Plan Review Details - Permit 15050267
Plan Review Stops For Permit 15050267
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 13:00 Rev Time 0.00
Received By jwitmer Date 2015-09-10 Time 12:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-25 Cont ID  
Sent By jwitmer Date 2015-08-25 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2015-08-25 Time 15:56 Sent To  
Notes
2015-08-25 16:29:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050267
 ADD: 1001 36TH ST. #M33
 CONT: TBD
 TEL: (386)7056
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. AUG. 25/2015
 ACTION: DENIED
  
 ) NOTICE:!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
  
 1) COMPLIED.
  
 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR
 FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW
 OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR
 LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART
 OF THE MAIN WIND FORCE RESISTING SYSTEM.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) COMPLIED> ) .
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2015-07-17 Time 12:18 Sent To  
Notes
2015-07-22 14:58:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050267
 ADD: 1001 36TH ST. #M33
 CONT: TBD
 TEL: (386)7056
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 17/15
 ACTION: DENIED
  
 1) THE WALL BETWEEN THE EXISTING LAUNDRY ROOM AND
 EXISTING ROOM IS TO BE DEMOLISHED, IS THIS A BLOCK
 WALL, LOAD BEARING WALL, IT APPEARS TO BE DRAWN TO BE A
 8 INCH WALL? THE PLANS SHEET A3 APPEAR TO HAVE THE SAME
 WALL LINE IN THE SAME LOCATION107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR
 FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW
 OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR
 LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART
 OF THE MAIN WIND FORCE RESISTING SYSTEM.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By jwitmer Date 2015-05-15 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 09:14 Sent To  
Notes
2015-05-15 09:29:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050267
 ADD: 1001 36TH ST. #M33
 CONT: TBD
 TEL: (386)7056
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 17/15
 ACTION: DENIED
  
 1) THE WALL BETWEEN THE EXISTING LAUNDRY ROOM AND
 EXISTING ROOM IS TO BE DEMOLISHED, IS THIS A BLOCK
 WALL, LOAD BEARING WALL, IT APPEARS TO BE DRAWN TO BE A
 8 INCH WALL? THE PLANS SHEET A3 APPEAR TO HAVE THE SAME
 WALL LINE IN THE SAME LOCATION107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR
 FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW
 OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR
 LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART
 OF THE MAIN WIND FORCE RESISTING SYSTEM.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-09-03 Cont ID  
Sent By skennedy Date 2015-09-03 Time 09:32 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-09-03 09:34:07APPLICANT INDICATES THE ELECTRICAL DESIGN IS TO BE
 PERFORMED UNDER PERMIT 15040378.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-24 Cont ID  
Sent By albarran Date 2015-07-24 Time 10:05 Rev Time 0.00
Received By albarran Date 2015-07-24 Time 9:15 Sent To M
Notes
2015-07-24 10:05:28PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PROVIDE A LEGIBLE AND ACCURATE SYMBOL LEGEND AS PER
 FBC
 2. YOU SHALL SUBMIT SPECIFIC LOAD CALCS AS REQUIRED BY
 NEC 220
 3. IDENTIFY ALL EQUIPMENT AND ITS SPECIFIC LOCATION ON
 THE FLOOR PLANS, ALONG WITH ITS DEDICATED ELECTRICAL
 CKT.
 4. IDENTIFY EVERY ELECTRICAL PANEL SHOWN ON THE FLOOR
 PLANS WITH ITS RESPECTIVE CIRCUIT DIRECTORY.
 5. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING ALL
 ELECTRICAL PANELS ON SITE.
 6. YOU SHALL PROVIDE A LIGHTING PLAN COMPLIANT WITH
 FBC-E SECTION 505.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By rlecky Date 2015-05-14 Time 12:51 Rev Time 0.00
Received By rlecky Date 2015-05-14 Time 12:41 Sent To  
Notes
2015-05-14 12:43:00PROVIDE LOAD CALCULATION. INDICATED SIZE OF EXISTING
 PANELBOARD AND SERVICE. VERIFY THE EXISTING SERVICE CAN
 CARRY THE NEW ELECTRICAL LOADS. PROVIDE A PANEL
 SCHEDULE SHOWING ALL WIRE AND CIRCUIT SIZES.NEC 215.5,
 220.10
  
 SEE ELECTRIC PERMIT #15040378
 R. LECKY, ELECTRICAL PLANS EXAMINER

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-31 Cont ID  
Sent By scaldero Date 2015-08-31 Time 14:32 Rev Time 0.00
Received By scaldero Date 2015-08-31 Time 14:30 Sent To  
Notes
2015-08-31 14:32:26PERMIT # 15050267
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL ADDITIONAL PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-11 Cont ID  
Sent By scaldero Date 2015-05-11 Time 13:38 Rev Time 0.00
Received By scaldero Date 2015-05-11 Time 13:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-09-17 Cont ID  
Sent By tklarge Date 2015-09-17 Time 06:48 Rev Time 0.00
Received By tklarge Date 2015-09-16 Time 10:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-08-19 Cont ID  
Sent By tklarge Date 2015-08-19 Time 10:57 Rev Time 0.00
Received By tklarge Date 2015-08-19 Time 10:07 Sent To  
Notes
2015-08-19 10:53:141) THE SUBMITTED VENT DETAIL IS INADEQUATE. SHOW THE
 TYPE OF VENT ( TYPE B, OR SINGLE WALL,ETC.) IF SINGLE
 WALL VENT, INDICATE THE THICKNESS OF THE METAL. THE
 SINGLE WALL VENT SHALL BE CONSTRUCTRED OF GALVANIZED
 SHEET METAL NOT LESS THAN 0.0304 INCH THICK PER 2010
 FBC-FUEL GAS SEC.503.7 AND SHALL BE INSTALLED PER FGC
 503.7.3 & 503.7.7.
 2) IF VENT IS OTHER THAN SINGLE WALL PIPE, THE VENT
 SHALL COMPLY WITH 2010 FGC SEC.503.6.4, 503.6.5.
 3) THE GAS LINE FROM THE GAS METER TO THE FIRST TEE
 CONNECTION SHALL BE 1 1/2" PER TABLE 402.4 (2).
 4) INDICATE THE TYPE OF PIPE BEING USED FOR GAS THE
 SYSTEM.
 5) THE TYPICAL GAS PIPE DROP SHOW 3 & 6 FT. DROPS TO
 THE APPLIANCES BUT THE GAS RISER SHOWS 2 & 4 FT. DROPS.
 CLARIFY.
 6) IDENTIFY ON THE FAN LITERATURE THE SPECIFIC MODEL
 THAT IS BEING USED. WPB AMEND TO FBC SEC.107.2.1.
 7) IDENTIFY ON THE MANUF. SPECS THE TYPE OF BACKDRAFT
 DAMPER BEING INSTALLED.WPB AMEND TO FBC SEC.107.2.1.
 8) SUBMIT ADDITIONAL DOCUMENTATION AS TO HOW THE MAKE
 UP AIR FAN MEETS THE MINIMUM REQUIRED AMOUNT OF
 COMBUSTION AIR IN ACCORDANCE WITH THE 2010 FGC
 SEC.304.5,304.6,304.7,304.10,& 304.11.
 9) HOW WILL THE FAN OPERATE - IS IT CONNECTED TO A
 LIGHT SWITCH AND OPERATE WHEN THE SPACE IS BEING USED?
 WHAT IS THE PURPOSE OF THE EDJ UNIT THAT IS BEING
 INSTALLED?
  
 I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO
 DISCUSS THE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By tklarge Date 2015-07-16 Time 05:18 Rev Time 0.00
Received By tklarge Date 2015-07-16 Time 05:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-09-28 Cont ID  
Sent By ccole Date 2015-09-28 Time 07:33 Rev Time 0.00
Received By ccole Date 2015-09-25 Time 10:56 Sent To  
Notes
2015-09-25 10:56:58RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-09-17 Cont ID  
Sent By tklarge Date 2015-09-17 Time 06:48 Rev Time 0.00
Received By tklarge Date 2015-09-03 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-09-03 Cont ID  
Sent By skennedy Date 2015-09-03 Time 09:32 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 07:53 Sent To  
Notes
2015-08-14 07:53:40B06

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-24 Cont ID  
Sent By albarran Date 2015-07-24 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-07-17 Time 14:11 Sent To  
Notes
2015-07-23 14:11:56PREVIOUS IN-STOP CLOSED BY MISTAKE. B20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2015-07-08 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-09 Cont ID  
Sent By tklarge Date 2015-06-09 Time 05:19 Rev Time  
Received By tklarge Date 2015-05-08 Time   Sent To  
Notes
2015-05-08 18:49:07B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-10-22 Cont ID  
Sent By jwitmer Date 2015-10-22 Time 10:40 Rev Time 0.00
Received By jwitmer Date 2015-10-21 Time 10:11 Sent To  
Notes
2015-10-22 10:40:3110/22/2015
 IMPACT FEE ASSESSMENT
 MU-2015-24847
 NO FEES DUE!
2015-10-22 10:12:16JWITMER'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By jwitmer Date 2015-05-15 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 09:29 Sent To  
Notes
2015-05-15 09:30:04BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2015-09-28 Cont ID  
Sent By ccole Date 2015-09-28 Time 07:33 Rev Time 0.00
Received By ccole Date 2015-09-28 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-09-14 Cont ID  
Sent By ccole Date 2015-09-14 Time 13:48 Rev Time 0.00
Received By ccole Date 2015-09-14 Time 13:46 Sent To  
Notes
2015-09-14 13:55:553RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050267
 9/14/15
  
 1) THIS IS THE 3RD SUBMITTAL ON THIS PROJECT AND
 COMMENTS FROM THE 1ST REVIEW STILL EXIST. I AM
 REPRINTING THEM HERE. PLEASE CORRECT AND REVISE THE
 PLAN ACCORDINGLY:
 2) (PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING
 SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE
 PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR
 INSTALLATIONS WILL BE NECESSARY.)
 PLEASE NOTE THAT THE MECHANICAL VENTILATION RATE PER
 THE TABLE IS 7.5 CFM PER PERSON WITH THE OCCUPANT
 DENSITY LEVEL 20 PERSONS PER 1000 SQ. FT. SHOW THE
 CALCULATION ON THE PLANS AND CLARIFY HOW THE SYSTEM
 WILL FUNCTION (APPARENTLY THE WALL FAN HAS BEEN REMOVED
 FROM THE PLANS).
 IF USING THE NATUTURAL VENTILATION METHOD, PLEASE
 PROVIDE A CALCULATION TO VERIFY COMPLIANCE WITH SECTION
 402.2 ( MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE
 4 PERCENT OF THE FLOOR AREA BEING VENTILATED).
 *NOTE: PLEASE REVIEW SECTION 304.9.3 FBC-10 FUEL GAS-
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR.
 IF YOU HAVE ANY QUESTIONS, NEED FURTHER CLARIFICATION,
 OR WOULD LIKE TO SET UP A MEETING TO HELP EXPEDITE THE
 PERMITTING PROCESS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 10:56 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 10:56 Sent To  
Notes
2015-08-21 11:29:573RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15050267
 8/21/15
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE
 MANUFACTURER'S SPECS FOR THE GREENHECK LOUVER, AND A
 VALID FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR
 THE GREENHECK LOUVER. PLEASE NOTE THAT THE LOUVER CAN
 PROTECT BOTH THE MAKEUP AIR OPENING AND THE EXHAUST FAN
 OPENING- CURRENTLY PLAN IS NOT SHOWING HOW THE FAN
 OPENING WILL BE PROTECTED. PLEASE ADDRESS THIS ISSUE.
 2) THE SUBMITTED SPECS FOR THE EXHAUST FAN DO NOT SHOW
 WHICH OF THE GREENHECK TYPE SE1 FANS WILL BE USED.
 PLEASE SUBMIT THE CUT SHEETS FOR THAT MODEL ONLY, AND
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN THAT INCLUDES
 THE MODEL NUMBER, CFM CAPACITY, AND ELECTRICAL DATA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-24 Cont ID  
Sent By ccole Date 2015-07-24 Time 11:05 Rev Time 0.00
Received By ccole Date 2015-07-24 Time 11:05 Sent To  
Notes
2015-07-24 11:29:242ND REVIEW: FBC 2010 MECHANICAL
  
 1) THE REQUESTED SUBMITTALS FOR THE DRYERS HAVE NOT
 BEEN REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL
 OF RECORD AS REQUESTED: PLEASE COMPLY AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN AS REQUESTED IN THE 1ST
 REVIEW.
 2) AS REQUESTED IN THE FIRST REVIEW, PROVIDE MAKE-UP
 AIR CALCULATIONS ON THE PLAN FOR THE DRYERS- (SEE
 MANUFACTURER'S RECOMMENDATIONS), AND VENTILATION
 CALCULATIONS FOR THE NEW LAUNDRY ROOM- (TABLE 403.3
 FBC-MECHANICAL). SHOW HOW ALL AIR IS BEING SUPPLIED AND
 CONTROLLED.
 3) AS REQUESTED IN THE 1ST REVIEW, PROVIDE FRONT AND
 PLAN VIEWS OF THE EXHAUST VENTS: INDICATE THE TYPE AND
 SIZE OF THE DUCTS, LENGTH OF THE CONNECTORS, HEIGHTS OF
 RISERS, TOTAL RUN CALCULATIONS AND TERMINATION
 LOCATIONS.
 4) SHOW COMPLIANCE WITH SECTION 504.4 FOR REQUIRED
 BACKDRAFT DAMPERS TO BE INSTALLED AT THE DRYER VENT
 TERMINATIONS.
 5) INDICATE IF THE GAS-FIRED WATER HEATER IS NEW OR
 EXISTING ON THE PLAN. IF THE UNIT IS NEW, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER AND
 VENT SYSTEM, AND PROVIDE A VENTING DIAGRAM. THE VENTING
 DIAGRAM SHALL SHOW THE TYPE AND SIZE OF VENT PIPE,
 TOTAL LENGTH OF CONNECTORS AND RISERS, AND TERMINATION
 LOCATION- REFER TO SECTION 504 FBC-10 FUEL GAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By ccole Date 2015-06-08 Time 16:45 Rev Time 0.00
Received By ccole Date 2015-06-08 Time 16:45 Sent To  
Notes
2015-06-08 17:17:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) A COMPLETE REVIEW OF THE PROPOSED PROJECT CANNOT BE
 COMPLETED WITHOUT SUBMITTAL OF COMPLETE MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW DRYERS AND VENTS.
 THE SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD- SECTION 614 FBC-10 FUEL
 GAS. PLEASE NOTE THAT THE CODE CLASSIFIES DRYERS AS
 EITHER RESIDIENTIAL OR COMMERCIAL, AND THE
 MANUFACTURER'S MAKE THAT DETERMINATION DEPENDING USAGE.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 DRYERS, AND CLARIFY IF THE DRYERS WILL BE
 COIN-OPERATED.
 3) INDICATE THE SOURCE OF, AND THE AMOUNT OF MAKE-UP
 AIR REQUIRED BY THE MANUFACTURER FOR EACH DRYER.
 4) PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING
 SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE
 PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR
 INSTALLATIONS WILL BE NECESSARY.
 5) PROVIDE FRONT AND PLAN VIEWS OF THE EXHAUST VENTS:
 INDICATE THE TYPE AND SIZE OF THE DUCTS, LENGTH OF THE
 CONNECTORS, HEIGHTS OF RISERS, TOTAL RUN CALCULATIONS
 AND TERMINATION LOCATIONS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-08-19 Cont ID  
Sent By tklarge Date 2015-08-19 Time 10:07 Rev Time 0.00
Received By tklarge Date 2015-08-17 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-16 Cont ID  
Sent By tklarge Date 2015-07-16 Time 05:11 Rev Time 0.00
Received By tklarge Date 2015-07-16 Time 02:40 Sent To  
Notes
2015-07-16 04:50:321) SUBMIT A TYPICAL VENT DETAIL FOR THE GAS DRYERS.
 SHOW THE SIZE, THE TYPE OF VENT, THE HEIGHT OF THE VENT
 ABOVE FINISH GRADE,
 2) SHOW THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING
 FROM THE POINT OF DELIVERY TO THE FURTHEST OUTLET ON
 THE SYSTEM. THERE IS OVER-TYPE ON THE GAS RISER SO SOME
 OF THE PIPE SIZES AND DIMENSIONS CANNOT BE READ.SHOW
 THE LENGTH OF THE TYPICAL PIPE DROPS TO THE DRYERS.
 3) INDICATE THE PSI OF THE GAS COMING INTO THE
 STRUCTURE. THE PLANS SHOW 5 PSI AT THE METER.IS THIS
 GOING TO BE THE PSI FOR THE SYSTEM? FOR A 5 PSI SYSTEM,
 THE FUEL GAS CODE HAS ONLY ONE TABLE AND THAT IS WITH A
 PRESSURE DROP OF 3.5 PSI. IS THIS THE TABLE YOU ARE
 USING? IF SO, INDICATE SUCH ON THE GAS PLANS WPB AMEND.
 TO FBC SEC. 107.3.5.1.5.
 4) SHOW THE LOCATION OF ALL LINE GAS PRESSURE REDUCING
 REGULATORS ( IF APPLICABLE ) AND SHOW THE VENTING OF
 THE REGULATORS PER 2010 FUEL GAS CODE SEC. 410.3,
 410.3.1. ALL REGULATORS SHALL BE ACCESSIBLE.
 5) THE GAS RISER SHOWS THE GAS LINE TO THE WATER HEATER
 AS 1 INCH AND THE PLAN VIEW SHOWS IT AS 3/4 ". WHICH IS
 IT?
 6) HOW WAS THE SIZE OF THE LINT TRAP DETERMINED? SUBMIT
 FLOW CALCULATIONS CONFIRMING THAT INTERCEPTOR IS OF
 ADEQUATE CAPACITY FOR THIS SYSTEM. 2010 FPC 1003.2.
 7) VENTS AND BRANCH VENTS EXCEEDING EXCEEDING 40 FEET
 IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE PIPE SIZE
 FOR THE ENTIRE LENGTH OF THE VENT PIPE IN ACCORDANCE
 WITH 2010 FPC SEC.916.2, 916.4.
 8) THE GAS PIPING SHALL BE BONDED PER 2010 FGC
 SEC.310.1.
 9) EXHAUST DUCTS FOR CLOTHES DRYERS SHALL BE EQUIPPED
 WITH BACKDRAFT DAMPERS.2010 FGC SEC.614.4.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYERS. 2010 FGC SEC.304.1.
 11) SHT. M-1 SHOWS 10 DRYERS BUT ONLY 8 EXHAUSTS.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-09 Cont ID  
Sent By tklarge Date 2015-06-09 Time 05:19 Rev Time 0.00
Received By tklarge Date 2015-06-09 Time 04:13 Sent To  
Notes
2015-06-08 15:28:451) SUBMIT A DETAIL FOR THE GAS VENT FOR THE WATER
 HEATER. SHOW THE SIZE, TYPE OF VENT, HEIGHT OF VENT
 ABOVE ROOF. SUBMIT A ROOF PLAN SHOWING THE LOCATION OF
 THE VENT IN RELATION TO AIR INTAKES,PARAPET WALLS (IF
 APPLICABLE) .WPB AMEND. TO 2010 FBC SEC.107.2.1, 2010
 FBC-FUEL GAS SEC.502,503.
 2) SUBMIT A TYPICAL VENT DETAIL FOR THE GAS DRYERS.SHOW
 THE SIZE, TYPE OF VENT, HEIGHT OF VENT ABOVE ROOF.
 SUBMIT A ROOF PLAN SHOWING THE LOCATION OF THE VENT IN
 RELATION TO AIR INTAKES, PARAPET WALLS (IF
 APPLICABLE).WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) SHOW THE TYPICAL SHUTOFF VALVES ON THE WATER RISER
 AND ON THE WATER HEATER.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) INDICATE THE TYPICAL SIZE OF THE WATER RISER TO THE
 WASHING MACHINES.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 5) INDICATE THE SIZE OF THE WATER HEATER IN WATER
 CAPACITY. (GALLONS).WPB AMEND. TO 2010 FBC SEC.107.2.1.
 6) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK
 BEING DONE.
 7) SUBMIT A GAS RISER DIAGRAM FOR REVIEW. THE RISER
 DIAGRAM SHALL SHOW THE BTU LOAD OF EACH APPLIANCE, THE
 TOTAL BTU LOAD ON THE GAS SYSTEM, THE DEVELOPED LENGTH
 OF PIPING FROM THE GAS METER TO THE FURTHEST GAS
 OUTLET,THE LENGTH OF EACH SECTION OF PIPE, THE TYPE OF
 PIPE BEING INSTALLED, THE PSI OF THE GAS SYSTEM,
 MANUFACTURER'S SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT/ APPLIANCES, THE LOCATION OF SHUTOFF VALVES,
 THE LOCATION OF ALL PRESSURE REGULATORS. INDICATE THE
 APPLICABLE GAS PIPE SIZING TABLE USED FOR THE DESIGN OF
 THE GAS SYSTEM. 201 FBC-FUEL GAS SEC.402.3.WPB AMEND.
 TO FBC SEC. 107.3.5.1.5.
 8) THE EXHAUST FOR CLOTHES DRYERS SHALL COMPLY W/ 2010
 FBC-FUEL GAS SEC.614. SUBMIT 2 COPIES OF THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR THE
 DRYERS. SUBMIT MANUF. SPECS TO DETERMINE IF DRYERS ARE
 RESIDENTIAL OR COMMERCIAL.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 9) THE WASHING MACHINES SHALLL BE INSTALLED ON A 3 INCH
 STACK PER 2010 FBC-PLUMBING SEC.406.3.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYERS AND THE WATER HEATER. COMPLY W/2010 FBC-FUEL GAS
 SEC.304.1
 11) SUBMIT DETAILS FOR THE STAND/SUPPORT FOR THE WATER
 HEATER.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHT. P-2 SHOWS THE GAS LINE TO THE WATER HEATER AS
 1" AND ALSO AS 3/4 ". CLARIFY.
 13) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINES PERR 2010 FBC-PLUMBING SEC.1003.6.
 14) SUBMIT VERIFICATION THAT A 3/4" HOT AND COLD WATER
 LINE IS ADEQUATE TO PROVIDE THE PROPER PRESSURE AND
 WATER SUPPLY TO THE 18 WASHING MACHINES. 2010
 FBC-PLUMBING SEC.604.1, 604.3.
 15) ALL GAS EQUIPMENT/APPLIANCES SHALL BE LISTED AND
 LABELED PER 2010 FUEL GAS CODE SEC. 301.3.
 16) GAS PIPING SHALL BE BONDED PER 2010 FBC-FUEL GAS
 SEC.310.
 17) VENTS AND BRANCH VENTS EXCEEDING 40 FEET IN
 DEVELOPED LENGTH SHALL BE INCREASED BY ONE PIPE SIZE IN
 ACCORDANCE WITH 2010 FBC-PLUMBING SEC. 916.2, 916.4.
  
 NOTE:A THOROUGH AND COMPREHENSIVE PLAN REVIEW CANNOT BE
 DONE UNTIL ALL THE ABOVE INFORMATION IS PROVIDED. IN
 ADDITION, APPROVAL FROM THE CITY'S ZONING DEPT. MAY
 REQUIRED FOR THE LOCATION OF THE DRYER AND GAS VENTS
 ONCE DETAILS ARE SUBMITTED.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy