| Plan Review Stops For Permit 15050267 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2015-09-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-09-10 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-09-10 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2015-08-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-25 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2015-08-25 16:29:58 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050267 | | | ADD: 1001 36TH ST. #M33 | | | CONT: TBD | | | TEL: (386)7056 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: TUES. AUG. 25/2015 | | | ACTION: DENIED | | | | | | ) NOTICE:!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA | | | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A | | | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO | | | CORRECT A CODE VIOLATION. | | | | | | | | | | | | | | | 1) COMPLIED. | | | | | | 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR | | | FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW | | | OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR | | | LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART | | | OF THE MAIN WIND FORCE RESISTING SYSTEM. | | | | | | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(C) WALL LOUVERS | | | | | | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 5) COMPLIED> ) . | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-07-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-17 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-17 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2015-07-22 14:58:52 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050267 | | | ADD: 1001 36TH ST. #M33 | | | CONT: TBD | | | TEL: (386)7056 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: FRI. JULY 17/15 | | | ACTION: DENIED | | | | | | 1) THE WALL BETWEEN THE EXISTING LAUNDRY ROOM AND | | | EXISTING ROOM IS TO BE DEMOLISHED, IS THIS A BLOCK | | | WALL, LOAD BEARING WALL, IT APPEARS TO BE DRAWN TO BE A | | | 8 INCH WALL? THE PLANS SHEET A3 APPEAR TO HAVE THE SAME | | | WALL LINE IN THE SAME LOCATION107.2.1.3 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR | | | FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW | | | OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR | | | LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART | | | OF THE MAIN WIND FORCE RESISTING SYSTEM. | | | | | | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(C) WALL LOUVERS | | | | | | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 5) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 | | | | | | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. | | | | | | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4 & ASCE 7-10 | | | | | | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. | | | | | | 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE & | | | NEGATIVE TABLE 1609.2(2) . | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-05-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-05-15 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-05-15 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2015-05-15 09:29:20 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050267 | | | ADD: 1001 36TH ST. #M33 | | | CONT: TBD | | | TEL: (386)7056 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: FRI. JULY 17/15 | | | ACTION: DENIED | | | | | | 1) THE WALL BETWEEN THE EXISTING LAUNDRY ROOM AND | | | EXISTING ROOM IS TO BE DEMOLISHED, IS THIS A BLOCK | | | WALL, LOAD BEARING WALL, IT APPEARS TO BE DRAWN TO BE A | | | 8 INCH WALL? THE PLANS SHEET A3 APPEAR TO HAVE THE SAME | | | WALL LINE IN THE SAME LOCATION107.2.1.3 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR | | | FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW | | | OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR | | | LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART | | | OF THE MAIN WIND FORCE RESISTING SYSTEM. | | | | | | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(C) WALL LOUVERS | | | | | | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 5) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 | | | | | | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. | | | | | | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4 & ASCE 7-10 | | | | | | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. | | | | | | 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE & | | | NEGATIVE TABLE 1609.2(2) . | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2015-09-03 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-03 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-09-03 09:34:07 | APPLICANT INDICATES THE ELECTRICAL DESIGN IS TO BE | | | PERFORMED UNDER PERMIT 15040378. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-07-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-24 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-24 |
Time |
9:15 |
Sent To |
M |
|
| Notes |
| 2015-07-24 10:05:28 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. PROVIDE A LEGIBLE AND ACCURATE SYMBOL LEGEND AS PER | | | FBC | | | 2. YOU SHALL SUBMIT SPECIFIC LOAD CALCS AS REQUIRED BY | | | NEC 220 | | | 3. IDENTIFY ALL EQUIPMENT AND ITS SPECIFIC LOCATION ON | | | THE FLOOR PLANS, ALONG WITH ITS DEDICATED ELECTRICAL | | | CKT. | | | 4. IDENTIFY EVERY ELECTRICAL PANEL SHOWN ON THE FLOOR | | | PLANS WITH ITS RESPECTIVE CIRCUIT DIRECTORY. | | | 5. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING ALL | | | ELECTRICAL PANELS ON SITE. | | | 6. YOU SHALL PROVIDE A LIGHTING PLAN COMPLIANT WITH | | | FBC-E SECTION 505. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-05-14 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2015-05-14 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2015-05-14 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2015-05-14 12:43:00 | PROVIDE LOAD CALCULATION. INDICATED SIZE OF EXISTING | | | PANELBOARD AND SERVICE. VERIFY THE EXISTING SERVICE CAN | | | CARRY THE NEW ELECTRICAL LOADS. PROVIDE A PANEL | | | SCHEDULE SHOWING ALL WIRE AND CIRCUIT SIZES.NEC 215.5, | | | 220.10 | | | | | | SEE ELECTRIC PERMIT #15040378 | | | R. LECKY, ELECTRICAL PLANS EXAMINER |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-08-31 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-08-31 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-08-31 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2015-08-31 14:32:26 | PERMIT # 15050267 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | | THE FIRE DEPARTMENT AFTER ALL ADDITIONAL PLAN REVIEWER | | | COMMENTS HAVE BEEN SATISFIED. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-05-11 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-05-11 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-05-11 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2015-09-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-09-17 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-09-16 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-08-19 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-08-19 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2015-08-19 10:53:14 | 1) THE SUBMITTED VENT DETAIL IS INADEQUATE. SHOW THE | | | TYPE OF VENT ( TYPE B, OR SINGLE WALL,ETC.) IF SINGLE | | | WALL VENT, INDICATE THE THICKNESS OF THE METAL. THE | | | SINGLE WALL VENT SHALL BE CONSTRUCTRED OF GALVANIZED | | | SHEET METAL NOT LESS THAN 0.0304 INCH THICK PER 2010 | | | FBC-FUEL GAS SEC.503.7 AND SHALL BE INSTALLED PER FGC | | | 503.7.3 & 503.7.7. | | | 2) IF VENT IS OTHER THAN SINGLE WALL PIPE, THE VENT | | | SHALL COMPLY WITH 2010 FGC SEC.503.6.4, 503.6.5. | | | 3) THE GAS LINE FROM THE GAS METER TO THE FIRST TEE | | | CONNECTION SHALL BE 1 1/2" PER TABLE 402.4 (2). | | | 4) INDICATE THE TYPE OF PIPE BEING USED FOR GAS THE | | | SYSTEM. | | | 5) THE TYPICAL GAS PIPE DROP SHOW 3 & 6 FT. DROPS TO | | | THE APPLIANCES BUT THE GAS RISER SHOWS 2 & 4 FT. DROPS. | | | CLARIFY. | | | 6) IDENTIFY ON THE FAN LITERATURE THE SPECIFIC MODEL | | | THAT IS BEING USED. WPB AMEND TO FBC SEC.107.2.1. | | | 7) IDENTIFY ON THE MANUF. SPECS THE TYPE OF BACKDRAFT | | | DAMPER BEING INSTALLED.WPB AMEND TO FBC SEC.107.2.1. | | | 8) SUBMIT ADDITIONAL DOCUMENTATION AS TO HOW THE MAKE | | | UP AIR FAN MEETS THE MINIMUM REQUIRED AMOUNT OF | | | COMBUSTION AIR IN ACCORDANCE WITH THE 2010 FGC | | | SEC.304.5,304.6,304.7,304.10,& 304.11. | | | 9) HOW WILL THE FAN OPERATE - IS IT CONNECTED TO A | | | LIGHT SWITCH AND OPERATE WHEN THE SPACE IS BEING USED? | | | WHAT IS THE PURPOSE OF THE EDJ UNIT THAT IS BEING | | | INSTALLED? | | | | | | I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO | | | DISCUSS THE COMMENTS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-07-16 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-16 |
Time |
05:18 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-16 |
Time |
05:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2015-09-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-09-28 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-09-25 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2015-09-25 10:56:58 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2015-09-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-09-17 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-09-03 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-09-03 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-03 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-14 |
Time |
07:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-07-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-24 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-17 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2015-07-23 14:11:56 | PREVIOUS IN-STOP CLOSED BY MISTAKE. B20 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-07-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-17 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-08 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-06-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-09 |
Time |
05:19 |
Rev Time |
|
| Received By |
tklarge |
Date |
2015-05-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-22 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-21 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2015-10-22 10:40:31 | 10/22/2015 | | | IMPACT FEE ASSESSMENT | | | MU-2015-24847 | | | NO FEES DUE! | | 2015-10-22 10:12:16 | JWITMER'S DESK |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-05-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-05-15 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-05-15 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2015-05-15 09:30:04 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2015-09-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-09-28 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-09-28 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2015-09-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-09-14 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-09-14 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2015-09-14 13:55:55 | 3RD REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15050267 | | | 9/14/15 | | | | | | 1) THIS IS THE 3RD SUBMITTAL ON THIS PROJECT AND | | | COMMENTS FROM THE 1ST REVIEW STILL EXIST. I AM | | | REPRINTING THEM HERE. PLEASE CORRECT AND REVISE THE | | | PLAN ACCORDINGLY: | | | 2) (PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY | | | ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. | | | THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING | | | SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE | | | PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR | | | INSTALLATIONS WILL BE NECESSARY.) | | | PLEASE NOTE THAT THE MECHANICAL VENTILATION RATE PER | | | THE TABLE IS 7.5 CFM PER PERSON WITH THE OCCUPANT | | | DENSITY LEVEL 20 PERSONS PER 1000 SQ. FT. SHOW THE | | | CALCULATION ON THE PLANS AND CLARIFY HOW THE SYSTEM | | | WILL FUNCTION (APPARENTLY THE WALL FAN HAS BEEN REMOVED | | | FROM THE PLANS). | | | IF USING THE NATUTURAL VENTILATION METHOD, PLEASE | | | PROVIDE A CALCULATION TO VERIFY COMPLIANCE WITH SECTION | | | 402.2 ( MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE | | | 4 PERCENT OF THE FLOOR AREA BEING VENTILATED). | | | *NOTE: PLEASE REVIEW SECTION 304.9.3 FBC-10 FUEL GAS- | | | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. | | | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S | | | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE | | | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE | | | REQUIRED VENTILATION AIR. | | | IF YOU HAVE ANY QUESTIONS, NEED FURTHER CLARIFICATION, | | | OR WOULD LIKE TO SET UP A MEETING TO HELP EXPEDITE THE | | | PERMITTING PROCESS PLEASE CONTACT ME. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2015-08-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-08-21 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-08-21 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2015-08-21 11:29:57 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15050267 | | | 8/21/15 | | | | | | 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE | | | MANUFACTURER'S SPECS FOR THE GREENHECK LOUVER, AND A | | | VALID FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR | | | THE GREENHECK LOUVER. PLEASE NOTE THAT THE LOUVER CAN | | | PROTECT BOTH THE MAKEUP AIR OPENING AND THE EXHAUST FAN | | | OPENING- CURRENTLY PLAN IS NOT SHOWING HOW THE FAN | | | OPENING WILL BE PROTECTED. PLEASE ADDRESS THIS ISSUE. | | | 2) THE SUBMITTED SPECS FOR THE EXHAUST FAN DO NOT SHOW | | | WHICH OF THE GREENHECK TYPE SE1 FANS WILL BE USED. | | | PLEASE SUBMIT THE CUT SHEETS FOR THAT MODEL ONLY, AND | | | PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN THAT INCLUDES | | | THE MODEL NUMBER, CFM CAPACITY, AND ELECTRICAL DATA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-07-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-24 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-24 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2015-07-24 11:29:24 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | | | 1) THE REQUESTED SUBMITTALS FOR THE DRYERS HAVE NOT | | | BEEN REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL | | | OF RECORD AS REQUESTED: PLEASE COMPLY AND PROVIDE | | | EQUIPMENT SCHEDULES ON THE PLAN AS REQUESTED IN THE 1ST | | | REVIEW. | | | 2) AS REQUESTED IN THE FIRST REVIEW, PROVIDE MAKE-UP | | | AIR CALCULATIONS ON THE PLAN FOR THE DRYERS- (SEE | | | MANUFACTURER'S RECOMMENDATIONS), AND VENTILATION | | | CALCULATIONS FOR THE NEW LAUNDRY ROOM- (TABLE 403.3 | | | FBC-MECHANICAL). SHOW HOW ALL AIR IS BEING SUPPLIED AND | | | CONTROLLED. | | | 3) AS REQUESTED IN THE 1ST REVIEW, PROVIDE FRONT AND | | | PLAN VIEWS OF THE EXHAUST VENTS: INDICATE THE TYPE AND | | | SIZE OF THE DUCTS, LENGTH OF THE CONNECTORS, HEIGHTS OF | | | RISERS, TOTAL RUN CALCULATIONS AND TERMINATION | | | LOCATIONS. | | | 4) SHOW COMPLIANCE WITH SECTION 504.4 FOR REQUIRED | | | BACKDRAFT DAMPERS TO BE INSTALLED AT THE DRYER VENT | | | TERMINATIONS. | | | 5) INDICATE IF THE GAS-FIRED WATER HEATER IS NEW OR | | | EXISTING ON THE PLAN. IF THE UNIT IS NEW, SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER AND | | | VENT SYSTEM, AND PROVIDE A VENTING DIAGRAM. THE VENTING | | | DIAGRAM SHALL SHOW THE TYPE AND SIZE OF VENT PIPE, | | | TOTAL LENGTH OF CONNECTORS AND RISERS, AND TERMINATION | | | LOCATION- REFER TO SECTION 504 FBC-10 FUEL GAS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-06-08 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-06-08 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2015-06-08 17:17:24 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) A COMPLETE REVIEW OF THE PROPOSED PROJECT CANNOT BE | | | COMPLETED WITHOUT SUBMITTAL OF COMPLETE MANUFACTURER'S | | | SPECIFICATIONS FOR THE NEW DRYERS AND VENTS. | | | THE SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE | | | DESIGN PROFESSIONAL OF RECORD- SECTION 614 FBC-10 FUEL | | | GAS. PLEASE NOTE THAT THE CODE CLASSIFIES DRYERS AS | | | EITHER RESIDIENTIAL OR COMMERCIAL, AND THE | | | MANUFACTURER'S MAKE THAT DETERMINATION DEPENDING USAGE. | | | 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE | | | DRYERS, AND CLARIFY IF THE DRYERS WILL BE | | | COIN-OPERATED. | | | 3) INDICATE THE SOURCE OF, AND THE AMOUNT OF MAKE-UP | | | AIR REQUIRED BY THE MANUFACTURER FOR EACH DRYER. | | | 4) PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY | | | ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. | | | THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING | | | SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE | | | PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR | | | INSTALLATIONS WILL BE NECESSARY. | | | 5) PROVIDE FRONT AND PLAN VIEWS OF THE EXHAUST VENTS: | | | INDICATE THE TYPE AND SIZE OF THE DUCTS, LENGTH OF THE | | | CONNECTORS, HEIGHTS OF RISERS, TOTAL RUN CALCULATIONS | | | AND TERMINATION LOCATIONS. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-08-19 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-08-17 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-07-16 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-16 |
Time |
05:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-16 |
Time |
02:40 |
Sent To |
|
|
| Notes |
| 2015-07-16 04:50:32 | 1) SUBMIT A TYPICAL VENT DETAIL FOR THE GAS DRYERS. | | | SHOW THE SIZE, THE TYPE OF VENT, THE HEIGHT OF THE VENT | | | ABOVE FINISH GRADE, | | | 2) SHOW THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING | | | FROM THE POINT OF DELIVERY TO THE FURTHEST OUTLET ON | | | THE SYSTEM. THERE IS OVER-TYPE ON THE GAS RISER SO SOME | | | OF THE PIPE SIZES AND DIMENSIONS CANNOT BE READ.SHOW | | | THE LENGTH OF THE TYPICAL PIPE DROPS TO THE DRYERS. | | | 3) INDICATE THE PSI OF THE GAS COMING INTO THE | | | STRUCTURE. THE PLANS SHOW 5 PSI AT THE METER.IS THIS | | | GOING TO BE THE PSI FOR THE SYSTEM? FOR A 5 PSI SYSTEM, | | | THE FUEL GAS CODE HAS ONLY ONE TABLE AND THAT IS WITH A | | | PRESSURE DROP OF 3.5 PSI. IS THIS THE TABLE YOU ARE | | | USING? IF SO, INDICATE SUCH ON THE GAS PLANS WPB AMEND. | | | TO FBC SEC. 107.3.5.1.5. | | | 4) SHOW THE LOCATION OF ALL LINE GAS PRESSURE REDUCING | | | REGULATORS ( IF APPLICABLE ) AND SHOW THE VENTING OF | | | THE REGULATORS PER 2010 FUEL GAS CODE SEC. 410.3, | | | 410.3.1. ALL REGULATORS SHALL BE ACCESSIBLE. | | | 5) THE GAS RISER SHOWS THE GAS LINE TO THE WATER HEATER | | | AS 1 INCH AND THE PLAN VIEW SHOWS IT AS 3/4 ". WHICH IS | | | IT? | | | 6) HOW WAS THE SIZE OF THE LINT TRAP DETERMINED? SUBMIT | | | FLOW CALCULATIONS CONFIRMING THAT INTERCEPTOR IS OF | | | ADEQUATE CAPACITY FOR THIS SYSTEM. 2010 FPC 1003.2. | | | 7) VENTS AND BRANCH VENTS EXCEEDING EXCEEDING 40 FEET | | | IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE PIPE SIZE | | | FOR THE ENTIRE LENGTH OF THE VENT PIPE IN ACCORDANCE | | | WITH 2010 FPC SEC.916.2, 916.4. | | | 8) THE GAS PIPING SHALL BE BONDED PER 2010 FGC | | | SEC.310.1. | | | 9) EXHAUST DUCTS FOR CLOTHES DRYERS SHALL BE EQUIPPED | | | WITH BACKDRAFT DAMPERS.2010 FGC SEC.614.4. | | | 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | | DRYERS. 2010 FGC SEC.304.1. | | | 11) SHT. M-1 SHOWS 10 DRYERS BUT ONLY 8 EXHAUSTS. | | | CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-09 |
Time |
05:19 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-09 |
Time |
04:13 |
Sent To |
|
|
| Notes |
| 2015-06-08 15:28:45 | 1) SUBMIT A DETAIL FOR THE GAS VENT FOR THE WATER | | | HEATER. SHOW THE SIZE, TYPE OF VENT, HEIGHT OF VENT | | | ABOVE ROOF. SUBMIT A ROOF PLAN SHOWING THE LOCATION OF | | | THE VENT IN RELATION TO AIR INTAKES,PARAPET WALLS (IF | | | APPLICABLE) .WPB AMEND. TO 2010 FBC SEC.107.2.1, 2010 | | | FBC-FUEL GAS SEC.502,503. | | | 2) SUBMIT A TYPICAL VENT DETAIL FOR THE GAS DRYERS.SHOW | | | THE SIZE, TYPE OF VENT, HEIGHT OF VENT ABOVE ROOF. | | | SUBMIT A ROOF PLAN SHOWING THE LOCATION OF THE VENT IN | | | RELATION TO AIR INTAKES, PARAPET WALLS (IF | | | APPLICABLE).WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 3) SHOW THE TYPICAL SHUTOFF VALVES ON THE WATER RISER | | | AND ON THE WATER HEATER.WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 4) INDICATE THE TYPICAL SIZE OF THE WATER RISER TO THE | | | WASHING MACHINES.WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 5) INDICATE THE SIZE OF THE WATER HEATER IN WATER | | | CAPACITY. (GALLONS).WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 6) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR | | | PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK | | | BEING DONE. | | | 7) SUBMIT A GAS RISER DIAGRAM FOR REVIEW. THE RISER | | | DIAGRAM SHALL SHOW THE BTU LOAD OF EACH APPLIANCE, THE | | | TOTAL BTU LOAD ON THE GAS SYSTEM, THE DEVELOPED LENGTH | | | OF PIPING FROM THE GAS METER TO THE FURTHEST GAS | | | OUTLET,THE LENGTH OF EACH SECTION OF PIPE, THE TYPE OF | | | PIPE BEING INSTALLED, THE PSI OF THE GAS SYSTEM, | | | MANUFACTURER'S SPECIFICATION SHEETS FOR ALL GAS | | | EQUIPMENT/ APPLIANCES, THE LOCATION OF SHUTOFF VALVES, | | | THE LOCATION OF ALL PRESSURE REGULATORS. INDICATE THE | | | APPLICABLE GAS PIPE SIZING TABLE USED FOR THE DESIGN OF | | | THE GAS SYSTEM. 201 FBC-FUEL GAS SEC.402.3.WPB AMEND. | | | TO FBC SEC. 107.3.5.1.5. | | | 8) THE EXHAUST FOR CLOTHES DRYERS SHALL COMPLY W/ 2010 | | | FBC-FUEL GAS SEC.614. SUBMIT 2 COPIES OF THE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR THE | | | DRYERS. SUBMIT MANUF. SPECS TO DETERMINE IF DRYERS ARE | | | RESIDENTIAL OR COMMERCIAL.WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 9) THE WASHING MACHINES SHALLL BE INSTALLED ON A 3 INCH | | | STACK PER 2010 FBC-PLUMBING SEC.406.3. | | | 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | | DRYERS AND THE WATER HEATER. COMPLY W/2010 FBC-FUEL GAS | | | SEC.304.1 | | | 11) SUBMIT DETAILS FOR THE STAND/SUPPORT FOR THE WATER | | | HEATER.WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 12) SHT. P-2 SHOWS THE GAS LINE TO THE WATER HEATER AS | | | 1" AND ALSO AS 3/4 ". CLARIFY. | | | 13) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING | | | MACHINES PERR 2010 FBC-PLUMBING SEC.1003.6. | | | 14) SUBMIT VERIFICATION THAT A 3/4" HOT AND COLD WATER | | | LINE IS ADEQUATE TO PROVIDE THE PROPER PRESSURE AND | | | WATER SUPPLY TO THE 18 WASHING MACHINES. 2010 | | | FBC-PLUMBING SEC.604.1, 604.3. | | | 15) ALL GAS EQUIPMENT/APPLIANCES SHALL BE LISTED AND | | | LABELED PER 2010 FUEL GAS CODE SEC. 301.3. | | | 16) GAS PIPING SHALL BE BONDED PER 2010 FBC-FUEL GAS | | | SEC.310. | | | 17) VENTS AND BRANCH VENTS EXCEEDING 40 FEET IN | | | DEVELOPED LENGTH SHALL BE INCREASED BY ONE PIPE SIZE IN | | | ACCORDANCE WITH 2010 FBC-PLUMBING SEC. 916.2, 916.4. | | | | | | NOTE:A THOROUGH AND COMPREHENSIVE PLAN REVIEW CANNOT BE | | | DONE UNTIL ALL THE ABOVE INFORMATION IS PROVIDED. IN | | | ADDITION, APPROVAL FROM THE CITY'S ZONING DEPT. MAY | | | REQUIRED FOR THE LOCATION OF THE DRYER AND GAS VENTS | | | ONCE DETAILS ARE SUBMITTED. | | | | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|