Plan Review Details - Permit 15050262
Plan Review Stops For Permit 15050262
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 09:19 Sent To  
Notes
2015-10-06 10:14:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: LANDMARK
 CONTACT: JORGE COSTAS
 TEL: (305)665-1146
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. OCT.06/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/BLDG TYPE: III-B/ R2
  
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) PROVISO: NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A-B) COMPLIED.
  
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" .
  
 3E) 3RD REQUEST!!! NOTE TO DATE NO PERMIT APPLICATION
 WHERE THE OWNER HAS SIGNED AND THEIR SIGNATURES
 NOTARIZED. AHOLD WILL BE PUT ON THE PERMIT NOT TO ISSUE
 UNTIL THE OWNERS SIGNATURE IS ON THE PERMIT
 APPLICATION.
  
 3F)NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 5-9) COMPLIED
  
 10) SHEET A-200A:
 10A) COMPLIED.
  
 10B) REVISION REQUIRED. 3RD REQUEST. BETWEEN DWELLING
 UNITS AND DWELLING UNITS AND COMMON AREAS WALL TYPE W5
 HAS BEEN INDICATED A 6 INCH CONCRETE REINFORCED WALL
 WITH NO INSULATION. PLEASE PROVIDE DOCUMENTATION THAT
 COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
 RESPONSE: WALL SOUND INSULATION THAT HAS ALREADY BEEN
 TESTED, IS FOUND ON SHEET A9.04 ALSO WALL TYPE SHEET
 A-8.01. NOTE THESE ARE SALES BROCHURES; THEY ARE NOT
 THE ACTUAL TEST. PROVIDE TEST REPORTS.
  
  
  
 11-19) COMPLIED.
  
 20)(A)REVISION REQUIRED: 3RD REQUEST. SHEET A4.02
 INDICATES 6 INCH CONCRETE SLAB. SHEET A-9.04 INDICATES
 THE USE OF (2) FLOOR INSULATION PRODUCTS, DB-4LOORING
 INSULATION, AND QT SCU 4002 PLEASE SUBMIT THE REPORTS
 FOR COMPLIANCE WITH 20A-20C, MISSING FLAME SPREAD.
  
 20)(B) REVISION REQUIRED: 3RD REQUEST. SHEET A-9.04
 ALSO SHOWS A WALL INSULATION TYPE DB-3, THIS IS A SALES
 BROCHURE PLEASE SUBMIT TEST INFORMATION, WALL
 INSULATION WILL NEED TO COMPLY WITH 1207.2 THE SALES
 BROCHURE SUBMITTED IS FOR WOOD AND METAL STUDS, NEVER
 TESTED ON A 6 INCH CONCRETE WALL. WALL INSULATION WILL
 NEED TO MEET 1207.2 ASTM E 90 AND SECTION 2010 FBC-B
 719.2 CONCEALED INSULATION FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE DEVELOPMENT OF 450.
  
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21-22) COMPLIED.
  
 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 23A) )PROVISO: FOR GLAZED PRODUCT APPROVALS, IDENTIFY
 THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED OPENING,
 IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE
 INSTALLED, PRESSURES, AND FASTENERS.
  
 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF
 TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-20 Cont ID  
Sent By jwitmer Date 2015-08-20 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2015-08-20 Time 06:23 Sent To  
Notes
2015-08-20 08:04:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: THURS. AUG. 20/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 3 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A) COMPLIED. ELECTRONIC MEDIA: SUBMITTED AN INDEX.
  
 2A-B) COMPLIED
  
 2C) THE ELECTRONIC PLANS SUBMITTED 370 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED OUT OF THE SET OF DRAWINGS THAT DID
 NOT PERTAIN TO THAT BUILDING AND DETAIL SHEETS, DETAILS
 NOT PERTAINING TO THAT BUILDING STRUCK THROUGH.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE UNIFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. THIS
 CODE SECTION IS FOR RECORD RETENTION BUT THE REALITY OF
 THIS IS, THE WAY THESE PLANS WERE SUBMITTED, IT IS VERY
 DIFFICULT TO FIND WHERE TO LOOK FOR CODE
 COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 2ND REQUEST. THE RESPONSE INDICATES A WRITTEN
 INSPECTION PLAN WAS SUBMITTED WITH THE RESPONSE, WHERE
 IS IT LOCATED. NOTE DO NOT TIE ANY OTHER DOCUMENTS WITH
 THE WRITTEN RESPONSE, THEY SHOULD BE PUT INTO THE
 DOCUMENT FOLDER.
 THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) 2ND REQUEST. THE PERMIT NUMBER FROM BUILDING # 1
 WAS RESUBMITTED. IF THE 1ST SHEET OF THE THRESHOLD
 AGREEMENT HAS ALL THREE PERMIT NUMBERS AND ADDRESSES
 THE ONE DOCUMENT WILL WORK FOR ALL THREE BUILDINGS.
 THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D)COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) NOTE TO DATE NO CONTRACTOR HAS SUBMITTED A PERMIT
 APPLICATION WHERE THE OWNER AND QUALIFIER HAVE SIGNED
 AND THEIR SIGNATURES NOTARIZED.
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 3F) NOTICE ONLY! NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $3,752,718.00 IS LOW. THIS
 REVIEW IS FOR A 4 STORY R2 BUILDING TYPE III-B FOR
 BUILDING # 3, THE VALUATION IS FIGURED $118.01 FROM THE
 IIC TABLE FEB. 01/ 2015.
 CALCULATED VALUE:
 BLDG. #3 TYPE III-B 61,409 SQ. FT. X $118.01=
 $7,246,876.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) 2ND REQUEST. SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6)2ND REQUEST. THE PERMIT APPLICATION CAME IN AS A TBD,
 TO BE DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF
 THIS PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE
 CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 4
 STORY BUILDING. FLORIDA S. S. 489.113.
  
 7) 2ND. SHEET A-0.01: UNDER THE HEADING CONSTRUCTION
 TYPE IS FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS
 NOT CLEAR SINCE THERE IS BLDGS. 2 & 3 ON THE SAME LINE
 AS BUILDING # 1. THE REAL QUESTION IS WILL THERE BE (2)
 TYPES OF FIRE SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN
 COMPLIANCE WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 &
 3 HAVE THE SAME TYPE OF FIRE SPRINKLERS OR WILL THEY
 HAVE A NFPA 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF
 BOTH SYSTEMS ARE GOING TO BE INSTALLED PLEASE LIST THEM
 IN THE BUILDING MATRIX AS SUCH.
  
 8-9) COMPLIED.
  
 10A-B) COMPLIED
  
 10C) PROVISO: RESPONSE INDICATES ONSITE TESTING WILL
 TAKE PLACE FOR CODE COMPLIANCE WITH: BETWEEN DWELLING
 UNITS AND DWELLING UNITS AND COMMON AREAS WALL TYPE W9
 HAS BEEN INDICATED AS A 6 INCH METAL STUD WALL, SOUND
 INSULATION BLANKET AND 5/8 INCH FIRE-CODE GYPSUM.
 PLEASE PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010
 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
 11-14)COMPLIED.
  
 15) 2ND REQUEST. THIS COMMENT STANDS FOR ALL 3 BUILDING
 ON ALL ELEVATED FLOORS. SHEET A-9.03 DETAIL # 6 SHOWS A
 WATERPROOFING DETAIL OF THE COMMON PEDESTRIAN WALKWAYS
 FOR ALL BUILDINGS, IS THE SHERCRETE BASE AND TOP COAT
 ALSO TO ACT AS THE FLOOR INSULATION THAT IS REQUIRED
 UNDER SECTION FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 ALL COMMON AREAS WILL NEED TO COMPLY WITH STRUCTURE
 BORNE SOUND. PLEASE PROVIDE ALL TESTING REPORTS FOR
 THIS PRODUCT.
  
 16) PROVISO: RESPONSE INDICATES ONSITE TESTING WILL
 TAKE PLACE FOR CODE COMPLIANCE WITH:
 2010 FBC-B 1207.3. STRUCTURE BORNE SOUND.
 2010 FBC-B 1207.2. AIR-BORNE SOUND.
 NOTE CODE COMPLIANCE WITH
 SHEET A-9.04 INDICATES THE USE OF (2) FLOOR INSULATION
 PRODUCTS, EASY MAT AND KNAUF INSULATION, PLEASE SUBMIT
 THE REPORTS FOR COMPLIANCE WITH FBC-B 719.2 FOR CODE
 COMPLIANCE : TYPE III-TYPE V CONSTRUCTION:
 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 16A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 16C) NOTICE!!! DIFFERENT THAN TYPE I TYPE II BLDGS.
 TYPE III-TYPE V CONSTRUCTION:
 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 17-18) COMPLIED
  
 19A)2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 19B) WILL PRODUCT APPROVALS FOR ,WINDOWS, DOORS, EXT.
 WALL LOUVERS, ROOFING COMPONENTS BE SUBMITTED FOR THE
 WORST CASE SCENARIO BUILDING # 5 OR WILL THE APPROVALS
 BE DIFFERENT FOR BUILDING # 1 THAN BUILDINGS 2 & 3.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 20A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF
 GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS
 ARE USED, CIRCLE THE MULLION TO BE INSTALLED,
 PRESSURES, AND FASTENERS.
  
 20B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE
 SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY
 REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND
 SIGNED & SEALED CALCULATIONS.
  
 20C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO
 BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED,
 IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES.
  
 20D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR
 CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT
 APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR
 THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING
 FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 21) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 22) COMPLIED
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-20 Cont ID  
Sent By jwitmer Date 2015-06-20 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2015-06-20 Time 08:01 Sent To  
Notes
2015-06-20 10:49:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. JUNE 20/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 3 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A) COMPLIED. ELECTRONIC MEDIA: SUBMITTED AN INDEX.
  
 2B) 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. THIS PLAN DOES NOT
 FOLLOW THE NAMING CONVENTION FOR EACH PAGE WITHIN THE
 SET OF PLANS AND SHOULD HAVE BEEN DENIED AT TIME OF
 ELECTRONIC SUBMISSION. THE ARCHITECTURAL SHEETS ARE NOT
 IN ORDER BECAUSE OF THE NAMING CONVENTION WAS NOT
 FOLLOWED, THE A1. SHEETS JUMP TO A-10 SERIES TO A-11
 SERIES THEN TO A-2SERIES, THEY DO NOT FOLLOW THE
 SUBMITTED INDEX SHEET!!!!! THE PLANS DO NOT MEET THE
 CITY STANDARD FOR ELECTRONIC MEDIA REQUIRED BY THE
 ELECTRONIC PLAN REVIEW LIBERIAN, CAROLINE PUELL. PLEASE
 CONTACT MS. PUELL AT 805-6659 FOR FURTHER INSTRUCTIONS
 AND CLARIFICATIONS.
  
 2C) THE ELECTRONIC PLANS SUBMITTED 370 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED OUT OF THE SET OF DRAWINGS THAT DID
 NOT PERTAIN TO THAT BUILDING AND DETAIL SHEETS, DETAILS
 NOT PERTAINING TO THAT BUILDING STRUCK THROUGH.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE UNIFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. THIS
 CODE SECTION IS FOR RECORD RETENTION BUT THE REALITY OF
 THIS IS, THE WAY THESE PLANS WERE SUBMITTED, IT IS VERY
 DIFFICULT TO FIND WHERE TO LOOK FOR CODE
 COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $3,752,718.00 IS LOW. THIS
 REVIEW IS FOR A 4 STORY R2 BUILDING TYPE III-B FOR
 BUILDING # 3, THE VALUATION IS FIGURED $118.01 FROM THE
 IIC TABLE FEB. 01/ 2015.
 CALCULATED VALUE:
 BLDG. #3 TYPE III-B 61,409 SQ. FT. X $118.01=
 $7,246,876.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6) THE PERMIT APPLICATION CAME IN AS A TBD, TO BE
 DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF THIS
 PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE
 CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 4
 STORY BUILDING. FLORIDA S. S. 489.113.
  
 7) SHEET A-0.01: UNDER THE HEADING CONSTRUCTION TYPE IS
 FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR
 SINCE THERE IS BLDGS. 2 & 3 ON THE SAME LINE AS
 BUILDING # 1. THE REAL QUESTION IS WILL THERE BE (2)
 TYPES OF FIRE SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN
 COMPLIANCE WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 &
 3 HAVE THE SAME TYPE OF FIRE SPRINKLERS OR WILL THEY
 HAVE A NFPA 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF
 BOTH SYSTEMS ARE GOING TO BE INSTALLED PLEASE LIST THEM
 IN THE BUILDING MATRIX AS SUCH.
  
 8) SHEET A-1.01;
 8A) DETAILS 3 AND 3.1 THE ACCESSIBLE & STANDARD PARKING
 DETAILS AND PARALLEL PARKING STRIPPING DETAILS ARE
 GOING TO NEED TO COMPLY WITH 2010 FBC-ACCESSIBILITY
 CODE ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. SEE
 WEST PALM BEACH MUNI-CODE SECTION 94-485 STALL PAINTING
 DETAIL.
  
 8B) DETAIL # 10. THE FENCE DESIGN IS INDICATED TO MEET
 THE FBC-B 2010 ASCE 7-05. PLEASE NOTE THE ASCE -05 WAS
 IN THE 2007 FBC-B. THE 2010 FBC-B SECTION 1609. 1.1 THE
 DETERMINATION OF WIND USES THE ASCE 7-10.
  
 9) 9) SHEET A-8.01 IDENTIFIES TYPE OF WALLS WITH WALL
 TAG ALPHA- NUMERICAL WALL TAGS FOR FIRE RESISTANCE
 RATINGS HOW DOES SHEET A-11.00 SERIES OF DRAWINGS
 RELATE TO SHEET A-8.01. SHEET A-8.01 DOES NOT HAVE
 BLOCK TYPE INFORMATION STATING THEY ARE A T012 OR T007
 TYPE BLOCK?
 10) SHEET A-2.11- A-2.15:
 10A) THIS COMMENT WILL STAND FOR ALL DOORS ON ALL
 FLOORS. THE FRONT ENTRY DOORS DO NOT INDICATE A DOOR
 IDENTIFICATION TAG, PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B TABLE 715.4.
  
 10B) BETWEEN DWELLING UNITS AND DWELLING UNITS AND
 COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED A 6 INCH
 CONCRETE REINFORCED WALL WITH NO INSULATION. PLEASE
 PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 FBC-B
 1207.2 HAS BEEN ACHIEVED.
  
 10C) ) BETWEEN DWELLING UNITS AND DWELLING UNITS AND
 COMMON AREAS WALL TYPE W9 HAS BEEN INDICATED AS A 6
 INCH METAL STUD WALL, SOUND INSULATION BLANKET AND 5/8
 INCH FIRE-CODE GYPSUM. PLEASE PROVIDE DOCUMENTATION
 THAT COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN
 ACHIEVED.
  
 11) SHEET A-2.14 ) PLEASE SHOW HOW COMPLIANCE WITH
 1209.2 WILL BE ACHIEVED 20 INCH X 30 INCH ATTIC ACCESS.
 12) SHEET A-2.15. ) PLEASE SHOW COMPLIANCE WITH THE
 UPPER 50% OF REQUIRED ROOF VENTS. THE HIPPED ROOFS SHOW
 SOFFIT VENTS BUT THERE IS NO NOTATION OF CODE
 COMPLIANCE FOR 2010 FBC-B 1203.2 WITH 50% OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET ABOVE THE EAVE OR CORNICE
 VENTS, WITH THE BALANCE OF THE REQUIRED VENTILATION
 PROVIDED BY THE EAVE VENTS.
  
 13) SEE SHEET 2014- 16 S.P.-A7.00-A7.03, THIS SHEET IS
 LOADED TWICE. DISCREPANCY .
  
 14) SHEET A-7-06 TRASH CHUTE;
 14A) DETAIL # 1 PLEASE PROVIDE DETAIL OF THE 2ND FLOOR
 BOTTOM OF SHAFT ENCLOSURE FIRE PROOFING OF HORIZONTAL
 ASSEMBLY. FBC-B 713.4.1.1 THROUGH PENETRATIONS.
  
 14 B) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS ON
 THE HORIZONTAL DAMPER THAT CLOSES OFF THE TRASH CHUTE
 FROM THE REMAINDER OF THE TERMINATION ROOM. FBC-B
 708.13.1. THIS MAY BE A HEAT ACTIVATED CLOSING DEVICE
 SHALL BE PERMITTED BETWEEN THE SHAFT AND THE
 TERMINATION ROOM.
  
 14C) DETAIL C DOES INDICATE A FIRE SPRINKLER RISER
 WITHIN THE SHAFT BUT NO COMPLIANCE WITH FBC-B
 903.2.11.2. CHUTES EXTENDING 3 OR MORE FLOORS SHALL
 HAVE ADDITIONAL SPRINKLER HEADS AT ALTERNATING FLOORS
 AND AT THE TOP OF THE SHAFT.
  
 15) SHEET A-9.03 DETAIL # 6 SHOWS A WATERPROOFING
 DETAIL OF THE COMMON PEDESTRIAN WALKWAYS FOR ALL
 BUILDINGS, IS THE SHERCRETE BASE AND TOP COAT ALSO TO
 ACT AS THE FLOOR INSULATION THAT IS REQUIRED UNDER
 SECTION FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 ALL COMMON AREAS WILL NEED TO COMPLY WITH STRUCTURE
 BORNE SOUND. PLEASE PROVIDE ALL TESTING REPORTS FOR
 THIS PRODUCT.
  
 16) SHEET A-9.04 INDICATES THE USE OF (2) FLOOR
 INSULATION PRODUCTS, EASY MAT AND KNAUF INSULATION,
 PLEASE SUBMIT THE REPORTS FOR COMPLIANCE WITH:
  
 16A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 16C) NOTICE!!! DIFFERENT THAN TYPE I TYPE II BLDGS.
 TYPE III-TYPE V CONSTRUCTION:
 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 17) SHEET S-3.02 UNDER THE HEADING WINDLOAD PRESSURES
 FOR WINDOWS AND DOORS, THE PLANS DO NOT INDICATE THE
 MEAN ROOF HEIGHT THESE PRESSURE WERE TAKEN FOR,
 BUILDING 1 IS A (5) STORY WHEREAS BUILDINGS 2 & 3 ARE
 BOTH 4 STORY BUILDINGS. DEFINITIONS, CHAPTER 2. MEAN
 ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT AND
 THE HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE,
 EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF ANGLE OF
 LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD).
  
 18) SHEET S-3.02 COMPONENTS AND CLADDING THE ROOF
 PRESSURES FOR ROOF ZONES 1,2 & 3 WERE NOT PROVIDED FOR
 10 SQ. FT. PLEASE ALSO NOTE THERE ARE 2 MEAN ROOF
 HEIGHTS TO CONSIDER, THE 5 STORY AND 4 STORY. THE OTHER
 ISSUE IS THE PRESSURES FOR THE FLAT ROOFS AS WELL AS
 FOR THE SLOPED ROOF. FBC-B 1609.1.5 & 1609.1.2.3.1.
  
 19A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 19B) WILL PRODUCT APPROVALS FOR ,WINDOWS, DOORS, EXT.
 WALL LOUVERS, ROOFING COMPONENTS BE SUBMITTED FOR THE
 WORST CASE SCENARIO BUILDING # 5 OR WILL THE APPROVALS
 BE DIFFERENT FOR BUILDING # 1 THAN BUILDINGS 2 & 3.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 20A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF
 GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS
 ARE USED, CIRCLE THE MULLION TO BE INSTALLED,
 PRESSURES, AND FASTENERS.
  
 20B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE
 SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY
 REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND
 SIGNED & SEALED CALCULATIONS.
  
 20C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO
 BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED,
 IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES.
  
 20D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR
 CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT
 APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR
 THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING
 FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 21) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 22) LIFE SAFETY SHEETS COMMON STATEMENT FOR ALL
 BUILDINGS AND ALL FLOORS. THE ROOMS THAT HAVE A
 FRACTION OF AN OCCUPANT IS ROLLED DOWN. THE RULE IS TO
 ROLL UP TO THE NEXT FULL OCCUPANT. EXAMPLE IS UNIT A,
 648/200= 4 X 3 UNITS= 12 OCCUPANTS NOT 10.
 FLORIDA BUILDING CODE INFORMAL INTERPRETATION 5479
 TUES. DEC. 17/2007. OCCUPANTS ONLY COME IN AS A HOLE,
 ALWAYS ROUND UP.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 15:39 Rev Time 0.00
Received By albarran Date 2015-10-07 Time 13:38 Sent To  
Notes
2015-10-07 15:40:06REVIEWED AS A PART OF PERMIT 15050261

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-25 Cont ID  
Sent By albarran Date 2015-09-25 Time 15:44 Rev Time 0.00
Received By skennedy Date 2015-09-22 Time 09:33 Sent To  
Notes
2015-09-25 15:44:34SEE MIKE ALBARAN'S COMMENTS ON 15050261

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-19 Cont ID  
Sent By albarran Date 2015-06-19 Time 09:35 Rev Time 0.00
Received By albarran Date 2015-06-15 Time 09:06 Sent To  
Notes
2015-06-19 09:35:32BECAUSE YOU ARE USING THE SAME PLANS FOR THIS AS FOR
 PERMIT #15050263, THE ELECTRICAL PLAN REVIEW COMMENTS
 ARE EXACTLY THE SAME.
  
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER FOR THE CITY OF WEST PALM BEACH HAVE COMPLETED
 THE REVIEW OF THE ABOVE MENTIONED PERMIT. BELOW ARE THE
 COMMENTS WITH REGARDS TO THE CORRECTIONS NOTED. AS THIS
 WAS A PAGE BY PAGE REVIEW, YOU WILL NOTICE REPEATED
 COMMENTS ON EACH RESPECTIVE PAGE. EACH OF THE COMMENTS
 NOTED HAVE BEEN CLOUDED OR IN SOME WAY IDENTIFIED IN A
 RED LAYER ON THE DIGITAL PLANS WHICH WERE REVIEWED
 USING PROJECTDOX.
  
 PG. E1.00, E.4.00A
 THE FOLLOWING NOTE SHALL BE ADDED WITH REGARDS TO THE
 BACKGROUND AUDIO.
 1. ALL BACKGROUND AUDIO SHALL BE MUTED VIA THE FACP IN
 THE EVENT OF AN ALARM CONDITION.
 PG. E1.10
 THOUGH THIS IS A PHOTOMETRIC SHEET, THE FOLLOWING IS A
 SUGGESTION AND MAYBE A COMMENT WHICH MAY BE ADDED
 SOMEWHERE ON THE PLANS TO AVOID PROBLEMS LATER.
 1. POOL CONTRACTOR TO COORDINATE W/GC TO AVOID FUTURE
 ENCROACHMENT INTO NEC REGULATED POOL AREA REQUIRED BY
 NEC 680.10 WHICH PROHIBITS ANY NON-POOL RELATED
 RACEWAYS WITHIN 5' OF POOL'S EDGE.
 PG. E2.01A, E2.01B, E2.02A, E2.02B, E2.03A, E2.03B,
 E2.07, E2.08, E2.12, E2.13,
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 PG. E2.01C, E2.02C, E2.03C, E2.04C, E2.07A, E2.08A,
 E2.09A, E2.12A, E2.13A, E2.14A
 1. ON EVERY FLOOR ABOVE THE GROUND LEVEL, THE STAIRS
 ARE A PART OF THE EMERGENCY EGRESS, AND SHOULD BE
 ILLUMINATED ACCORDINGLY AND INCLUDED AS SUCH.
 PG. E2.04A,
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS.
 DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE
 REQUIRED.
 3. THIS SPACE REQUIRES LIGHTING AS PER NEC
 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR
 EMERGENCY EGRESS AS WELL.
 PG. E2.04B, E2.09, E2.14
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS.
 DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE
 REQUIRED.
 3. THIS SPACE REQUIRES LIGHTING AS PER NEC
 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR
 EMERGENCY EGRESS AS WELL.
 4. THIS UNIT IS FURTHER THAN THE ALLOWABLE DISTANCE
 FROM THE SERVICE OUTLET PER NEC 210.63.
 PG. E2.06A, E2.11A,
 1. THOUGH ON THE GROUND FLOOR, THESE STAIRS SHALL BE
 CONSIDERED A PART OF THE EMERGENCY EGRESS.
 PG. E3.00
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 PG. E3.01, E3.02 (TYPICAL TO BOTH UNITS)
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK
 THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP
 4. NEC 210.52.(A)(2) REQUIRES AN OUTLET ON A WALL SPACE
 OF 2' OR LARGER
 5. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A
 WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE
 SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
 PG. E3.03 (TYPICAL TO BOTH UNITS)
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK
 THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP
 4. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A
 WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE
 SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
 5. HERE WE HAVE A PROBLEM:
 A) FBC-R 314.3(2) REQUIRES THAT THE SMOKE DETECTOR
 OUTSIDE THE BEDROOM BE IN THE IMMEDIATE AREA.
 B) NFPA 72 SECTION 29.8.3.4(6) REQUIRES THAT A SMOKE
 DETECTOR INSTALLED INSIDE OF OR WITHIN 3' OF THE DOOR
 OF THE BATHROOM BE LISTED FOR THE PURPOSE.
 THEREFORE THERE SHALL BE A PROPERLY LISTED SMOKE
 DETECTOR PLACED IN THIS AREA TO PROTECT THESE TWO
 BEDROOMS
 PG. E4.00B
 1. EXIT LIGHT ILLUMINATED ON BOTH SIDES REQUIRED HERE.
 2. EXIT LIGHT DUAL ARROWS REQUIRED HERE
 3. THIS AREA IS PART OF THE EMERGENCY EGRESS AND THUS
 SHALL BE ILLUMINATED AS SUCH.
 PG. E4.01, E4.03, E4.05, E4.06,
 1. INCORRECTLY MENTIONED ARC-FLASH (ARC-FLASH
 PROTECTION AS PER NEC 110.16)
 PG. E4.07, E4.08,
 1. THERE APPEARS TO BE CLEARANCE ISSUES IN VIOLATION OF
 NEC 110.26 BETWEEN THE OUTLET ON THE WALL AND THE
 COMPACTING APPARATUS.
 PG. E5.01, E5.02, E5.03,
 1. AS PER NEC 230.8, UNDERGROUND SERVICE RACEWAYS SHALL
 BE SEALED AS INDICATED IN 300.5.
 2. ALL SPARE UNDERGROUND RACEWAYS SHALL BE SEALED AS
 WELL.
 3. PANELBOARDS & METER SOCKETS SHALL BE MARKED AS
 INDICATED BY NEC 110.16 FOR ARC-FLASH PROTECTION.
 PG. E5.06
 1. THE QUOTED SECTION DOES NOT EXIST IN THE 2008
 EDITION OF THE NEC. PLEASE CORRECT ACCORDINGLY
 PG. E6.00, E6.01,
 1. FIRE ALARM CIRCUITS SHALL COMPLY WITH BOTH NEC 760 &
 NFPA 72, SECTION 10.6.5
 2. SEE PG. E6.02, FOR PANEL ?CH? SCHEDULE.
 3. CORRECT THIS LABEL DESIGNATION LABEL
 4. PER NEC 4322.52, ELECTRIC DRINKING FOUNTAINS SHALL
 BE ON A GFI CIRCUIT (PG. E6.02)
 PG. FA1.00, FA2.00
 1. SEPARATE PERMIT & SUBMITTAL REQUIRED FOR FIRE ALARM
 WORK
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-08-25 Cont ID  
Sent By mgonzale Date 2015-08-25 Time   Rev Time 1.00
Received By mgonzale Date 2015-08-25 Time   Sent To ENG
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-05-21 Cont ID  
Sent By cranford Date 2015-05-21 Time 10:23 Rev Time 0.00
Received By cranford Date 2015-05-21 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-07 Cont ID  
Sent By wjolin Date 2015-10-07 Time 12:48 Rev Time 0.00
Received By wjolin Date 2015-10-07 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-08-13 Cont ID  
Sent By wjolin Date 2015-08-13 Time 09:04 Rev Time 0.00
Received By wjolin Date 2015-08-13 Time 09:04 Sent To  
Notes
2015-08-13 09:04:47PERMIT #15050261 - 838 ADAMS STREET (66 UNITS)
 PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS)
 PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - THE FIRE DEPARTMENT REQUIRES PLANS
 AND PERMITS FOR ALL CONSTRUCTION RELATED TRAILERS AND
 MODULAR BUILDINGS. ADDITIONALLY PER NFPA 241- STANDARD
 FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS, SECTION 4.2: TEMPORARY OFFICES,
 TRAILERS, AND OTHER FACILITIES OF COMBUSTIBLE
 CONSTRUCTION OR HOUSING COMBUSTIBLE CONTENTS SHALL BE
 SEPARATED FROM ADJACENT BUILDINGS, TRAILERS OR
 STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. PER TABLE
 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - PER NFPA 241 SECTION 4.2.2:
 DETACHMENT BETWEEN TEMPORARY STRUCTURES, ADEQUATE
 TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND PORTABLE
 EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET PM-1: PER SECTION 18.2.3.5.3
 (NFPA 1), FIRE LANES SHALL BE MARKED WITH FREESTANDING
 SIGNS READING, "FIRE LANE - NO PARKING BY ORDER OF THE
 FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART. FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: FIRE MAINS SUPPLYING TWO
 OR MORE FIRE HYDRANTS WILL NEED TO BE LOOPED AND WILL
 NOT BE PERMITTED TO TERMINATE AT A DEAD END BLOWOFF
 CAP.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: THE FIRELINE BACKFLOW
 PREVENTERS SHALL COMPLY WITH NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.01A & SHEET E2.01B: PROVIDE
 TWO ADDITIONAL EXIT SIGNS IN THE EXIT ACCESS CORRIDOR
 NEAR COLUMN INTERSECTION B.1/1.2. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.07: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET E2.12: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT: SHEET FP2.04 NOW INCLUDES A STATEMENT
 THAT SPRINKLERS ARE BEING REQUIRED BY THE LOCAL
 JURISDICTION. THIS IS AN INCORRECT STATEMENT;
 COMBUSTIBLE CONCEALED ROOF SPRINKLER PROTECTION IS
 REQUIRED BY NFPA 13 SECTION 8.15. SHEET FP2.05 HAS NOT
 BEEN CORRECTED AT ALL.
 ORIGINAL COMMENT - SHEET FP2.04 & FP2.05: PLAN
 INDICATES NO SPRINKLER PROTECTION FOR THE
 NON-ACCESSIBLE TRUSS SPACE; CONTRARY TO NFPA 13 SECTION
 8.15. INDICATE A CODE REFERENCE PERMITTING THIS
 COMBUSTIBLE CONCEALED SPACE FROM BEING PROTECTED BY
 FIRE SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-22 Cont ID  
Sent By wjolin Date 2015-05-22 Time 12:30 Rev Time 0.00
Received By wjolin Date 2015-05-22 Time 12:30 Sent To  
Notes
2015-05-22 12:30:29PERMIT #15050261 - 838 ADAMS STREET (66 UNITS)
 PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS)
 PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE FIRE DEPARTMENT REQUIRES PLANS AND PERMITS FOR ALL
 CONSTRUCTION RELATED TRAILERS AND MODULAR BUILDINGS.
 ADDITIONALLY PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER
 FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING
 COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT
 BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL
 CONSTRUCTION WORK.
  
 SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 SHEET PM-1: PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT."
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A
 SURFACE DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING
 AT LEAST 36 TONS. ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 SHEET WS-1: FIRE MAINS SUPPLYING TWO OR MORE FIRE
 HYDRANTS WILL NEED TO BE LOOPED AND WILL NOT BE
 PERMITTED TO TERMINATE AT A DEAD END BLOWOFF CAP.
  
 SHEET WS-1: THE FIRELINE BACKFLOW PREVENTERS SHALL
 COMPLY WITH NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO
 PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS
 SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 COULD NOT LOCATE A DRAWING INDEX.
  
 COULD NOT LOCATE ANY LIFE SAFETY PLANS FOR THE PROPOSED
 POOL AREA AND CHILDRENS' PLAYGROUND AREA.
  
 SHEET A7.00: STAIRWAY IDENTIFICATION: 7.2.2.5.4.1 NEW
 ENCLOSED STAIRS SERVING THREE OR MORE STORIES SHALL
 COMPLY WITH 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET E2.01A & SHEET E2.01B: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION B.1/1.2. TYPICAL ALL LEVELS.
  
 SHEET E2.07: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE
 EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1.
 TYPICAL ALL LEVELS.
  
 SHEET E2.12: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE
 EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1.
 TYPICAL ALL LEVELS.
  
 SHEET FA1.00: COULD NOT LOCATE REMOTE ANNUNCIATOR
 PANEL. TYPICAL ALL 3 BUILDINGS.
  
 SHEET FA2.00: FIRE ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE.
  
 SHEET FP1.00: SEVERAL NOTES INDICATE THE 2007 EDITION
 OF NFPA 13. THE STATE OF FLORIDA HAS ADOPTED AND
 ENFORCES THE 2010 EDITION.
  
 SHEET FP2.00: THE NON-RESIDENTIAL PUBLIC SPACES ARE
 INDICATE THE SPRINKLERS ARE BEING FED FROM THE SECOND
 FLOOR SPRINKLER SYSTEM. PROVIDE A DEDICATED FLOW SWITCH
 FOR THIS AREA OR SUPPLY THIS AREA FROM THE FIRST FLOOR
 SPRINKLER SYSTEM TO ELIMINATE CONFUSION THAT THE FIRE
 EVENT IS LOCATED ON THE SECOND FLOOR.
  
 SHEET FP2.04 & FP2.05: PLAN INDICATES NO SPRINKLER
 PROTECTION FOR THE NON-ACCESSIBLE TRUSS SPACE; CONTRARY
 TO NFPA 13 SECTION 8.15. INDICATE A CODE REFERENCE
 PERMITTING THIS COMBUSTIBLE CONCEALED SPACE FROM BEING
 PROTECTED BY FIRE SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-10-03 Cont ID  
Sent By tklarge Date 2015-10-03 Time 14:25 Rev Time 0.00
Received By tklarge Date 2016-10-03 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 11:25 Rev Time 0.00
Received By skennedy Date 2015-09-30 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-25 Cont ID  
Sent By skennedy Date 2015-09-25 Time 15:44 Rev Time 0.00
Received By skennedy Date 2015-07-23 Time 18:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-28 Cont ID  
Sent By tklarge Date 2015-06-28 Time 08:33 Rev Time 0.00
Received By tklarge Date 2015-05-13 Time 11:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-12-01 Cont ID  
Sent By rbrown Date 2015-12-01 Time 11:58 Rev Time 0.00
Received By rbrown Date 2015-12-01 Time 11:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 09:19 Sent To  
Notes
2015-10-06 10:18:21BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-20 Cont ID  
Sent By jwitmer Date 2015-08-20 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2015-08-20 Time 06:23 Sent To  
Notes
2015-08-20 08:08:46BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-20 Cont ID  
Sent By jwitmer Date 2015-06-20 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2015-06-20 Time 11:07 Sent To  
Notes
2015-06-20 11:07:24BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-05 Cont ID  
Sent By ccole Date 2015-10-05 Time 14:53 Rev Time 0.00
Received By ccole Date 2015-10-05 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-05 Cont ID  
Sent By ccole Date 2015-08-05 Time 15:40 Rev Time 0.00
Received By ccole Date 2015-08-05 Time 15:40 Sent To  
Notes
2015-08-05 16:11:282ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050262
 8/5/15
  
 1) REFERENCE COMMENT #1 FROM THE 1ST REVIEW: THE
 REVISED ENERGY CALCULATIONS WERE NOT SUBMITTED.
 2) REFERENCE COMMENT #2 FROM THE 1ST REVIEW: THE
 REQUESTED AC COOLING AND HEATING LOAD CALCULATIONS WERE
 NOT SUBMITTED.
 3) REFERENCE COMMENT #3 FROM THE 1ST REVIEW: THE
 REQUIRED EXHAUST FOR THE GROUND FLOOR TRASH ROOM IS NOT
 SHOWN ON THE PLAN. REVISE THE FAN SCHEDULE ON SHEET
 M-3.00 TO INCLUDE THE TRASH ROOM EXHAUST FANS ON THE
 OTHER FLOORS, AND SHOW HOW MAKEUP AIR IS BEING
 SUPPLIED.
 4) REFERENCE COMMENTS #5 & 6 FROM THE 1ST REVIEW: THE
 SPECS FOR THE RINNAI WATER HEATER WERE NOT SUBMITTED.
 5) REFERENCE COMMENT #10: PLEASE REMOVE SHEET A-10.08
 SHOWING THE HILTI FIRESTOPPING DETAILS, THE ENGINEER OF
 RECORD HAS INDICATED IN HIS NARRATIVE RESPONSE THAT HE
 WILL BE USINGTREMCO.
 6) REFERENCE COMMENT #12: THE RESPONSE NARRATIVE FROM
 THE ENGINEER IS STATING THAT THE CONDENSER TIE-DOWN
 DETAILS ARE IN THE STRUCTURAL DRAWINGS. PLEASE INDICATE
 ON WHICH PLAN SHEET THE DETAILS CAN BE FOUND.
 7) REFERENCE COMMENT #13: 2ND REQUEST FOR PRODUCT DATA
 SHEETS, PRODUCT APPROVALS AND NOA'S TO BE SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By ccole Date 2015-06-17 Time 09:42 Rev Time 0.00
Received By ccole Date 2015-06-17 Time 09:42 Sent To  
Notes
2015-06-17 10:16:061ST REVIEW: FBC 2010 MECHANICAL- 6/17/15
 PERMIT # 15050262
 SILVER PALMS PLACE- BLDG. #3
  
 1) THE ENERGY CALCULATIONS FOR BUILDING #3 DO NOT
 INCLUDE DATA AND COMPLIANCE INFO FOR AC-1 (TRASH ROOM
 ON GROUND FLOOR).
 2) THE REQUIRED AC LOAD CALCULATIONS WERE NOT INCLUDED
 WITH THE SUPPORTING DOCUMENTS- SECTIONS 101.5 AND
 503.2.1 FBC-10 ENERGY CONSERVATION.
 3) SHEETS M1.11- M1.14: EXHAUST SYSTEMS AT A RATE OF
 1.00 CFM PER SF ARE REQUIRED FOR THE TRASH ROOMS AND
 THE TRASH CHUTES SHOWN ON THE GROUND THRU 4TH FLOORS-
 TABLE 6-4 ASHRAE 62.1- 07. PLEASE REVISE THE PLANS
 ACCORDINGLY, AND CLARIFY WHY ONLY THE GROUND FLOOR
 TRASH ROOM IS BEING CONDITIONED BY AC-1.
 4) M2.00 & M2.01: THE DRYER BOOSTER FANS SHOWN IN UNITS
 A, AND A & C ACCESSIBLE UNITS ARE PROHIBITED BY THE
 CITY OF WEST PALM BEACH FIRE RESCUE.
 5) M2.00 & M2.01: THE RINNAI DIRECT GAS VENTS SHALL BE
 LISTED FOR PLENUM INSTALLATIONS PER SECTION 503.2.3
 FBC-10 FUEL GAS. SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER AND VENTING SYSTEM REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 6) M2.00 & M2.01: PLACE A NOTE INDICATING THE REQUIRED
 CLEARANCE DISTANCES FOR THE THRU-WALL TERMINATION OF
 THE RINNAI DIRECT CONCENTRIC VENT.
 7) M3.00: PLEASE REMOVE OR REVISE ALL HVAC NOTES
 REFERENCING CODE SECTIONS FROM THE FBC-10 RESIDENTIAL
 CODE. THE PROPOSED PROJECT IS REGULATED BY THE FBC-10
 BUILDING CODES.
 8) M3.00: THE HVAC REFRIGERANT PIPING NOTES SHALL
 INDICATE THE PIPING INSULATION IS PLENUM RATED PER
 SECTION 602.2.1 FBC-10.
 9) M1.15: PROVIDE A SEQUENCE OF OPERATION FOR THE
 MOTORIZED EXHAUST DAMPER AT THE SIDEWALL OF THE
 ELEVATOR SHAFT.
 10) PIPE PENETRATION SEALS: SHEETS A.10.06 & A10.07
 SHOW TREMCO FIRE STOPPING DETAILS, AND SHEET A.10.08
 SHOWS HILTI. PLEASE SELECT ONE SYSTEM OR THE OTHER FOR
 THE AC REFRIGERANT AND CONDENSATE PIPINGS.
 11) PROVIDE A TYPICAL SECTION CUT FOR THE AHU'S IN THE
 PLENUM CLOSET INDICATING CLOSET CONSTRUCTION MATERIALS,
 CLEARANCES DISTANCE MEASUREMENTS AROUND THE UNITS,
 REFRIGERANT PIPING RUNS, AND PRIMARY AND SECONDARY
 CONDENSATE DISPOSAL DETAILS PER SECTION 307 FMC-10 (
 INCLUSIVE OF ALL SUB-SECTIONS).
 12) M3.01: WIND LOAD DESIGN PRESSURE CALCULATIONS AND
 TIE-DOWN ENGINEERING ARE REQUIRED FOR ANCHORING THE
 CONDENSER STANDS AND CONDENSER UNIS TO THE ROOF
 STRUCTURE- SECTION 301.12 FMC-10, AND SECTION 1609
 FBC-10 BUILDING. PLEASE REVISE THE DETAIL ACCORDINGLY
 AND CORRECT THE 150 MPH WIND LOAD SPECIFICATION.
 13) PROVIDE A SUBMITTAL PACKAGE WITH ALL DOCUMENTS
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD. PLEASE INCLUDE NOA'S, PRODUCT APPROVALS, AND
 MANUFACTURER'S SPECIFICATIONS FOR THE CONDENSER STANDS,
 THE EXHAUST AND O/A INTAKE FANS, THE O/A MOTORIZED
 DAMPERS, THE EXHAUST AND INTAKE WALL LOUVERS, THE
 ELEVATOR SHAFT MOTORIZED DAMPER, THE AC SYSTEMS, THE
 GAS WATER HEATER AND VENT SYSTEM, AND THE REFRIGERANT
 PIPE INSULATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-03 Time 11:24 Rev Time 0.00
Received By skennedy Date 2015-10-03 Time 09:26 Sent To  
Notes
2015-10-13 11:25:15REVIEW BY TKL

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-06 Cont ID  
Sent By tklarge Date 2015-08-06 Time 06:32 Rev Time 0.00
Received By tklarge Date 2015-08-05 Time 04:27 Sent To  
Notes
2015-08-06 04:35:401)THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. 2ND
 REQUEST.
 2) THE OVERFLOW RAINWATER DOWNSPOUTS SHALL DISCHARGE A
 MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL
 PER 2010 FBC 1503.7. PLACE A NOTE ON THE PLANS.THIS
 COMMENTS REFERS TO THE DOWNSPOUTS FROM THE GUTTERS.
 THEY ARE NOT UNDERGROUND.
 3) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL
 PROJECTED ROOF AREA" -1008 SQ. FT.- THIS DOES NOT ADD
 UP.PLEASE CLARIFY. IS THIS A TYPO ERROR?
 4) SHT. A2.05 - THIS BUILDING HAS TWO FLAT ROOFS
 IDENTIFY RWL-1 & RWL-2 ON THE PLANS. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.2ND REQUEST.
 5) THE STORM DRAINAGE RISER SHOWS OVERFLOW DRAINS, NOT
 SCUPPERS, YET THERE ARE TABLES FOR SCUPPER SIZING. ARE
 THERE OR ARE THERE NOT ROOF SCUPPERS ON THIS BUILDING?
 IF SO, SHOW THE LOCATION OF ALL SCUPPERS AND SHOW THE
 LENGTH AND HEIGHT DIMENSIONS OF THE SCUPPERS AND THE
 DESIGN HEAD ( IN INCHES). SCUPPERS SHALL BE SIZED PER
 THE 2010 FBC-PLUMBING TABLE 1106.7. IF NOT, DELETE ANY
 REFERENCE/TABLE TO ROOF SCUPPERS.
 6) SUBMIT GUTTER CALCULATIONS FOR THE ROOF GUTTERS AND
 DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & 1106.7.
 2ND REQUEST.
 7) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS ( IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 8) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS (IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS. COMPLY
 WITH 2010 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1)
 THROUGH 1106.2 (2), 1106.3,1106.7.
 9) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF DRAIN
 CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. SUBMIT
 ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND SHOW
 THE LOCATION OF THE SCUPPERS ( IF APPLICABLE ) AND
 PROVIDE SCUPPER CALCULATIONS.COMPLY WITH 2010
 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) THROUGH
 1106.2 (2), 1106.3,1106.7.
 10) SHT. P1.00 - SHOWS A 2 INCH WATER SERVICE TO
 BUILDING #2 AND SHT. WS-1 SHOWS A 4 INCH WATER SERVICE.
 CLARIFY. 2ND REQUEST. THE CIVIL PLANS STILL SHOW A 4
 INCH WATER LINE. WHICH IS IT? THE PLANS SHALL
 CORRELATE.
 11) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2ND REQUEST. THE RESPONSE STATED THEY WILL BE PROVIDED.
 WHEN?
 12) SHT. P4.00 - SHOW THE TONNAGE OF THE AIR
 CONDITIONING EQUIPMENT ON THE CONDENSATE RISER. COMPLY
 W/ TABLE 314.2.2. OF 2010 FPC. THE PLAN WAS ONLY
 CORRECTED FOR BUILDING #1. CORRECT THE PLAN FOR THE
 OTHER BUILDINGS. 2ND REQUEST.
 13) SUBMIT THE MANUFACTURER SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1. I CANNOT DETERMINE IF
 THE VENT LOCATIONS ARE APPROVED AND TO CODE WITHOUT THE
 INSTALLATION MANUAL THAT SHOWS THE REQUIREMENTS. MY
 CONCERNS ARE THAT THIS IS A DIRECT VENT APPLIANCE AND
 THE CLOSE PROXIMITY TO AN EXHAUST DUCT MAY CREATE A
 CODE ISSUE.2010 FBC-FUEL GAS CODE SEC.503.2.3.
 14) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 SUBMIT A DETAIL THAT SHOWS ALL THE PIPING. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1. 2ND REQUEST.
 15) IDENTIFY THE OVERFLOW DRAINS ON ALL THE ROOF PLANS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P1.00 - CLEARLY SHOW WHERE THE WATER SERVICE
 ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 17) THE AREA OF THE SLOPED ROOFS THAT ARE DRAINING ONTO
 THE LOWER ROOFS SHALL BE INCLUDED IN THE ROOF DRAINAGE
 CALCULATIONS. THIS WAS OVERLOOKED IN FIRST REVIEW.2010
 FBC -PLUMBING SECS.1106.2 & 1106.3.
 18) THE PLUMBING DRAWINGS REFER TO THE ARCHITECTURAL
 PLANS FOR DOWNSPOUT DETAILS. I COULD NOT FIND ANY
 DOWNSPOUT DETAILS IN THE ARCHITECTURAL PLANS. CLARIFY.
 19) NOTE #14 ON THE ENLARGED ARCHITECTURAL FLOOR PLANS
 REFER TO THE ARCHITECTURAL AND PLUMBING DRAWINGS FOR
 DETAILS FOR THE GUTTERS AND DOWNSPOUTS. I COULD NOT
 FIND ANY DETAILS ON ANY OF THESE PLANS. CLARIFY.
 20) AS UPLOADED, ALL THE PLUMBING DRAWINGS ARE LABELED
 AS "P' DRAWINGS. THERE IS NO WAY TO DISCERN WHICH
 DRAWINGS ARE FOR BUILDING #1, #2 OR #3. PLEASE SUBMIT
 ONLY THE DRAWINGS THAT ARE APPLICABLE TO THIS PERMIT
 AND THIS BUILDING. THIS APPLIES TO ALL THE DRAWINGS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 21) SEVERAL RESPONSES ON THE PLAN REVIEW COMMENT STATE
 "REFER TO REVISED ROOF PLAN" OR "SEE ARCHITECTURAL
 DRAWINGS." THESE RESPONSES ARE VAGUE AND
 INCONCLUSIVE.PLEASE PROVIDE THE SPECIFIC DRAWING NUMBER
 WHEN REFERENCING PLAN SHEETS.. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-28 Cont ID  
Sent By tklarge Date 2015-06-28 Time 9:30 Rev Time 0.00
Received By tklarge Date 2015-06-27 Time 12:26 Sent To  
Notes
2015-06-28 08:32:58THIS REVIEW WAS DONE UNDER PERMIT #15050261 WHICH HAD
 THE PLANS FOR ALL THREE BUILDINGS. SOME OF THE COMMENTS
 MAY ONLY BE APPLICABLE TO BUILDING #1 AND DO NOT APPLY
 TO BUILDINGS #2 & #3.
  
  
 1) THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5.
 2) RAINWATER DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF
 ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL PER 2010 FBC
 1503.7.
 3) THE ROOF DRAINAGE CALCULATIONS FOR THE DESIGN OF THE
 STORMWATER SYSTEM SHALL INCLUDE ONE-HALF OF THE AREA OF
 ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 PER THE 2010 FPC SEC.1106.4. SHOW THAT THIS HAS BEEN
 DONE WITH THE SIZING OF THE STORM DRAINAGE SYSTEM.
 4) SHT. A2.05 - SCUPPER CALCULATION - SEE ROOF SQ.FT.
 W/PARAPET.- THE SQUARE FOOTAGE CANNOT BE READ. CLARIFY.
 5) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES HORIZONTAL
 PROJECTED ROOF AREA -1008 SQ. FT. PLEASE CLARIFY. IS
 THIS A DISCREPANCY?
 6) SHT. A2.05 - SHOW THE LOCATION OF THE SCUPPERS ON
 THE PLAN AND THE LOCATION OF RWL-1 & RWL-2. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SUBMIT GUTTER CALCULATIONS FOR THE GABLE END GUTTERS
 AND DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 &
 1106.7.
 8) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 9) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 10) SHT. P1.00 - SHOWS A 2" WATER SERVICE TO BUILDING
 #2 AND SHT. WS-1 SHOWS A 4" WATER SERVICE. CLARIFY.
 11) SHT. P1.00 - SHOW THE TERMINATION POINTS OF THE
 STORM AND CONDENSATE DRAINS ON THE PLANS. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 12) SHT. P2.00 - PLANS REFER TO THE CIVIL DRAWINGS FOR
 THE CONTINUATION OF THE STORM AND CONDENSATE DRAINS.
 THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS.
 CLARIFY.
 13) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) AIR CHAMBERS ARE NOT PERMITTED FOR WATER HAMMER.
 DELETE ALL REFERENCE ON THE PLUMBING PLANS TO AIR
 CHAMBERS. A WATER HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK ?CLOSING VALVES ARE UTILIZED. FPC
 SEC.604.9.
 15) SHT. P4.00 - SHOW THE TONNAGE OF THE EQUIPMENT ON
 THE CONDENSATE RISER. COMPLY W/ TABLE 314.2.2. OF 2010
 FPC
 16) SUBMIT THE MANUFACTURER SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 17) SHOW THE LOCATION OF ALL THE GAS VENTS FROM THE
 TANKLESS WATER HEATERS.
 18) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
2015-06-27 12:26:49REVIEW NOT COMPLETE.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 09:20 Sent To  
Notes
2015-10-06 10:17:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: LANDMARK
 CONTACT: JORGE COSTAS
 TEL: (305)665-1146
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. OCT.06/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/BLDG TYPE: III-B/ R2
  
 ACTION: PROVISO
  
 THIS REVIEW IS FOR BUILDING # 3 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
  
 1B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 1C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF
 TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 1D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 2 )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-08-20 Cont ID  
Sent By jwitmer Date 2015-08-20 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2015-08-20 Time 06:23 Sent To  
Notes
2015-08-20 08:09:31ROOF REVIEW: NO ROOFING PRODUCT APPROVALS WERE
 SUBMITTED UNDER THIS REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-20 Cont ID  
Sent By jwitmer Date 2015-06-20 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2015-06-20 Time 11:08 Sent To  
Notes
2015-06-20 11:08:40ROOF REVIEW: NO ROOFING PRODUCT APPROVALS WERE
 SUBMITTED UNDER THIS REVIEW.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-10-27 Cont ID  
Sent By cpuell Date 2015-10-27 Time 11:19 Rev Time 0.00
Received By cpuell Date 2015-10-27 Time 11:19 Sent To  
Notes
2015-10-27 11:19:22OK PER SKENNEDY
2015-10-26 08:21:02SKENNEDY'S DESK
2015-05-13 16:35:08RECEIVED HARDCOPY SIGNED & SEALED ARDAMAN & ASSOCIATES
 SOILS REPORTS (WITH APPLICATION).

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-09 Cont ID  
Sent By jroach Date 2015-10-09 Time 11:34 Rev Time 0.00
Received By jroach Date 2015-10-09 Time 11:34 Sent To  
Notes
2015-10-09 11:34:36ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.09.2015
 PERMIT NO.: 15050262
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT
 HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO.
 72-15.
  
 2. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 3. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE PROPERTY SHALL BE RE-PLATTED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-08-24 Cont ID  
Sent By jroach Date 2015-08-24 Time 16:03 Rev Time 0.00
Received By jroach Date 2015-08-24 Time 16:03 Sent To  
Notes
2015-08-24 16:03:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.24.2015
 PERMIT NO.: 15050261, 15050262, 15050263
 ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807
 DIVISION AVENUE
 CONTRACTOR/CONTACT: ???
 TELEPHONE NO.: ???
 SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT
 HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO.
 72-15, AS WELL AS THE FOLLOWING WHICH WERE CONDITIONS
 OF APPROVAL:
  
  I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS
 WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE
 (IN ALIGNMENT WITH 17TH STREET).
  
  II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF
 THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3.
  
 2. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED.
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED
 COST ESTIMATE (MATERIAL + LABOR).
  
 3. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED
 INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING
 THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX.
  
 4. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED
 THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE
 DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE
 NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.).
  
 5. ON SHEET A1.01, DETAIL 3 DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS WITH REGARD TO SIZE, AND DOESN'T MATCH WHAT
 IS SHOWN ON THE PLANS.
  
 6. THE SITE LIGHTING SHOWN ON SHEET E-1.00 AND E-1.10
 DO NOT MATCH. AND PHOTOMETRIC LEVELS SHALL BE SHOWN AT
 THE PROPERTY LINE, NOT EXCEEDING 0.5 FOOTCANDLES.
  
 7. IN AN EMAIL TO JON SCHMIDT & ASSOCIATES ON
 8/24/2015, SEVERAL AREAS OF CONCERN WERE IDENTIFIED
 WHERE IT APPEARS THAT THE LOCATION OF UTILITIES, SIGHT
 LIGHTING, ETC. HAVE CREATED DEFICIENCES OR CONFLICTS
 WITH LANDSCAPING. THESE AREAS SHOULD BE EVALUATED AND
 ADJUSTED ACCORDINGLY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  
 5/19/15

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-05 Cont ID  
Sent By jroach Date 2015-06-05 Time 16:04 Rev Time 0.00
Received By jroach Date 2015-06-05 Time 16:04 Sent To  
Notes
2015-06-05 16:04:18ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.04.2015
 PERMIT NO.: 15050261, 15050262, 15050263
 ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807
 DIVISION AVENUE
 CONTRACTOR/CONTACT: ???
 TELEPHONE NO.: ???
 SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 72-15, PRIOR TO THE
 ISSUANCE OF A PERMIT:
  
 A. A MINOR AMENDMENT SHALL BE SUBMITTED TO THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION FOR
 THE FOLLOWING:
  
  I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS
 WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE
 (IN ALIGNMENT WITH 17TH STREET).
  
  II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF
 THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3.
  
 2. REMINDER - PRIOR TO THE ISSUANCE OF ANY CERTIFICATE
 OF OCCUPANCY, THE PROPERTY SHALL BE RE-PLATTED IN
 ACCORDANCE WITH ALL APPLICABLE STATUTES, REGULATIONS,
 AND THE CITY'S POLICIES AND PROCEDURES.
  
 3. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED.
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED
 COST ESTIMATE (MATERIAL + LABOR).
  
 4. REMINDER - ALL UTILITIES WITHIN THE RPD SHALL BE
 LOCATED UNDERGROUND.
  
 5. THE EAST-WEST ROADWAY EXTENDING WEST FROM DIVISION
 AVENUE (IN LINE WITH ADAMS STREET), SHALL BE
 INCORPORATED INTO ALL PERMIT MATERIALS FOR THIS PROJECT
 AS IT IS REQUIRED TO BE COMPLETED IN ASSOCIATION WITH
 SILVER PALM PLACE.
  
 6. PLEASE CONFIRM THAT THE PROPOSED DESIGN, RADIUS,
 MATERIALS, LOAD, ETC. FOR THE ROUNDABOUT WILL BE
 ACCEPTABLE TO THE CITY'S FIRE-RESCUE DEPARTMENT; OR ARE
 THEY ACCEPTABLE OF DRIVING THROUGH THE PARKING AREA?
 SIGNAGE MAY BE REQUIRED.
  
 7. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED
 INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING
 THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX.
  
 8. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED
 THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE
 DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE
 NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.).
  
 9. PLEASE CONSULT WITH THE CITY'S TRAFFIC ENGINEER AS
 TO WHETHER OR NOT THE EAST-WEST ROADWAYS SHOULD BE
 SIGNED AS "ADAMS STREET" AND "17TH STREET". THESE WILL
 NOT BE DEDICATED ROADWAYS. ADDITIONALLY, I DON'T IF THE
 PROPER ADDRESSES HAVE BEEN ASSIGNED BECAUSE OF THIS.
  
 10. THE UTILITIES SHOWN ON THE WATER & SEWER PLANS DO
 NOT MATCH WHAT WAS SHOWN ON THE LANDSCAPE PLANS. PLEASE
 ENSURE THAT THE PLANS ARE CONSISTENT AND THAT THERE ARE
 NO CONFLICTS. ADDITIONALLY, THE LANDSCAPE PLANS SHALL
 ENSURE THAT ALL MECHANICAL EQUIPMENT, METERS, BACKFLOW
 PREVENTERS, ETC. ARE SCREENED AS REQUIRED.
  
 11. THERE IS AN FDC CONNECTION SHOWN IN A LANDSCAPE
 ISLAND NEAR BUILDING #2 THAT APPEARS TO CONFLICT WITH A
 PROPOSED SHADE TREE. THE FDC MAY NEED TO BE RELOCATED.
  
 12. PLEASE ENSURE THAT THERE IS NO CONFLICT BETWEEN THE
 LANDSCAPING AND THE PROPOSED FIRE HYDRANT LOCATED IN
 THE PARKING LOT ISLAND BETWEEN BUILDINGS #2 AND #1
 (SOUTH OF THE ROUNDABOUT).
  
 13. ON SHEET A1.01, DETAIL 1 SHOULD SHOW A MINIMUM OF 5
 FEET OF LANDSCAPING ISLAND FROM THE INSIDES OF THE
 CURBING.
  
 14. ON SHEET A1.01, DETAILS 3 AND 3.1 DO NOT MEET THE
 MINIMUM REQUIREMENTS OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS WITH REGARD TO SIZE, STRIPING,
 ETC.
  
 15. ON SHEET A1.01, DETAIL 9, THE LANDSCAPING IS ON THE
 WRONG SIDE OF THE CONCRETE PAD, AND THE BIKE RACKS MAY
 BE ORIENTED IN THE WRONG DIRECTION ON THE SITE PLAN.
 THE BIKE RACK SHOULD BE ORIENTED SUCH THAT TWO (2)
 BIKES CAN BE EASILY PUSHED INTO PLACE ON EITHER SIDE OF
 THE RACK.
  
 16. ON SHEET A1.00, NOTES #9 AND #10 ARE REVERSED.
  
 17. ON SHEET A-1.02, THE STAIR FLOOR PLANS REFER TO THE
 INCORRECT SHEET FOR THE CROSS SECTIONS.
  
 18. IN LOOKING AT THE BUILDING PERMITS, THE ARCHITECT'S
 PLANS ARE SHOWING THAT THE FIRST FLOOR OF THE UNITS ON
 DIVISION AVENUE IS 4-5 FEET (OR MORE IN SOME AREAS)
 ABOVE GRADE. THIS LEAVES A LARGE AREA UNDERNEATH THE
 FIRST LEVEL OF WINDOWS. ALL THAT'S PROPOSED ON THE
 LANDSCAPE PLAN IS SOD WITH A 24 INCH HIGH ROW OF
 "SEMINOLE PINK HIBISCUS". ADDITIONAL PLANTINGS SHALL BE
 PROVIDED TO ADDRESS THE SCALE OF THE BASE OF THE
 BUILDING.
  
 19. LANDSCAPE SCREENING SHALL BE PROVIDED AROUND THE
 PROPOSED FPL TRANSFORMERS (UNLESS OTHERWISE PROHIBITED
 BY FPL).
  
 20. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN
 THE PROPOSED SITE LIGHTING AND THE LANDSCAPING.
  
 21. LANDSCAPE SCREENING AND FENCING SHALL BE PROVIDED
 FOR THE POOL EQUIPMENT.
  
 22. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN
 THE PROPOSED FPL TRANSFORMERS AND THE LANDSCAPING.
  
 23. PLEASE PROVIDE CROSS SECTIONS AT THE LOCATIONS OF
 THE ROOF-TOP MECHANICAL EQUIPMENT TO INDICATE THAT ALL
 EQUIPMENT WILL BE ADEQUATE SCREENED WITH THE PROPOSED
 PARAPETS, ETC. PLEASE SHOW THE MECHANICAL EQUIPMENT
 (ACCURATELY SIZED) IN THE CROSS SECTION.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved