A MIXED USE.
  
 5A) SHEET 080-A2-01 OF THE MASTER BUILDING PERMIT
 INDICATES AN AREA ROOM 103 RESIDENTS CLUB DINING.
 APPROXIMATELY 480 SQUARE FEET WITH AN OCCUPANT LOAD OF
 32 PEOPLE. THERE ARE 2 ISSUES TO CONSIDER, THE PLANS DO
 NOT SHOW ANY COOKING EQUIPMENT JUST A 2 COMPARTMENT
 SINK IN THE PANTRY AREA, ROOM 109.
 FOR THE USE OF THE DINING FACILITIES PLEASE PROVIDE HOW
 PAYMENT WILL BE MADE FOR THE USE OF TENANT SPACE AND
 SERVICES RENDERED. TO CONSIDER THIS SPACE AS A DELI,
 SMALL RESTAURANT (2010 FBC-B 309.1 RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD LESS THAN
 50 PERSONS) AND NOT JUST AN AMENITY THE BUILDING
 OFFICIAL WILL NEED DOCUMENTATION TO SHOW THIS IS A
 MERCANTILE OCCUPANCY WHERE SERVES WERE RENDERED AND
 PAYMENT MADE.
  
 5B) SHEET 080-A2-01 OF THE MASTER BUILDING PERMIT
 INDICATES ROOM # 143 TO BE A MANICURE AND HAIR DRESSING
 SHOP OR A BEAUTY PARLOR 2010 FBC-B 304.1. THIS COULD BE
 CONSIDERED A BUSINESS OCCUPANCY .
 TO CONSIDER THIS SPACE AS A BEAUTY PARLOR AND NOT JUST
 AN AMENITY THE BUILDING OFFICIAL WILL NEED
 DOCUMENTATION TO SHOW HOW PAYMENT FOR SERVICES
 RENDERED.
  
 6) ASCE 24-05 6.2.1 DRY FLOOD PROOFING LIMITATIONS. DRY
 FLOOD PROOFING OF RESIDENTIAL AREAS OF MIXED USE
 STRUCTURES SHALL NOT BE PERMITTED.
 TECHNICAL BULLETIN 6-93, AND TECHNICAL BULLETIN 3-93.
  
 7) PLEASE PROVIDE COMPLIANCE WITH ASCE 24-05 TABLE 6-1
 THE MINIMUM ELEVATION OF FLOODPROOFING, RELATED TO BASE
 FLOOD ELEVATION (BFE) OR DESIGN FLOOD ELEVATION DFE).
 PLEASE ALSO INCLUDE THE STRUCTURE CATEGORY.
  
 8) PLEASE REVIEW ASCE 24-5 SECTION 6.2.1 DRY FLOOD
 PROOFING LIMITATIONS SHOW COMPLIANCE WITH SECTIONS 1 &
 2.
  
 9) SHOW COMPLIANCE ALSO WITH ASCE 24-5 SECTION 6.2.2
 DRY FLOODPROOFING REQUIREMENTS 1-3.
  
 10) SHOW HOW COMPLIANCE WITH ASCE 24-5 SECTION 6.2.3
 REQUIREMENTS 1-3.
  
 11) NFPA REGULATION 60.3(3) (II) TOGETHER WITH
 ATTENDANT UTILITY AND SANITARY FACILITIES, BE DESIGNED
 SO THAT BELOW THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATERTIGHT WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING
 THE CAPACITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC
 LOADS AND EFFECTS OF BUOYANCY.
  
 12) NFIP 60.3? (4) (I) A REGISTERED PROFESSIONAL
 ENGINEER OF ARCHITECT SHALL DEVELOP AND /OR REVIEW
 STRUCTURAL DESIGN, SPECIFICATIONS, AND PLANS FOR THE
 CONSTRUCTION AND SHALL CERTIFY THAT THE DESIGN AND
 METHODS OF CONSTRUCTION ARE IN ACCORDANCE WITH THE
 ACCEPTED STANDARDS OF PRACTICE FOR MEETING THE
 APPLICABLE PROVISIONS OF PARAGRAPHS (3)(II) OR (8)(II)
 OF THIS SECTION, AND (II) A RECORD OF SUCH CERTIFICATES
 WHICH INCLUDES THE SPECIFIC ELEVATIONS (IN RELATION TO
 MEAN SEA LEVEL) TO WHICH SUCH STRUCTURES ARE FLOOD
 PROOFED SHALL BE MAINTAINED WITH THE OFFICIAL
 DESIGNATED BY THE COMMUNITY?
  
 13) PLEASE REVIEW ALL OF THE REQUIREMENTS WITHIN THE
 FEMA TECHNICAL BULLETIN 3-93 FOR NON-RESIDENTIAL
 FLOODPROOFING-REQUIREMENTS AND CERTIFICATIONS:
 HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1511-20
 490-5294/JOB6.PDF
  
 14) PROVISO: FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
 15) PROVISO: PERIMETER FENCING UNDER A SEPARATE PERMIT.
 PLEASE PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 16) PROVISO: 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 9F) FBC-B 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 17) PROVISO: [F] 3311.1 WHERE REQUIRED. IN BUILDINGS
 REQUIRED TO HAVE STANDPIPES BY SECTION 905.3.1, NOT
 LESS THAN ONE STANDPIPE SHALL BE PROVIDED FOR USE
 DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED
 WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40
 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 18)PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 19) PROVISO: ALL CONSTRUCTION TRAILERS (MOBILE OR
 MODULAR BUILDINGS) THAT ARE GOING TO HAVE MEETING IN
 THEM WILL BE REQUIRED TO GET A PERMIT, 102.2( E )
 MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY OFFICES,
 EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 20)PROVISO: DEPENDING ON THE SIZE OF THE CONSTRUCTION
 TRAILERS, CLOSENESS TO BUILDINGS AND OR OTHER
 CONSTRUCTION TRAILERS THE FIRE DEPARTMENT THROUGH THE
 FIRE PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS.
  
 21)PROVISO: TO DATE THERE HAS BEEN NO PERMIT APPLIED
 FOR, FOR TEST PILING INCOMPLIANCE WITH THE 2010 FBC-B
 1810.3.3.1.2 LOAD TEST.
  
 22) 2ND REQUEST, NO RESPONSE COMMENT. THERE IS A
 QUESTION OF THE BONDING OF THE STEEL RE-ENFORCEMENT FOR
 ELECTRICAL. IS THERE ALSO GOING TO BE ANY LIGHTNING
 BONDING GOING TO BE REQUIRED? PERMIT WILL NEED TO BE
 PULLED FOR THE SCHEDULING OF THESE INSPECTIONS, NO
 DETAILS.
  
 23) IMPACT FEES DEFERRED TO BUILDING PERMIT.
  
 24) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-12-29 Cont ID  
Sent By jwitmer Date 2015-12-29 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2015-12-29 Time   Sent To  
Notes
2015-12-29 11:40:13THE BRISTOL
 BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561)832-1616
 E-MAIL: [email protected]
  
  
  
 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. JAN. 07/2016
 ACTION: DENIED
  
 NOTICE!!!! NO NARRATIVE!!!!!! WHEN OPENING THE BUILDING
 WORKFLOW-REVIEW COMMENTS 11-25-2015 WINDOW THERE IS NO
 COMMENTS AS TO WHERE YOU CAN FIND THE ANSWERS TO THE
 QUESTIONS ASKED. YOU SEE: REVIEW CYCLE DEPARTMENT
 MARKUP SNAPSHOT.
  
  
  
  
  
  
  
 1) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY
 CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED
 UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 2) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) 3RD REQUEST. A FLOOD ZONE CERTIFICATE IS REQUIRED AS
 PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT.
  
 IN GOING TO THE 2010 FBC-B SECTION 1612.4 THE DESIGN
 AND CONSTRUCTION OF BUILDINGS LOCATED IN THE FLOOD
 HAZARD AREAS THE DESIGN SHALL BE IN ACCORDANCE WITH
 ASCE 24. BEFORE GOING TO THE ASCE 24 I HAD REVIEWED THE
 SUBMITTED COASTAL A ZONE REPORT AND CONCUR THAT THE
 PROPERTY IS NOT LOCATED IN A COASTAL A5 ZONE BUT AN A5
 FLOOD ZONE.
  
 IN REVIEWING ASCE 24 SECTION 6.2.1 DRY FLOOD PROOFING
 LIMITATIONS STATES THAT IN NONRESIDENTIAL AREAS OF
 MIXED USE STRUCTURES SHALL NOT BE ALLOWED UNLESS SUCH
 STRUCTURES ARE LOCATED OUTSIDE OF THE HIGH RISK FLOOD
 HAZARD AREAS, COASTAL HIGH HAZARD AREAS, AND COASTAL A
 ZONES.
 DRY FLOOD PROOFING OF RESIDENTIAL AREAS OF MIXED USE
 STRUCTURES SHALL NOT BE PERMITTED.
  
 THE ABOVE REQUIREMENT WE FELT THAT THE DESIGN MET ALL
 OF THESE REQUIREMENTS. THE RESIDENTIAL AREAS WERE ALL
 ABOVE THE BASE FLOOD, WE CONSIDERED THE BUILDING A
 MIXED USE R2 OCCUPANCY ABOVE WITH 2 STORIES OF STORAGE
 OCCUPANCIES THE PARKING WHICH WOULD BE ALLOWED TO BE
 BELOW THE BASE FLOOD WITH DRY FLOOD PROOFING .
  
 ASCE 24 SECTION 6.2.1 DRY FLOOD PROOFING
  
 ASCE 24- 6.0 DRY FLOOD.PDF
  
 THE REAL ISSUE WITH THIS DESIGN IS FEMA'S TECHNICAL
 BULLETIN 6-93. NFIP REGULATIONS
 THE NFIP REGULATIONS PROVIDE DIRECTION CONCERNING
 WHETHER OR NOT BELOW GRADE PARKING IS PERMITTED IN
 SFHAS, BOTH COASTAL AND RIVERINE. FOR THE PURPOSES OF
 THE NFIP, BELOW GRADE PARKING IS CONSIDERED A BASEMENT.
 A BASEMENT IS DEFINED AS ANY AREA OF A BUILDING HAVING
 ITS FLOOR SUBGRADE (BELOW GROUND LEVEL) ON ALL SIDES.
 THE FOLLOWING SUBSECTIONS PROVIDE APPLICABLE EXCERPTS
 FROM THE NFIP REGULATIONS. BELOW-GRADE PARKING GARAGES
 IN RESIDENTIAL BUILDINGS IN A ZONES.
 SECTION 60.3(C)(2) OF THE NFIP REGULATIONS STATES THAT
 A COMMUNITY SHALL: ?REQUIRE THAT ALL NEW CONSTRUCTION
 AND SUBSTANTIAL IMPROVEMENTS OF RESIDENTIAL STRUCTURES
 WITHIN ZONES A1-A30, AE AND AH ON THE COMMUNITY?S FIRM
 HAVE THE LOWEST FLOOR (INCLUDING BASEMENT) ELEVATED TO
 OR ABOVE THE BASE FLOOD LEVEL... ?
  
 UNDER THE NFIP, A BELOW GRADE PARKING GARAGE IS
 CONSIDERED A BASEMENT IF IT IS BELOW GRADE ON ALL
 SIDES. THEREFORE, THE CONSTRUCTION OF BELOW- GRADE
 PARKING GARAGES IS PROHIBITED BENEATH RESIDENTIAL
 BUILDINGS IN ZONES A1-A30, AE, AND AH.
  
 PLEASE SEE THE TECHNICAL BULLETIN 6-93
  
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) COMPLIED> THERE ARE SEVERAL DOCUMENTS THAT HAVE BEEN
 SUBMITTED IN THE SUPPORTING DOCUMENT FILE, NONE OF
 THESE FILES INDICATE THAT THE ARCHITECT OF RECORD HAS
 REVIEWED THEM THERE IS NO SHOP DRAWING STAMP OF
 APPROVAL WITH APPROVAL OR APPROVED AS NOTED.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER
 ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS?
 OFFICE.
 5) COMPLIED> THRESHOLD INSPECTION PLAN FL S. S.
 553.71(7). WRITTEN / TYPED STRUCTURAL THRESHOLD
 INSPECTION PLAN
 5-9) COMPLIED.
 10) PROVISO: FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
 11) PROVISO: PERIMETER FENCING UNDER A SEPARATE PERMIT.
 PLEASE PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
 12) PROVISO: 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 9F) FBC-B 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 13) PROVISO: [F] 3311.1 WHERE REQUIRED. IN BUILDINGS
 REQUIRED TO HAVE STANDPIPES BY SECTION 905.3.1, NOT
 LESS THAN ONE STANDPIPE SHALL BE PROVIDED FOR USE
 DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED
 WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40
 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
 14)PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 15) PROVISO: ALL CONSTRUCTION TRAILERS (MOBILE OR
 MODULAR BUILDINGS) THAT ARE GOING TO HAVE MEETING IN
 THEM WILL BE REQUIRED TO GET A PERMIT, 102.2( E )
 MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY OFFICES,
 EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 16)PROVISO: DEPENDING ON THE SIZE OF THE CONSTRUCTION
 TRAILERS, CLOSENESS TO BUILDINGS AND OR OTHER
 CONSTRUCTION TRAILERS THE FIRE DEPARTMENT THROUGH THE
 FIRE PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS.
  
 17) COMPLIED.
  
 18)PROVISO: TO DATE THERE HAS BEEN NO PERMIT APPLIED
 FOR, FOR TEST PILING INCOMPLIANCE WITH THE 2010 FBC-B
 1810.3.3.1.2 LOAD TEST.
  
 19) COMPLIED.
  
 20) COMPLIED. WRITTEN SPECIAL INSPECTORS .
  
 21) COMPLIED. SHEET S1.1 FOUNDATIONS NOTE # 5-9 PROVIDE
 DETAILS ON THE BACK FILLING OF THE BASEMENT WALLS.
 SHEET A0.24 HEADING THERMAL & MOISTURE PROTECTION.
 PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1805.3
 WATERPROOFING 1-4.
  
 22) COMPLIED. CONCERNS THE PLANS DO NOT PROVIDE
 DOCUMENTATION OF CODE SECTION 2010 FBC-B 403.3.2
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 A MINIMUM OF (2) WATER MAINS LOCATED IN DIFFERENT
 STREETS. ALSO REVIEW THE EXCEPTION.
  
 23) 2ND REQUEST, NO RESPONSE COMMENT. THERE IS A
 QUESTION OF THE BONDING OF THE STEEL RE-ENFORCEMENT FOR
 ELECTRICAL. IS THERE ALSO GOING TO BE ANY LIGHTNING
 BONDING GOING TO BE REQUIRED? PERMIT WILL NEED TO BE
 PULLED FOR THE SCHEDULING OF THESE INSPECTIONS, NO
 DETAILS.
  
 24) IMPACT FEES DEFERRED TO BUILDING PERMIT.
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-05 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2015-11-04 Time 13:01 Sent To  
Notes
2015-11-05 07:44:34THE BRISTOL
 BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561)832-1616
 E-MAIL: [email protected]
  
  
  
 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: WED. NOV. 04/2015
 ACTION: DENIED
  
 1) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY
 CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED
 UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 2) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) 2ND REQUEST. A FLOOD ZONE CERTIFICATE IS REQUIRED AS
 PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT.
  
  
 FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) COMPLIED> THERE ARE SEVERAL DOCUMENTS THAT HAVE BEEN
 SUBMITTED IN THE SUPPORTING DOCUMENT FILE, NONE OF
 THESE FILES INDICATE THAT THE ARCHITECT OF RECORD HAS
 REVIEWED THEM THERE IS NO SHOP DRAWING STAMP OF
 APPROVAL WITH APPROVAL OR APPROVED AS NOTED.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER
 ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS?
 OFFICE.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) 2ND REQUEST. THRESHOLD INSPECTION PLAN FL S. S.
 553.71(7). 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN
 / TYPED STRUCTURALTHRESHOLD INSPECTION PLAN) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 5-9) COMPLIED.
  
 10) PROVISO: FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
 11) PROVISO: PERIMETER FENCING UNDER A SEPARATE PERMIT.
 PLEASE PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
 12) 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 9F) FBC-B 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 13) PROVISO: [F] 3311.1 WHERE REQUIRED. IN BUILDINGS
 REQUIRED TO HAVE STANDPIPES BY SECTION 905.3.1, NOT
 LESS THAN ONE STANDPIPE SHALL BE PROVIDED FOR USE
 DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED
 WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40
 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
 14)PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 15) PROVISO:ALL CONSTRUCTION TRAILERS (MOBILE OR
 MODULAR BUILDINGS) THAT ARE GOING TO HAVE MEETING IN
 THEM WILL BE REQUIRED TO GET A PERMIT, 102.2( E )
 MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY OFFICES,
 EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 16)PROVISO: DEPENDING ON THE SIZE OF THE CONSTRUCTION
 TRAILERS, CLOSENESS TO BUILDINGS AND OR OTHER
 CONSTRUCTION TRAILERS THE FIRE DEPARTMENT THROUGH THE
 FIRE PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS.
  
 17) 2ND REQUEST, FORM 1ST REVIEW NO RESPONSE. PLEASE
 NOTE THERE IS CONCERN RAISED THAT A SEAWALL REPAIR
 PERMIT IS IN FOR REVIEW, PERMIT # 15041128. IS THERE
 ANY CONCERNS THIS PORTION OF THE PROJECT NEEDS TO BE
 COMPLETED BEFORE THE AUGER CAST PILING BEGIN? IN THE
 GFA SOILS REPORT ON PAGE 10 IN BOLD PRINT AND UNDER
 LINED IS THE FOLLOWING COMMENT:
  
  
 I BELIEVE THIS IS COVERED UNDER SECTION 2010 FBC-B
 1803.3. ADDITIONAL STUDIES MAY BE REQUIRED.
  
  
 18)PROVISO: TO DATE THERE HAS BEEN NO PERMIT APPLIED
 FOR, FOR TEST PILING INCOMPLIANCE WITH THE 2010 FBC-B
 1810.3.3.1.2 LOAD TEST.
  
 19) 2ND REQUEST. NO WRITTEN SPECIAL INSPECTORS PLAN WAS
 SUBMITTED. TO DATE WE HAVE NO COMPANY SIGNED ON TO
 OVERSEE THE AUGER CAST PILE OR TEST PILE. FBC-B 1803.4
 QUALIFIED REPRESENTATIVE. 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION 117
 TESTS. THE BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST
 REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO
 BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 20) 2ND REQUEST. NO WRITTEN SPECIAL INSPECTORS PLAN WAS
 SUBMITTED.
 SHEET S1.01 NOTE # 20B UNDER THE HEADING REINFORCED
 CONCRETE MASONRY STATES THAT OBSERVE PLACEMENT OF AT
 LEAST 10% OF THE INDIVIDUAL UNITS FOR EACH GROUT LIFT.
 FL. S. S. 553.79 (5)(A) THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO AND APPROVED BY THE ENFORCING
 AGENCY BEFORE THE ISSUANCE OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE OF
 THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 21) COMPLIED. SHEET S1.1 FOUNDATIONS NOTE # 5-9 PROVIDE
 DETAILS ON THE BACK FILLING OF THE BASEMENT WALLS.
 SHEET A0.24 HEADING THERMAL & MOISTURE PROTECTION.
 PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1805.3
 WATERPROOFING 1-4.
  
 22) COMPLIED. CONCERNS THE PLANS DO NOT PROVIDE
 DOCUMENTATION OF CODE SECTION 2010 FBC-B 403.3.2
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 A MINIMUM OF (2) WATER MAINS LOCATED IN DIFFERENT
 STREETS. ALSO REVIEW THE EXCEPTION.
  
 23) 2ND REQUEST, NO RESPONSE COMMENT. THERE IS A
 QUESTION OF THE BONDING OF THE STEEL RE-ENFORCEMENT FOR
 ELECTRICAL. IS THERE ALSO GOING TO BE ANY LIGHTNING
 BONDING GOING TO BE REQUIRED? PERMIT WILL NEED TO BE
 PULLED FOR THE SCHEDULING OF THESE INSPECTIONS, NO
 DETAILS.
  
 24) IMPACT FEES DEFERRED TO BUILDING PERMIT.
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-13 Cont ID  
Sent By jwitmer Date 2015-06-13 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2015-05-28 Time 16:21 Sent To  
Notes
2015-06-13 10:31:54THE BRISTOL
 BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561)832-1616
 E-MAIL: [email protected]
  
  
  
 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. JUNE 13/2015
 ACTION: DENIED
  
 1) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY
 CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED
 UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 2) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) THERE ARE SEVERAL DOCUMENTS THAT HAVE BEEN SUBMITTED
 IN THE SUPPORTING DOCUMENT FILE, NONE OF THESE FILES
 INDICATE THAT THE ARCHITECT OF RECORD HAS REVIEWED THEM
 THERE IS NO SHOP DRAWING STAMP OF APPROVAL WITH
 APPROVAL OR APPROVED AS NOTED.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER
 ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS?
 OFFICE.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 FORMS WERE SENT TO: [email protected] AT SAT. JUNE
 13/ 2015 08:30 AM
  
 5C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 5F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE
 E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED,
 THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED
 AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS,
 TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK
 & WHITE..
  
 5G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  
 6) PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. 2010
 FBC-B 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL
 SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO
 UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR
 PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE
 UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT
 SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR
 CUT SLOPES SHALL BE PERMITTED ONLY UPON THE
 PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE
 TO THE BUILDING OFFICIAL.
  
 7) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE?2010 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 8) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. 2010 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING
 PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM
 DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION
 WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF
 AND EROSION DURING CONSTRUCTION OR DEMOLITION
 ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION
 TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS
 OF ADJOINING BUILDINGS ADVISING THEM THAT THE
 EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
 109.3.10 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
 9)PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 3303.5
 WATER ACCUMULATION. PROVISION SHALL BE MADE TO PREVENT
 THE ACCUMULATION OF WATER OR DAMAGE TO ANY FOUNDATIONS
 ON THE PREMISES OR THE ADJOINING PROPERTY.
  
 10)FBC-B 3306.9 ADJACENT TO EXCAVATIONS. EVERY
 EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS
 FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
 11) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
 12) 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 9F) FBC-B 3309.2 FIRE HAZARDS.
 THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD
 AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 13) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO
 HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE
 STANDPIPE SHALL BE PROVIDED FOR USE DURING
 CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN
 THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET
 (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE
 PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT
 ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
 14) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 15) ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR
 MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT
 THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513,
 FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS
 WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 16) DEPENDING ON THE SIZE OF THE CONSTRUCTION TRAILERS,
 CLOSENESS TO BUILDINGS AND OR OTHER CONSTRUCTION
 TRAILERS THE FIRE DEPARTMENT THROUGH THE FIRE
 PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS.
  
 17) PLEASE NOTE THERE IS CONCERN RAISED THAT A SEAWALL
 REPAIR PERMIT IS IN FOR REVIEW, PERMIT # 15041128. IS
 THERE ANY CONCERNS THIS PORTION OF THE PROJECT NEEDS TO
 BE COMPLETED BEFORE THE AUGER CAST PILING BEGIN? IN THE
 GFA SOILS REPORT ON PAGE 10 IN BOLD PRINT AND UNDER
 LINED IS THE FOLLOWING COMMENT:
  
  
 I BELIEVE THIS IS COVERED UNDER SECTION 2010 FBC-B
 1803.3. ADDITIONAL STUDIES MAY BE REQUIRED.
  
  
 18) TO DATE THERE HAS BEEN NO PERMIT APPLIED FOR, FOR
 TEST PILING INCOMPLIANCE WITH THE 2010 FBC-B
 1810.3.3.1.2 LOAD TEST.
  
 19) TO DATE WE HAVE NO COMPANY SIGNED ON TO OVERSEE THE
 AUGER CAST PILE OR TEST PILE. FBC-B 1803.4 QUALIFIED
 REPRESENTATIVE. 2010 FLORIDA BUILDING CODE W * 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 117 TESTS. THE
 BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS AS
 PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE AT
 THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED
 TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 20) SHEET S1.01 NOTE # 20B UNDER THE HEADING REINFORCED
 CONCRETE MASONRY STATES THAT OBSERVE PLACEMENT OF AT
 LEAST 10% OF THE INDIVIDUAL UNITS FOR EACH GROUT LIFT.
 FL. S. S. 553.79 (5)(A) THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO AND APPROVED BY THE ENFORCING
 AGENCY BEFORE THE ISSUANCE OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE OF
 THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 21) SHEET S1.1 FOUNDATIONS NOTE # 5-9 PROVIDE DETAILS
 ON THE BACK FILLING OF THE BASEMENT WALLS. SHEET A0.24
 HEADING THERMAL & MOISTURE PROTECTION. PLEASE PROVIDE
 COMPLIANCE WITH: 2010 FBC-B 1805.3 WATERPROOFING 1-4.
  
 22) CONCERNS THE PLANS DO NOT PROVIDE DOCUMENTATION OF
 CODE SECTION 2010 FBC-B 403.3.2 REQUIRED FIRE PUMPS
 SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF (2)
 WATER MAINS LOCATED IN DIFFERENT STREETS. ALSO REVIEW
 THE EXCEPTION.
  
 23) THERE IS A QUESTION OF THE BONDING OF THE STEEL
 RE-ENFORCEMENT FOR ELECTRICAL. IS THERE ALSO GOING TO
 BE ANY LIGHTNING BONDING GOING TO BE REQUIRED? PERMIT
 WILL NEED TO BE PULLED FOR THE SCHEDULING OF THESE
 INSPECTIONS, NO DETAILS.
  
 24) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 16:12 Rev Time 0.00
Received By albarran Date 2015-11-05 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By dhayes Date 2015-06-24 Time 10:41 Rev Time 0.00
Received By dhayes Date 2015-06-24 Time 10:09 Sent To  
Notes
2015-06-24 11:42:386/24/2015
 PROJECT: THE BRISTOL 1100 S. FLAGLER
 PERMIT#: 15050292
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW FOUNDATION ONLY
 ACTION: DENIED
  
 THERE ARE NO ELECTRICAL PLANS OR SPECIFICATIONS
 INCLUDED WITH THIS SUBMITTAL. REVISE YOUR PLANS IN
 RESPONSE TO THE FOLLOWING REVIEW COMMENTS:
  
 1) AS A FOUNDATION ONLY PERMIT THE MINIMUM PLAN REVIEW
 CRITERIA SHALL INCLUDE BUT NOT BE LIMITED TO AN
 ELECTRICAL GOUNDING ELECTRODE SYSTEM DESIGN DETAIL PER
 THE NEC ARTICLE 250. SEE NEC 250.30(7) AND 250.50 AND
 250.52
  
 2) PG. MEP INDICATES AN FPL DUCT BANK BUT DOES NOT
 INDICATE ANY UNDERGROUND CONDUITS THAT MAY BE AFFECTED
 BY THE INSTALLATION OF THE FOUNDATION PILES OR FOOTINGS
 SUCH AS ON SITE GERERATOR POWER FOR EMERGENCY POWER
 LOADS OR STANDBY POWER LOADS PER FBC 403.7, 403.8
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-12-22 Cont ID  
Sent By mgonzale Date 2015-12-23 Time   Rev Time 1.00
Received By mgonzale Date 2015-12-22 Time   Sent To Z
Notes
2015-12-22 17:28:55 
  
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-09-28 Cont ID  
Sent By cranford Date 2015-09-28 Time 09:58 Rev Time 0.00
Received By cranford Date 2015-09-28 Time 09:57 Sent To  
Notes
2015-09-28 09:58:07SEE PREVIOUS COMMENTS

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By cranford Date 2015-05-21 Time 12:28 Rev Time 0.00
Received By cranford Date 2015-05-21 Time 12:24 Sent To  
Notes
2015-05-21 12:28:06PLEASE SUBMIT AN APPLICATION FOR ENGINEERING
 DEVELOPMENT APPROVAL. THE CIVIL PLANS INCLUDED IN THIS
 SUBMITTAL ARE FOR REFERENCE ONLY.
  
 PLEASE INDICATE THE DISCHARGE POINT(S) FOR THE STORM
 SUMP PIT AND TRENCH DRAIN SHOWN ON SHEETS A2.0P1 AND
 A2.0P2.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-22 Cont ID  
Sent By pleduc Date 2015-05-22 Time   Rev Time 0.00
Received By pleduc Date 2015-05-22 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2016-03-07 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-12 Cont ID  
Sent By lmarchan Date 2016-01-12 Time 15:08 Rev Time 0.00
Received By lmarchan Date 2015-12-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-10 Cont ID  
Sent By cpuell Date 2015-11-10 Time 09:38 Rev Time 0.00
Received By cpuell Date 2015-09-02 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By tklarge Date 2015-06-24 Time 14:04 Rev Time 0.00
Received By tklarge Date 2015-05-11 Time 13:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-11-17 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2015-11-05 Time 07:23 Sent To  
Notes
2015-11-05 07:24:0511/13/2015 RECEIVED E-MAIL FROM MR. SWOOPE THAT THE
 IMPACT FEES WILL BE WAIVED ON THE FOUNDATION PERMIT BUT
 WILL BE COLLECTED BEFORE THE ISSUANCE OF THE BUILDING
 PERMIT.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-13 Cont ID  
Sent By jwitmer Date 2015-06-13 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2015-06-13 Time 10:27 Sent To  
Notes
2015-06-13 10:27:31BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-29 Cont ID  
Sent By tklarge Date 2015-09-10 Time 08:40 Rev Time 0.00
Received By tklarge Date 2015-09-10 Time 04:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-24 Cont ID  
Sent By tklarge Date 2015-06-24 Time 14:04 Rev Time 0.00
Received By tklarge Date 2015-06-24 Time 14:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-03-30 Cont ID  
Sent By skennedy Date 2016-03-30 Time 14:41 Rev Time 0.00
Received By skennedy Date 2016-03-30 Time 14:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-03-25 Cont ID  
Sent By skennedy Date 2016-03-25 Time 11:01 Rev Time 0.00
Received By skennedy Date 2016-03-25 Time 11:01 Sent To  
Notes
2016-03-25 11:34:102ND REVIEW: FBC 2010
  
 REVIEW OF SIGNATURES:
  
 AT THIS TIME EVIDENCE OF APPLICATION TO THE STATE OF
 FLORIDA BY SOLOMON, CORDWELL, BUENZ & ASSOCIATES IS
 ACCEPTABLE. NOTE THE CERTIFICATE NUMBER TO BE ISSUED
 SHALL BE AFFIXED TO ALL APPLICABLE PLAN SHEETS TO BE
 RE-SUBMITTED FOR PERMIT 15111020.
  
 AT THIS TIME EVIDENCE OF APPLICATION TO THE STATE OF
 FLORIDA BY CS ASSOCIATES, INC. IS ACCEPTABLE. NOTE THE
 CERTIFICATE NUMBER TO BE ISSUED SHALL BE AFFIXED TO ALL
 APPLICABLE PLAN SHEETS TO BE RE-SUBMITTED FOR PERMIT
 15111020.
  
 SURVEY - THE SURVEY IS NOT SIGNED AND SEALED. PLEASE
 PROVIDE A S&S VERSION.
  
 ARCHITECTURAL - THE DIGITALLY APPLIED SIGNATURE ON
 SHEET SS1.0 BY GARY KOHN, AR-94323 DOES NOT
 AUTHINTICATE. THE MULTI-PAGE PDF OF ARHITECTURAL SHEETS
 ARE NOT, IN FULL, THE SAME VERSION OF THE REVIEWED
 SHEETS THAT HAVE BEEN UPLOADED TO PROJECTDOX. FOR
 EXAMPLE, SHEET A0..01 INDICATES IN THE TITLE BLOCK
 8/27/2015 AS THE DATE OF THE SHEET WHEREAS THE REVIEWED
 VERSION OF SHEET A0.01 INDICATES 5/8/2015 AS THE
 UPDATED VERSION OF THE SHEET. THIS MAY BE THE ONLY
 SHEET THAT IS NOT PROPERLY DATED AND IN THAT EVENT,
 THERE IS NO NEED TO SWAP IT AS IT IS ACCEPTABLE IN THE
 UPDATED FORM. HOWEVER, THE FILE SEEMS TO BE CORRUPT.
 SHEETS BEYOND A3.0* DO NOT FULLY OPEN. PLEASE RE-SUBMIT
 THE FILE WITH SHEETS MATCHING THE PREVIOUSLY REVIEWED
 VERSIONS AND A DIGITAL SIGNATURE THAT CAN BE VERIFIED.
 .
  
 STRUCTURAL - THE MULTI-PAGE PDF OF STRUCTURAL SHEETS
 S&S BY RALPH M CALISTRO, PE 77329 ARE NOT, IN FULL, THE
 SAME VERSION OF THE REVIEWED SHEETS THAT HAVE BEEN
 UPLOADED TO PROJECTDOX. FOR EXAMPLE, SHEET S1.01
 INDICATES IN THE TITLE BLOCK 5/8/2015 AS THE DATE OF
 THE SHEET WHEREAS THE REVIEWED VERSION OF SHEET S1.01
 INDICATES 2/26/2016 AS THE UPDATED VERSION OF THE
 DESIGN. PLEASE RE-SUBMIT THE S&S FILE WITH SHEETS
 MATCHING THE PREVIOUSLY REVIEWED VERSIONS. YOU MAY
 SUMBIT ONLY CORRECTED SHEETS IN AN ADDITIONAL FILE IF
 YOU PREFER AS THERE MAY BE ONLY A FEW IN NEED OF
 CORRECTION..
  
 MEP - AGAIN, THE 5/6/2015 SHEET IS PROVIDED WHEREAS THE
 8/27/15 VERSION IS THE REVIEWED VERSION. THE SIGNATURE
 AUTHINTICATES PROPERLY.
  
 LANDSCAPE & CIVIL - ACCEPTED AS CONSIDERED FOR
 REFERENCE ONLY, HOWEVER THE GENERAL NOTES BELOW APPLY.
  
 GENERAL - THE FOLLOWING ISSUE MAY BE CLEARED THROUGH
 CORRECTED SUBMITTALS TO THE PRIMARY BUILDING PERMIT
 NUMBER 15111020. PLEASE NOTE THAT MANY SHEETS CONTAIN
 TITLE BLOCK DISCREPANCIES SUCH AS THE ORIGINAL ADDRESS
 NOT UPDATED, THE LACK OF A CERTIFICATE OF AUTHORIZATION
 NUMBER, AND THE LACK OF THE NAME AND LICENSE NUMBER OF
 THE DESIGN PROFESSIONAL. PLEASE BE ADVISED THAT
 ALTHOUGH THE NEWLY CREATED SS SHEETS CONTAIN THE NAME
 AND LICENSE NUMBER OF THE DESIGN PROFESSIONAL, ALL
 SHEETS MUST INDICATE SO, IN THE TITLE BLOCK, APART FROM
 THE SEAL OR DIGITAL SIGNATURE SHOWING IT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By skennedy Date 2016-03-14 Time 15:16 Rev Time 0.00
Received By skennedy Date 2016-03-10 Time 13:39 Sent To  
Notes
2016-03-14 15:22:051ST REVIEW: FBC 2010
  
 I HAVE REVIEWED THE SUBMITTAL AND COMMENTED TO DAN
 PETROVIC AS TO THE LACK OF COMPLIANT TITLE BLOCK
 INFORMATION AND WE DISCUSSED THE DIGITAL SIGNATURE
 SUBMITTAL PROCESS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-01-12 Cont ID  
Sent By jroach Date 2016-01-12 Time 15:04 Rev Time 0.00
Received By jroach Date 2016-01-12 Time 15:04 Sent To  
Notes
2016-01-12 15:05:15THIS REVIEW IS FOR THE FOUNDATION PERMIT ONLY!

Review Stop Z ZONING
Rev No 2 Status F Date 2015-11-10 Cont ID  
Sent By jroach Date 2015-11-10 Time 09:13 Rev Time 0.00
Received By jroach Date 2015-11-10 Time 09:13 Sent To  
Notes
2015-11-10 09:16:56ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.10.2015
 PERMIT NO.: 15050292
 ADDRESS: 1100 SOUTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: CHRISTOPHER KENNEDY - SUFFOLK
 CONSTRUCTION
 TELEPHONE NO.: 561.832.1616
 SCOPE OF REVIEW: FOUNDATION PERMIT FOR NEW CONDOMINIUM
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A PERMIT:
  
  A. PURSUANT TO RESOLUTION NO. 140-14, A CONSTRUCTION
 SITE SECURITY AND MANAGEMENT PLAN SHALL BE REVIEWED AND
 APPROVED BY THE CITY OF WEST PALM BEACH POLICE
 DEPARTMENT - CRIME PREVENTION UNIT. A COPY OF THE
 MANAGEMENT PLAN AND APPROVAL LETTER FROM THE CRIME
 PREVENTION UNIT SHALL BE PROVIDED TO THE DEVELOPMENT
 SERVICES DEPARTMENT - PLANNING DIVISION.
  
  B. PURSUANT TO RESOLUTION NO. 140-14, A RESTRICTIVE
 COVENANT, IN A FORM ACCEPTABLE TO THE CITY OF WEST PALM
 BEACH CITY ATTORNEY'S OFFICE AND DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION, SHALL BE RECORDED BY
 THE DEVELOPER IN THE PUBLIC RECORD OF PALM BEACH
 COUNTY, FLORIDA, RESTRICTING THAT THE PARCEL TO THE
 NORTH SHALL NEVER BE FILLED, SHALL ALWAYS REMAIN OPEN
 AND UNOBSTRUCTED (WITH THE EXCEPTION OF EXISTING
 VEGETATION), AND SHALL NEVER BE BUILT UPON, EXCEPT FOR
 RECREATIONAL OR ENVIRONMENTAL PURPOSES.
  
 2. PRIOR TO THE REMOVAL OF ANY OF THE EXISTING PARKING
 ON THE PROPERTY, ALL APPLICABLE IMPROVEMENTS TO THE
 FIRST BAPTIST CHURCH OF WEST PALM BEACH COMMUNITY
 SERVICE PLANNED DEVELOPMENT (CSPD) SHALL BE COMPLETED
 TO ENSURE THAT THE MINIMUM NUMBER OF PARKING SPACES
 REQUIRED BY ARTICLE XIV OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS FOR THE CHURCH AND ITS
 ANCILLARY FACILITIES ARE PROVIDED.
  
 3. THE SITE PLAN SHALL PROVIDE DIMENSIONED SETBACKS
 FROM THE PROPERTY LINE TO THE BUILDING.
  
 4. ENSURE THAT THE SITE PLAN MATCHES THAT WHICH WAS
 APPROVED VIA MINOR PD AMENDMENT (PB CASE NO. 1635G) ON
 09.09.2015.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By jroach Date 2015-06-04 Time 10:57 Rev Time 0.00
Received By jroach Date 2015-06-04 Time 10:57 Sent To  
Notes
2015-06-04 10:58:11ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.04.2015
 PERMIT NO.: 15050292
 ADDRESS: 1100 SOUTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: CHRISTOPHER KENNEDY ? SUFFOLK
 CONSTRUCTION
 TELEPHONE NO.: 561.832.1616
 SCOPE OF REVIEW: FOUNDATION PERMIT FOR NEW CONDOMINIUM
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A PERMIT:
  
  A. PURSUANT TO RESOLUTION NO. 140-14, A CONSTRUCTION
 SITE SECURITY AND MANAGEMENT PLAN SHALL BE REVIEWED AND
 APPROVED BY THE CITY OF WEST PALM BEACH POLICE
 DEPARTMENT ? CRIME PREVENTION UNIT. A COPY OF THE
 MANAGEMENT PLAN AND APPROVAL LETTER FROM THE CRIME
 PREVENTION UNIT SHALL BE PROVIDED TO THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING DIVISION.
  
  B. PURSUANT TO RESOLUTION NO. 140-14, A RESTRICTIVE
 COVENANT, IN A FORM ACCEPTABLE TO THE CITY OF WEST PALM
 BEACH CITY ATTORNEY?S OFFICE AND DEVELOPMENT SERVICES
 DEPARTMENT ? PLANNING DIVISION, SHALL BE RECORDED BY
 THE DEVELOPER IN THE PUBLIC RECORD OF PALM BEACH
 COUNTY, FLORIDA, RESTRICTING THAT THE ABOVE-DESCRIBED
 PROPERTY SHALL NEVER BE FILLED, SHALL ALWAYS REMAIN
 OPEN AND UNOBSTRUCTED (WITH THE EXCEPTION OF EXISTING
 VEGETATION), AND SHALL NEVER BE BUILT UPON, EXCEPT FOR
 RECREATIONAL OR ENVIRONMENTAL PURPOSES.
  
 2. THE PLANS SUBMITTED FOR THE FOUNDATION PERMIT DO NOT
 MATCH THOSE APPROVED VIA RESOLUTION NO. 140-14. ANY
 MODIFICATIONS TO THE PLANS SHALL REQUIRE AN AMENDMENT
 TO THE RESIDENTIAL PLANNED DEVELOPMENT (RPD).
  
 3. PRIOR TO THE REMOVAL OF ANY OF THE EXISTING PARKING
 ON THE PROPERTY, ALL APPLICABLE IMPROVEMENTS TO THE
 FIRST BAPTIST CHURCH OF WEST PALM BEACH COMMUNITY
 SERVICE PLANNED DEVELOPMENT (CSPD) SHALL BE COMPLETED
 TO ENSURE THAT THE MINIMUM NUMBER OF PARKING SPACES
 REQUIRED BY ARTICLE XIV OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS FOR THE CHURCH AND ITS
 ANCILLARY FACILITIES ARE PROVIDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved