Plan Review Details - Permit 15050261
Plan Review Stops For Permit 15050261
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 05:32 Sent To  
Notes
2015-10-06 07:33:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK
 CONTACT: JORGE COSTAS
 TEL: (305)665-1146
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. OCT.06/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 5 STORY/BLDG TYPE: I-B/ R2
  
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) PROVISO: NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A-B) COMPLIED.
  
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" .
  
 3E) 3RD REQUEST!!! NOTE TO DATE NO PERMIT APPLICATION
 WHERE THE OWNER HAS SIGNED AND THEIR SIGNATURES
 NOTARIZED. AHOLD WILL BE PUT ON THE PERMIT NOT TO ISSUE
 UNTIL THE OWNERS SIGNATURE IS ON THE PERMIT
 APPLICATION.
  
 3F)NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) PROVISO: CALCULATED FEES ENTERED INTO FEE SCHEDULE.
 10/06/2015
 CALCULATED VALUE:
 BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00
 BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00
  
  
 5-9) COMPLIED
  
 10) SHEET A-200A:
 10A) COMPLIED.
  
 10B) REVISION REQUIRED. 3RD REQUEST. BETWEEN DWELLING
 UNITS AND DWELLING UNITS AND COMMON AREAS WALL TYPE W5
 HAS BEEN INDICATED A 6 INCH CONCRETE REINFORCED WALL
 WITH NO INSULATION. PLEASE PROVIDE DOCUMENTATION THAT
 COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
 RESPONSE: WALL SOUND INSULATION THAT HAS ALREADY BEEN
 TESTED, IS FOUND ON SHEET A9.04 ALSO WALL TYPE SHEET
 A-8.01. NOTE THESE ARE SALES BROCHURES; THEY ARE NOT
 THE ACTUAL TEST. PROVIDE TEST REPORTS.
  
  
  
 11-19) COMPLIED.
  
 20)(A)REVISION REQUIRED: 3RD REQUEST. SHEET A4.02
 INDICATES 6 INCH CONCRETE SLAB. SHEET A-9.04 INDICATES
 THE USE OF (2) FLOOR INSULATION PRODUCTS, DB-4LOORING
 INSULATION, AND QT SCU 4002 PLEASE SUBMIT THE REPORTS
 FOR COMPLIANCE WITH 20A-20C, MISSING FLAME SPREAD.
  
 20)(B) REVISION REQUIRED: 3RD REQUEST. SHEET A-9.04
 ALSO SHOWS A WALL INSULATION TYPE DB-3, THIS IS A SALES
 BROCHURE PLEASE SUBMIT TEST INFORMATION, WALL
 INSULATION WILL NEED TO COMPLY WITH 1207.2 THE SALES
 BROCHURE SUBMITTED IS FOR WOOD AND METAL STUDS, NEVER
 TESTED ON A 6 INCH CONCRETE WALL. WALL INSULATION WILL
 NEED TO MEET 1207.2 ASTM E 90 AND SECTION 2010 FBC-B
 719.2 CONCEALED INSULATION FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE DEVELOPMENT OF 450.
  
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21-22) COMPLIED.
  
 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 23A) )PROVISO: FOR GLAZED PRODUCT APPROVALS, IDENTIFY
 THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED OPENING,
 IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE
 INSTALLED, PRESSURES, AND FASTENERS.
  
 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF
 TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By jwitmer Date 2015-08-18 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2015-08-17 Time 06:30 Sent To  
Notes
2015-08-18 16:51:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. AUGUST 18/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A-B) COMPLIED.
  
 2C) THE ELECTRONIC PLANS SUBMITTED 368 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED THE SHEETS THAT DID NOT PERTAIN TO
 THAT BUILDING AND DETAIL SHEETS, DETAILS NOT PERTAINING
 TO THAT BUILDING STRUCK THROUGH. 107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE UNIFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES. THIS CODE SECTION IS
 FOR RECORD RETENTION BUT THE REALITY OF THIS IS, THE
 WAY THESE PLANS WERE SUBMITTED, IT IS VERY DIFFICULT TO
 FIND WHERE TO LOOK FOR CODE COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 2ND REQUEST, THE RESPONSE INDICATES THE WRITTEN
 THRESHOLD INSPECTION PLAN WAS SUBMITTED PLEASE INDICATE
 WHERE IT CAN BE LOCATED?
 THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) COMPLIED. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE
 A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) NOTE TO DATE NO CONTRACTOR HAS SUBMITTED A PERMIT
 APPLICATION WHERE THE OWNER AND QUALIFIER HAVE SIGNED
 AND THEIR SIGNATURES NOTARIZED.
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 3F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $11,712,570.25 IS LOW. THERE IS
 A DISCREPANCY IN THE BUILDING TYPE FOR BUILDING # 1, SO
 THE VALUATION IS FIGURED FOR BOTH BUILDING TYPES.
 CALCULATED VALUE:
 BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00
 BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5)2ND REQUEST. SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6) 2ND REQUEST. THE PERMIT APPLICATION CAME IN AS A
 TBD, TO BE DETERMINED. A HOLD WILL BE PUT ON THE
 ISSUANCE OF THIS PERMIT TO VERIFY LICENSURE
 REQUIREMENTS THAT THE CONTRACTOR HOLDS THE APPROPRIATE
 LICENSURE FOR A 5 STORY BUILDING. FLORIDA S. S.
 489.113.
  
 7) SHEET A-0.01:
 7A)2ND REQUEST. THE CONSTRUCTION TYPE IS LISTED FOR
 BLDG # 1 AS II-B BUILDING, WHEREAS UNDER THE HEADING OF
 FIRE RESISTANCE RATING THE BUILDING IS LISTED AS
 CONSTRUCTION TYPE I-B. THIS DISCREPANCY IN THE PLANS
 WILL AFFECT THE REQUIREMENTS IN TABLE 601. 107.2.1.3,
 ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THAT
 FIRE RESISTANCE RATINGS AND ALLOWABLE HEIGHT AND AREA
 ARE FOR A CONSTRUCTION BLDG. TYPE I-B. FOR THE PURPOSE
 OF THIS REVIEW A BLDG. TYPE I-B WILL BE ASSUMED.
  
 7B) 2ND REQUEST. UNDER THE HEADING CONSTRUCTION TYPE IS
 FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR
 SINCE THERE ARE BLDGS. 2 & 3 ON THE SAME LINE AS
 BUILDING # 1.
  
 THE REAL QUESTION IS WILL THERE BE (2) TYPES OF FIRE
 SPRINKLERS, FOR BUILDING # 1 WILL REQUIRE THE NFPA 13
 FIRE SPRINKLER IN COMPLIANCE WITH FBC-B 903.3.1.1 AND
 WILL BUILDINGS 2 & 3 HAVE THE SAME TYPE OF FIRE
 SPRINKLERS OR WILL THEY HAVE A NFPA 13-R INCOMPLIANCE
 WITH FBC-B 903.3.1.2. IF BOTH SYSTEMS ARE GOING TO BE
 INSTALLED PLEASE LIST THEM IN THE BUILDING MATRIX FOR
 EACH BUILDING TYPE.
  
 8-9) COMPLIED.
  
 10) SHEET A-200A:
 10A) THIS COMMENT WILL BE FOR THE 1ST FLOOR LS-1.01
 UNIT B NEXT TO STAIR # 2. THE FRONT ENTRY DOORS DO NOT
 INDICATE A DOOR IDENTIFICATION TAG, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B TABLE 715.4.
  
 10B) 2ND REQUEST. BETWEEN DWELLING UNITS AND DWELLING
 UNITS AND COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED
 A 6 INCH CONCRETE REINFORCED WALL WITH NO INSULATION.
 PLEASE PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010
 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
  
  
 11-19) COMPLIED.
  
 20)2ND REQUEST. SHEET A-9.04 INDICATES THE USE OF (2)
 FLOOR INSULATION PRODUCTS, EASY MAT AND KNAUF
 INSULATION, PLEASE SUBMIT THE REPORTS FOR COMPLIANCE
 WITH 20A-20C.
  
 PLEASE NOTE WITH THE DESIGNER OF RECORD SPECING OUT THE
 USE OF EASY MAT WE CANNOT APPROVE THESE CODE SECTIONS.
 TO DATE NO CONTRACTOR, SUPPLIER OR MANUFACTURER HAS
 BEEN ABLE TO PROVIDE TESTING REPORTS FOR THE SOUND
 REQUIREMENTS OF ASTM E 492 AND ASTM E 90. WE DO HAVE A
 FLAME SPREAD TEST THAT WILL PASS A BUILDING TYPE I OR
 II BUT NOT THE MORE RESTRICTIVE REQUIREMENT FOUND FOR
 BUILDING TYPE IIIB. SEE 719.2 CONCEALED INSTALLATION.
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21-22) COMPLIED.
  
 23)2ND REQUEST. EITHER THE DESIGNER OF RECORD OR THE
 CONTRACTOR CAN ELECT TO SUBMIT THE PRODUCT APPROVALS
 AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL UNDER
 107.3.4.2, THIS IS A WRITTEN REQUEST, OTHERWISE WE WILL
 NEED THE PRODUCT APPROVALS TO REVIEW FOR CODE
 COMPLIANCE. PLEASE NOTE TO IDENTIFY, OPENING SIZES,
 TYPE OF GLAZING, PRESSURES, TYPE OF FASTENERS, MULLIONS
 ETC.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 23A) 2ND REQUEST. FOR GLAZED PRODUCT APPROVALS,
 IDENTIFY THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED
 OPENING, IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE
 INSTALLED, PRESSURES, AND FASTENERS.
  
 23B)2ND REQUEST. FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C)2ND REQUEST. FOR THE SLOPED ROOF: PROVIDE THE TYPE
 OF TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2ND REQUEST. EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2015-06-07 Time 07:32 Sent To  
Notes
2015-06-08 13:04:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JUNE 07/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. THERE IS NO INDEX SHEET IN THE SET
 OF PLANS. THERE IS 386 PAGES OF PLANS, WITHOUT AN INDEX
 SHEET TO BE ABLE TO IDENTIFY THE TYPE OF DRAWING IT
 WILL TAKE A LONGER TIME TO COMPLETE REVIEWS AND SUBJECT
 TO NEW COMMENTS BECAUSE OF NOT BEING ABLE TO IDENTIFY
 WHERE TO FIND INFORMATION.
 THIS PLAN SHOULD HAVE BEEN KICKED BACK AT PERMIT
 SUBMISSION.
  
 2B) 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. THIS PLAN DOES NOT
 FOLLOW THE NAMING CONVENTION FOR EACH PAGE WITHIN THE
 SET OF PLANS AND SHOULD HAVE BEEN DENIED AT TIME OF
 ELECTRONIC SUBMISSION. THE ARCHITECTURAL SHEETS ARE NOT
 IN ORDER BECAUSE OF THE NAMING CONVENTION WAS NOT
 FOLLOWED, THE A1. SHEETS JUMP TO A-10 SERIES TO A-11
 SERIES THEN TO A-2SERIES. THE PLANS DO NOT MEET THE
 CITY STANDARD FOR ELECTRONIC MEDIA REQUIRED BY THE
 ELECTRONIC PLAN REVIEW LIBERIAN, CAROLINE PUELL. PLEASE
 CONTACT MS. PUELL AT 805-6659 FOR FURTHER INSTRUCTIONS
 AND CLARIFICATIONS.
  
 2C) THE ELECTRONIC PLANS SUBMITTED 368 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED THE SHEETS THAT DID NOT PERTAIN TO
 THAT BUILDING AND DETAIL SHEETS, DETAILS NOT PERTAINING
 TO THAT BUILDING STRUCK THROUGH. 107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE UNIFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES. THIS CODE SECTION IS
 FOR RECORD RETENTION BUT THE REALITY OF THIS IS, THE
 WAY THESE PLANS WERE SUBMITTED, IT IS VERY DIFFICULT TO
 FIND WHERE TO LOOK FOR CODE COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $11,712,570.25 IS LOW. THERE IS
 A DISCREPANCY IN THE BUILDING TYPE FOR BUILDING # 1, SO
 THE VALUATION IS FIGURED FOR BOTH BUILDING TYPES.
 CALCULATED VALUE:
 BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00
 BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6) THE PERMIT APPLICATION CAME IN AS A TBD, TO BE
 DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF THIS
 PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE
 CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 5
 STORY BUILDING. FLORIDA S. S. 489.113.
  
 7) SHEET A-0.01:
 7A) THE CONSTRUCTION TYPE IS LISTED AS II-B BUILDING,
 WHEREAS UNDER THE HEADING THE BUILDING IS LISTED AS
 CONSTRUCTION TYPE I-B. THIS DISCREPANCY IN THE PLANS
 WILL AFFECT THE REQUIREMENTS IN TABLE 601. 107.2.1.3,
 ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THAT
 FIRE RESISTANCE RATINGS AND ALLOWABLE HEIGHT AND AREA
 ARE FOR A CONSTRUCTION BLDG. TYPE I-B. FOR THE PURPOSE
 OF THIS REVIEW A BLDG. TYPE I-B WILL BE ASSUMED.
  
 7B) UNDER THE HEADING CONSTRUCTION TYPE IS FOUND A BOX
 CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR SINCE THERE
 ARE BLDGS. 2 & 3 ON THE SAME LINE AS BUILDING # 1. THE
 REAL QUESTION IS WILL THERE BE (2) TYPES OF FIRE
 SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN COMPLIANCE
 WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 & 3 HAVE THE
 SAME TYPE OF FIRE SPRINKLERS OR WILL THEY HAVE A NFPA
 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF BOTH SYSTEMS
 ARE GOING TO BE INSTALLED PLEASE LIST THEM IN THE
 BUILDING MATRIX AS SUCH.
  
 8) SHEET A-1.01;
 8A) DETAILS 3 AND 3.1 THE ACCESSIBLE & STANDARD PARKING
 DETAILS AND PARALLEL PARKING STRIPPING DETAILS ARE
 GOING TO NEED TO COMPLY WITH 2010 FBC-ACCESSIBILITY
 CODE ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. SEE
 WEST PALM BEACH MUNI-CODE SECTION 94-485 STALL PAINTING
 DETAIL.
  
 8B) DETAIL # 10. THE FENCE DESIGN IS INDICATED TO MEET
 THE FBC-B 2010 ASCE 7-05. PLEASE NOTE THE ASCE -05 WAS
 IN THE 2007 FBC-B. THE 2010 FBC-B SECTION 1609. 1.1 THE
 DETERMINATION OF WIND USES THE ASCE 7-10.
  
 9) SHEET A-8.01 IDENTIFIES TYPE OF WALLS WITH WALL TAG
 ALPHA- NUMERICAL WALL TAGS FOR FIRE RESISTANCE RATINGS
 HOW DOES SHEET A-11.00 SERIES OF DRAWINGS RELATE TO
 SHEET A-8.01. SHEET A-8.01 DOES NOT HAVE BLOCK TYPE
 INFORMATION STATING THEY ARE A T012 OR T007 TYPE BLOCK?
  
 10) SHEET A-200A:
 10A) THIS COMMENT WILL STAND FOR ALL DOORS ON ALL
 FLOORS. THE FRONT ENTRY DOORS DO NOT INDICATE A DOOR
 IDENTIFICATION TAG, PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B TABLE 715.4.
  
 10B) BETWEEN DWELLING UNITS AND DWELLING UNITS AND
 COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED A 6 INCH
 CONCRETE REINFORCED WALL WITH NO INSULATION. PLEASE
 PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 FBC-B
 1207.2 HAS BEEN ACHIEVED.
  
  
  
 11) SHEET A-2.01B THE AREA ON THE 2ND FLOOR OVER THE
 COMMON AREAS OF THE 1ST FLOOR, THERE ARE WALLS SHOWN ON
 THIS AREA OF THE 2ND STORY BUT NO DOORWAYS TO GAIN
 ENTRY, IS THIS AREA A CLEAR STORY TO THE 1ST FLOOR?
 WHAT IS THE USAGE IF NOT? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
  
 12) PLEASE NOTE CONCERN IN STAIRWELL 2 & 3 THE 1ST, 2ND
 & 3RD FLOORS SHOW A 6 INCH POURED CONCRETE WALL AND ON
 THE 4TH AND 5TH FLOOR THE SAME WALL BECOMES A 8 INCH
 BLOCK WALL WITH REINFORCING. THIS SAME WALL IN THE
 PLUMBING SHEETS P2.04 SHOWS A 4 INCH RAIN WATER LETTER
 AND A 4 INCH OVERFLOW RAIN WATER LETTER WITHIN THE SAME
 WALL. THE RAIN WATER LETTERS CAN NOT BE WITHIN THE
 STAIR WELL IN BOTH STAIRS FBC-B 1022.4 PENETRATIONS. IF
 SHEET A-8.03 DETAIL #8 & 9 IS REFLECT A BUILD-OUT INTO
 THE STAIRWELL, PLEASE SHOW IN THE STAIRWELL WHERE THIS
 IS TO OCCUR, AND THE PILASTER WILL NEED TO BE A 2 HR.
 RATED SHAFT.
  
 FOR THE POURED CONCRETE SECTION OF WALL FBC-B 1906.3
 PIPES AND SLEEVES CAN NOT BE EMBEDDED IN CONCRETE
 UNLESS WITH THE APPROVAL OF THE DESIGN PROFESSIONAL.
 PLEASE SHOW WITH THE 2 HOUR FIRE RATING OF THE
 STAIRWELL ENCLOSURE WILL BE MAINTAINED WHEN OVER 4 ?
 INCHES OF PIPE WILL BE IN A 6 INCH WALL PLUS THE REBAR.
  
 FOR THE MASONRY BLOCK WALL AND TIE BEAMS , THE OUTSIDE
 DIAMETER OF A 4 INCH PIPE BEING 4 ? INCHES THIS TAKES
 OVER 60 PERCENT OF THE VOLUME AWAY IN A 7 ? INCH WALL
 AND BEAM THERE WOULD BE ONLY A 1 ? INCHES LEFT ON BOTH
 SIDES OF THE PIPE. FBC-B 2108 .2 ACI 530. CHAPTER 4
 EMBEDDED ITEMS 4.1.1.2 DESIGN SHALL CONSIDER THE
 STRUCTURAL EFFECTS RESULTING FROM THE REMOVAL OF
 MASONRY TO ALLOW FOR THE PLACEMENT OF PIPES OR
 CONDUITS.
  
 13) SHEET A-7-06 TRASH CHUTE;
 13A) DETAIL # 1 PLEASE PROVIDE DETAIL OF THE 2ND FLOOR
 BOTTOM OF SHAFT ENCLOSURE FIRE PROOFING OF HORIZONTAL
 ASSEMBLY. FBC-B 713.4.1.1 THROUGH PENETRATIONS.
  
 13 B) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS ON
 THE HORIZONTAL DAMPER THAT CLOSES OFF THE TRASH CHUTE
 FROM THE REMAINDER OF THE TERMINATION ROOM. FBC-B
 708.13.1. THIS MAY BE A HEAT ACTIVATED CLOSING DEVICE
 SHALL BE PERMITTED BETWEEN THE SHAFT AND THE
 TERMINATION ROOM.
  
 13C) DETAIL C DOES INDICATE A FIRE SPRINKLER RISER
 WITHIN THE SHAFT BUT NO COMPLIANCE WITH FBC-B
 903.2.11.2. CHUTES EXTENDING 3 OR MORE FLOORS SHALL
 HAVE ADDITIONAL SPRINKLER HEADS AT ALTERNATING FLOORS
 AND AT THE TOP OF THE SHAFT.
  
 14) SHEET A-7.00 DETAIL # 1 STAIRWELL 1 & 4, THE 1ST
 FLOOR INDICATES A VOID SPACE UNDER THE STAIRS, PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 VERTICAL CLEARANCE 307.4 AND FIGURE 307.4.
  
 15) SHEET A-7.01 DETAIL # 1 STAIRWELL 2 & 3, THE 1ST
 FLOOR INDICATES A VOID SPACE UNDER THE STAIRS, PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 VERTICAL CLEARANCE 307.4 AND FIGURE 307.4.
  
 16) SHEET A-2.05;
 16A) THE HIPPED ROOFS SHOW SOFFIT VENTS BUT THERE IS NO
 NOTATION OF CODE COMPLIANCE FOR 2010 FBC-B 1203.2 WITH
 50% OF THE REQUIRED VENTILATING AREA PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE SPACE
 TO BE VENTILATED AT LEAST 3 FEET ABOVE THE EAVE OR
 CORNICE VENTS, WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY THE EAVE VENTS.
  
 16B) PLEASE SHOW HOW COMPLIANCE WITH 1209.2 WILL BE
 ACHIEVED 20 INCH X 30 INCH ATTIC ACCESS.
  
 16C) PLEASE SEE HIPPED ROOF SECTION A, ON BOTH SIDES OF
 THIS ROOF THERE ARE FLAT ROOFS THAT DO NOT SHOW HOW THE
 WATER IS GOING TO BE REMOVED FROM THESE ROOF TOPS?
 FBC-B 1503.4.
  
 17) SHEET A-6.04 AT THE BOTTOM OF THE SHEET THE PLANS
 INDICATE BACKING REQUIREMENTS FOR TUB AND SHOWERS. THE
 HEIGHT DIMENSION IS PROVIDED TO THE TOP OF THE BACKING
 OF 38 INCHES AND THE VERTICAL DIMENSION OF THE BACKING
 FOR THE BACK WALL OF THE TUB. WHAT IS MISSING IS THE
 END WALL OF THE TUB AND SHOWER, WHAT IS THE MINIMUM
 VERTICAL DISTANCE FOR THE BACKING. THE OTHER ISSUE IT
 APPEARS FOR THE BACKING THE SHOWER BACK WALL WAS
 MISLABELED TUB. 2010 FBC- ACCESSIBILITY/ FAIR HOUSING
 SEE FIGURE # 5.
  
 18) SHEET A-9.00 DETAILS 1 & 3 BOTH SHOW THE USE OF
 ROOF SHEATHING, THICKNESS NOR SPAN OF PLYWOOD NOT
 PROVIDED. FBC-B TABLE 2304.7(5).
  
 19) SHEET A-9.00 DETAILS 1 & 3 BOTH SHOW THE USE OF
 PLYWOOD ROOF SHEATHING AND WOOD TRUSSES. PLEASE SEE
 FBC-B 603.1.1.3.
  
 20) SHEET A-9.04 INDICATES THE USE OF (2) FLOOR
 INSULATION PRODUCTS, EASY MAT AND KNAUF INSULATION,
 PLEASE SUBMIT THE REPORTS FOR COMPLIANCE WITH:
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21) SHEET S-3.02 UNDER THE HEADING WINDLOAD PRESSURES
 FOR WINDOWS AND DOORS, THE PLANS DO NOT INDICATE THE
 MEAN ROOF HEIGHT THESE PRESSURE WERE TAKEN FOR,
 BUILDING 1 IS A (5) STORY WHEREAS BUILDINGS 2 & 3 ARE
 BOTH 4 STORY BUILDINGS. DEFINITIONS, CHAPTER 2. MEAN
 ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT AND
 THE HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE,
 EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF ANGLE OF
 LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD).
  
 22) SHEET S-3.02 COMPONENTS AND CLADDING THE ROOF
 PRESSURES FOR ROOF ZONES 1,2 & 3 WERE NOT PROVIDED FOR
 10 SQ. FT. PLEASE ALSO NOTE THERE ARE 2 MEAN ROOF
 HEIGHTS TO CONSIDER, THE 5 STORY AND 4 STORY. THE OTHER
 ISSUE IS THE PRESSURES FOR THE FLAT ROOFS AS WELL AS
 FOR THE SLOPED ROOF. FBC-B 1609.1.5 & 1609.1.2.3.1.
  
 23) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 23A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF
 GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS
 ARE USED, CIRCLE THE MULLION TO BE INSTALLED,
 PRESSURES, AND FASTENERS.
  
 23B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE
 SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY
 REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND
 SIGNED & SEALED CALCULATIONS.
  
 23C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO
 BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED,
 IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES.
  
 23D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR
 CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT
 APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR
 THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING
 FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-06 Time 19:46 Rev Time 0.00
Received By albarran Date 2015-10-06 Time 14:53 Sent To  
Notes
2015-10-06 19:47:27ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By albarran Date 2015-09-04 Time 11:41 Rev Time 0.00
Received By albarran Date 2015-09-02 Time 10:37 Sent To  
Notes
2015-09-04 11:42:55MOST OF THE PREVIOUSLY MENTIONED ITEMS HAVE BEEN
 ADDRESSED. I CONTACTED SERGIO MARTINEZ OF JMM
 CONSULTING WITH THE LIST OF THE REMAINING ITEMS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-09 Cont ID  
Sent By albarran Date 2015-06-09 Time 20:01 Rev Time 0.00
Received By albarran Date 2015-06-03 Time 08:40 Sent To  
Notes
2015-06-09 17:18:48PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 PG. E-1.00 ELECTRICAL SITE PLAN
 1. BEING THAT THE PROPOSED POOL WILL BE UNDER A
 SEPARATE PERMIT. A NOTE AS TO THE NEC 680.10
 REQUIREMENT FOR NO UNDERGROUND RACEWAYS WITHIN 5? OF
 THE WATER?S EDGE SHOULD BE MADE TO KEEP THE AREA CLEAR
 OF NON-POOL RELATED CONDUIT.
  
 PG. E1.10 PHOTOMETRIC PLAN
 1. AN AMENDMENT TO NOTE 4 IN IRRIGATION PUMP SYSTEMS TO
 INCLUDE THE CODE REQUIREMENT THAT THE DEVICES ALSO BE
 RATED ?WR? WEATHER RESISTANT.
  
 PG. E2.02A, E2.02B, E2.03A, E2.03B, E2.04A, E2.04B,
 E2.08, E2.09, E.2.13 & E2.14
 1. THE ABOVE PAGES ARE MISSING AN EXIT LIGHT IN THE
 CORNER WHERE THE TWO CORRIDORS INTERSECT. THIS/THESE
 LIGHTS SHALL BE VISIBLE FROM BOTH SIDES.
 2. IN ADDITION TO THE ABOVE, PGS. E2.04A, E2.09 & E2.14
 HAVE ACCESS TO THE ROOF. THERE SHALL BE AN EXIT LIGHT
 ON THE ROOF SIDE OF EACH OF THESE DOORS.
 3. THE SAME APPLIES TO PG. E2.04B. THE DOOR ON THE
 MATCH LINE HAS BEEN CLOUDED ON BOTH A & B.
  
 PG. E2.07A, E2.08A, E2.09A, E2.12A, E2.13A & E2.14A
 1. ON THESE PAGES YOU SHOW THE EMERGENCY EGRESS
 LIGHTING, AND THOUGH THE STAIRS ARE SHOWN ON THE
 INDIVIDUAL FLOOR PLANS, THEY ARE A PART OF THE
 EMERGENCY EGRESS AND THEREFORE REFLECTED AS SUCH.
  
  
  
 PG. E3.00, UNITS NOTES & LEGEND
 THIS IS PRIMARILY A NOTES PAGE AND HAS TWO ITEMS
 NEEDING CORRECTION. THESE SAME NOTES ARE TYPICAL
 THROUGHOUT THE DRAWINGS.
 1. NOTE 17 OF THE APARTMENT UNIT NOTES SHOULD BE
 AMENDED TO INCLUDE THE NEC 314.27 REQUIREMENT THAT THE
 CEILING BOXES BE RATED TO SUPPORT 50#. THIS NOTE HAS
 BEEN NOTED ELSEWHERE ON THE PLANS.
 2. I NOTICED THAT YOUR DESIGN INCLUDES CEILING FANS AND
 THEREFORE, APARTMENT SINGLE STATION SMOKE DETECTORS,
 NOTE 4 SHALL BE AMENDED TO INCLUDE 36? FROM THE TIP OF
 A CEILING FAN BLADE.
  
 PGS. E3.01, E3.02 & E3.03
 THE NOTES ON ALL OF THE SHEETS ARE THE SAME; THEREFORE
 THE FIRST THREE COMMENTS APPLY TO ALL.
 1. UNIT CODED NOTES, #4 SHALL INCLUDE THE TIP OF A
 CEILING FAN. (THE REGULATION INVOLVING THE KITCHEN IS
 ONLY THAT IF THE UNIT IS WITHIN 10? OF THE RANGE IT HAS
 TO BE SILENCEABLE).
 2. ADDITIONAL NOTES, #7 IS A REPEAT OF #4 ABOVE, & #2
 SHOULD BE AMENDED TO READ?AND BE RATED WEATHER
 RESISTANT ?WR? AS PER NEC 406.8.
 THE FOLLOWING ITEMS ARE ISSUES THAT WERE CLOUDED
 THROUGHOUT ALL THREE MODEL UNITS. THESE CLOUDS CAN BE
 SEEN BY VIEWING THE CHANGE MARK LAYERS.
 3. NEC 210.52 (A)(1) RECEPTACLES SHALL BE INSTALLED
 SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE
 FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A
 RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE
 EDGE OF THE WALL.
 4. NEC 210.52 (A)(2) ANY WALL SPACE 2 FT. OR MORE IN
 WIDTH SHALL HAVE AN OUTLET
 5. NEC 210.52(C)(1) A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTERTOP SPACE THAT IS 12 IN.
 OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT
 NO POINT ALONG THE WALL LINE IS MORE THAN 24 IN.
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.
 6. NEC 210.52(C)(3) AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH PENINSULAR COUNTERTOP.
 7. NEC 210.520(D) IN DWELLING UNITS, AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS
 WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN.
 8. NEC 210.70(A)(3) AT LEAST ONE LIGHTING OUTLET
 CONTAINING A SWITCH OR CONTROLLED BY A WALL SWITCH
 SHALL BE INSTALLED WHERE THESE SPACES ARE USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH SMC
 BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
  
 PG. E4.00A
 1. SOUND SYSTEM NOTES BOX SHALL HAVE AN ADDITIONAL LINE
 ITEM STATING THAT THE AUDIO SYSTEM SHALL BE MUTED VIA
 THE FACP IN THE EVENT OF AN ALARM CONDITION.
  
 PG. E4.00B
 1. ILLUMINATION ELECTRICAL NOTES #3, SEE CORRECTION TO
 NEC 700.12(F)
  
 PG. E4.01, E4.03, E4.05, E4.06, MAIN ELECTRICAL ROOM
 ?A?, ?B? & ?C?
 1. SEE CLOUDED AREA IN ELECTRICAL ROOM NOTES WHICH HAS
 TO BE CLARIFIED.
  
 PG. E4.02 & E4.09 MACHINE ROOMS
 1. ELEVATOR ELECTRICAL NOTES BOX, NOTRE #1 SHALL BE
 CORRECTED TO READ AS FOLLOWS: NEC 620.51.
  
 PG. E4.07, E4.08 ENLARGED TRASH ROOMS
 1. BOTH, TRASH ROOM A, B, C & D, HAVE THE SAME COMMENT
 AS FOLLOWS: CHECK FOR PROPER WORKING CLEARANCE AS PER
 NEC 110.26. THERE DOES NOT APPEAR TO BE SUFFICIENT
 CLEARANCE BETWEEN THE ELECTRICAL OUTLETS AND WHATEVER
 IS IN FRONT OF THEM.
  
 PG. E5.06
 1. CORRECT INCORRECTLY QUOTED NEC SECTION TO READ
 (410.130(G))
 2. CLARIFY YOUR INTENT AT THE OUTLET STUB UP DETAIL
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
2015-06-09 15:45:43SEE ATTACHMENTS FOR DERTAILS OF ELECTRICAL PLAN REVIEW
 RESULTS.
 FIRE ALARM REVIEW TO FOLLOW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-08-25 Cont ID  
Sent By mgonzale Date 2015-08-25 Time   Rev Time 1.00
Received By mgonzale Date 2015-08-25 Time   Sent To ENG
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By cranford Date 2015-05-21 Time 10:10 Rev Time 0.00
Received By cranford Date 2015-05-21 Time 09:43 Sent To  
Notes
2015-05-21 10:10:47ON SHEET LP-1, SHOW THE VISIBILITY TRIANGLE AT THE
 INTERSECTION OF ADAMS AND DIVISION.
  
 KELLY CRANFORD, PE
 LAND DEVELOPMENT ENGINEERING
 (561)494-1098
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-07 Cont ID  
Sent By wjolin Date 2015-10-07 Time 12:47 Rev Time 0.00
Received By wjolin Date 2015-10-07 Time 12:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-08-13 Cont ID  
Sent By wjolin Date 2015-08-13 Time 09:03 Rev Time 0.00
Received By wjolin Date 2015-08-12 Time 16:17 Sent To  
Notes
2015-08-13 08:41:41PERMIT #15050261 - 838 ADAMS STREET (66 UNITS)
 PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS)
 PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - THE FIRE DEPARTMENT REQUIRES PLANS
 AND PERMITS FOR ALL CONSTRUCTION RELATED TRAILERS AND
 MODULAR BUILDINGS. ADDITIONALLY PER NFPA 241- STANDARD
 FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS, SECTION 4.2: TEMPORARY OFFICES,
 TRAILERS, AND OTHER FACILITIES OF COMBUSTIBLE
 CONSTRUCTION OR HOUSING COMBUSTIBLE CONTENTS SHALL BE
 SEPARATED FROM ADJACENT BUILDINGS, TRAILERS OR
 STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. PER TABLE
 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - PER NFPA 241 SECTION 4.2.2:
 DETACHMENT BETWEEN TEMPORARY STRUCTURES, ADEQUATE
 TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND PORTABLE
 EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET PM-1: PER SECTION 18.2.3.5.3
 (NFPA 1), FIRE LANES SHALL BE MARKED WITH FREESTANDING
 SIGNS READING, "FIRE LANE - NO PARKING BY ORDER OF THE
 FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART. FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: FIRE MAINS SUPPLYING TWO
 OR MORE FIRE HYDRANTS WILL NEED TO BE LOOPED AND WILL
 NOT BE PERMITTED TO TERMINATE AT A DEAD END BLOWOFF
 CAP.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: THE FIRELINE BACKFLOW
 PREVENTERS SHALL COMPLY WITH NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.01A & SHEET E2.01B: PROVIDE
 TWO ADDITIONAL EXIT SIGNS IN THE EXIT ACCESS CORRIDOR
 NEAR COLUMN INTERSECTION B.1/1.2. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.07: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET E2.12: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT: SHEET FP2.04 NOW INCLUDES A STATEMENT
 THAT SPRINKLERS ARE BEING REQUIRED BY THE LOCAL
 JURISDICTION. THIS IS AN INCORRECT STATEMENT;
 COMBUSTIBLE CONCEALED ROOF SPRINKLER PROTECTION IS
 REQUIRED BY NFPA 13 SECTION 8.15. SHEET FP2.05 HAS NOT
 BEEN CORRECTED AT ALL.
 ORIGINAL COMMENT - SHEET FP2.04 & FP2.05: PLAN
 INDICATES NO SPRINKLER PROTECTION FOR THE
 NON-ACCESSIBLE TRUSS SPACE; CONTRARY TO NFPA 13 SECTION
 8.15. INDICATE A CODE REFERENCE PERMITTING THIS
 COMBUSTIBLE CONCEALED SPACE FROM BEING PROTECTED BY
 FIRE SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-22 Cont ID  
Sent By wjolin Date 2015-05-22 Time 12:30 Rev Time 0.00
Received By wjolin Date 2015-05-15 Time 13:12 Sent To  
Notes
2015-05-15 14:20:00PERMIT #15050261 - 838 ADAMS STREET (66 UNITS)
 PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS)
 PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE FIRE DEPARTMENT REQUIRES PLANS AND PERMITS FOR ALL
 CONSTRUCTION RELATED TRAILERS AND MODULAR BUILDINGS.
 ADDITIONALLY PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER
 FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING
 COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT
 BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL
 CONSTRUCTION WORK.
  
 SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 SHEET PM-1: PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT."
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A
 SURFACE DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING
 AT LEAST 36 TONS. ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 SHEET WS-1: FIRE MAINS SUPPLYING TWO OR MORE FIRE
 HYDRANTS WILL NEED TO BE LOOPED AND WILL NOT BE
 PERMITTED TO TERMINATE AT A DEAD END BLOWOFF CAP.
  
 SHEET WS-1: THE FIRELINE BACKFLOW PREVENTERS SHALL
 COMPLY WITH NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO
 PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS
 SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 COULD NOT LOCATE A DRAWING INDEX.
  
 COULD NOT LOCATE ANY LIFE SAFETY PLANS FOR THE PROPOSED
 POOL AREA AND CHILDRENS' PLAYGROUND AREA.
  
 SHEET A7.00: STAIRWAY IDENTIFICATION: 7.2.2.5.4.1 NEW
 ENCLOSED STAIRS SERVING THREE OR MORE STORIES SHALL
 COMPLY WITH 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET E2.01A & SHEET E2.01B: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION B.1/1.2. TYPICAL ALL LEVELS.
  
 SHEET E2.07: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE
 EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1.
 TYPICAL ALL LEVELS.
  
 SHEET E2.12: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE
 EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1.
 TYPICAL ALL LEVELS.
  
 SHEET FA1.00: COULD NOT LOCATE REMOTE ANNUNCIATOR
 PANEL. TYPICAL ALL 3 BUILDINGS.
  
 SHEET FA2.00: FIRE ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE.
  
 SHEET FP1.00: SEVERAL NOTES INDICATE THE 2007 EDITION
 OF NFPA 13. THE STATE OF FLORIDA HAS ADOPTED AND
 ENFORCES THE 2010 EDITION.
  
 SHEET FP2.00: THE NON-RESIDENTIAL PUBLIC SPACES ARE
 INDICATE THE SPRINKLERS ARE BEING FED FROM THE SECOND
 FLOOR SPRINKLER SYSTEM. PROVIDE A DEDICATED FLOW SWITCH
 FOR THIS AREA OR SUPPLY THIS AREA FROM THE FIRST FLOOR
 SPRINKLER SYSTEM TO ELIMINATE CONFUSION THAT THE FIRE
 EVENT IS LOCATED ON THE SECOND FLOOR.
  
 SHEET FP2.04 & FP2.05: PLAN INDICATES NO SPRINKLER
 PROTECTION FOR THE NON-ACCESSIBLE TRUSS SPACE; CONTRARY
 TO NFPA 13 SECTION 8.15. INDICATE A CODE REFERENCE
 PERMITTING THIS COMBUSTIBLE CONCEALED SPACE FROM BEING
 PROTECTED BY FIRE SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-11-28 Cont ID  
Sent By tklarge Date 2015-10-03 Time 14:17 Rev Time 0.00
Received By tklarge Date 2015-10-03 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-09 Cont ID  
Sent By cpuell Date 2015-10-09 Time 13:03 Rev Time 0.00
Received By cpuell Date 2015-09-30 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-09 Cont ID  
Sent By cpuell Date 2015-09-09 Time 14:05 Rev Time 0.00
Received By cpuell Date 2015-07-23 Time 18:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-28 Cont ID  
Sent By tklarge Date 2015-06-28 Time 08:24 Rev Time 0.00
Received By tklarge Date 2015-05-13 Time 13:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-12-01 Cont ID  
Sent By rbrown Date 2015-12-01 Time 11:50 Rev Time 0.00
Received By rbrown Date 2015-12-01 Time 11:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 05:36 Sent To  
Notes
2015-10-06 07:17:31IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By jwitmer Date 2015-08-18 Time 16:51 Rev Time 0.00
Received By jwitmer Date 2015-08-17 Time 06:31 Sent To  
Notes
2015-08-18 16:51:51IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 06:21 Rev Time  
Received By jwitmer Date 2015-06-07 Time 07:33 Sent To  
Notes
2015-06-08 06:21:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JUNE 07/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-05 Cont ID  
Sent By ccole Date 2015-10-05 Time 14:23 Rev Time 0.00
Received By ccole Date 2015-10-05 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-25 Cont ID  
Sent By ccole Date 2015-08-06 Time 14:08 Rev Time 0.00
Received By ccole Date 2015-08-06 Time 14:06 Sent To  
Notes
2015-08-06 14:20:592ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050261
 8/6/15
 .
 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- SECTION 503.2.1 FBC-10
 ENERGY CONSERVATION.
 2) SHEET M2.02: CLARIFY HOW THE DUCT SMOKE DETECTOR IN
 AHU-10 WILL BE SUPERVISED: PROVIDE A SEQUENCE OF
 OPERATION FOR FAN SHUT DOWN.
 3) SHEET M3.0: REVISE THE HVAC DESIGN TABLE TO INCLUDE
 THE FIRE DAMPERS IN THE "YES" COLUMN.
 4) PROVIDE INSTALLATION DETAILS FOR THE FIRE DAMPERS
 AND DUCT SMOKE DETECTORS.
 5) M3.0: THE 80 CFM TOILET EXHAUST FANS ARE UNDERSIZED
 PER TABLE 403.3 FBC-10 MECHANICAL- MINIMUM 100 CFM
 REQUIRED IN THE TOILET AREAS OF THE BATHROOMS.
 6) SHEET M3.01: WIND LOAD DESIGN PRESSURE CALCULATIONS
 AND TIE-DOWN ENGINEERING ARE REQUIRED FOR ANCHORING THE
 CONDENSER STANDS AND CONDENSER UNITS TO THE ROOF
 STRUCTURE- SECTION 301.12 FMC-10, AND SECTION 1609
 FBC-10 BUILDING. PLEASE REVISE THE DETAIL ACCORDINGLY
 AND CORRECT THE 150 MPH WIND LOAD SPECIFICATION.
 7) REMOVE SHEET A-10.08 SHOWING THE HILTI FIRESTOPPING
 DETAILS, THE ENGINEER OF RECORD HAS INDICATED IN HIS
 NARRATIVE RESPONSE TO BUILIDNGS 2 & 3 THAT HE HAS
 APPROVED THE TREMCO SYSTEM.
 8) 13) PROVIDE A SUBMITTAL PACKAGE WITH ALL DOCUMENTS
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD. PLEASE INCLUDE NOA'S, PRODUCT APPROVALS, AND
 MANUFACTURER'S SPECIFICATIONS FOR THE CONDENSER STANDS,
 THE EXHAUST AND O/A INTAKE FANS, THE O/A MOTORIZED
 DAMPERS, THE EXHAUST AND INTAKE WALL LOUVERS, THE
 ELEVATOR SHAFT MOTORIZED DAMPER, THE AC SYSTEMS, THE
 RINNAI GAS WATER HEATER AND VENT SYSTEM, THE FIRE
 DAMPERS, THE DUCT SMOKE DETECTORS, AND THE REFRIGERANT
 PIPE INSULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By hmoser Date 2015-06-16 Time 14:15 Rev Time 0.00
Received By hmoser Date 2015-06-16 Time 09:29 Sent To  
Notes
2015-06-16 14:15:51PLAN DENIED
  
 1) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST OUTLETS
 # 2 AND 501.2.1.1 EXHAUST DISCHARGE 2010 FBC (M)
 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 INCLUDING A/C CLOSET DOORS 2010 FBC (M)
 3) CITY OF WEST PALM BEACH FIRE RESCUE WILL NOT PERMIT
 DRYER BOOSTER FANS IN DRYER DUCT .
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-03 Cont ID  
Sent By tklarge Date 2015-10-03 Time 09:24 Rev Time 0.00
Received By tklarge Date 2015-10-03 Time 08:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-06 Cont ID  
Sent By tklarge Date 2015-08-06 Time 06:49 Rev Time 0.00
Received By tklarge Date 2015-08-06 Time 04:33 Sent To  
Notes
2015-08-05 08:23:151)THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. 2ND
 REQUEST.
 2) THE OVERFLOW RAINWATER DOWNSPOUTS SHALL DISCHARGE A
 MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL
 PER 2010 FBC 1503.7. PLACE A NOTE ON THE PLANS.THIS
 COMMENTS REFERS TO THE DOWNSPOUTS FROM THE GUTTERS.
 THEY ARE NOT UNDERGROUND.
 3) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL
 PROJECTED ROOF AREA" -1008 SQ. FT.- THIS DOES NOT ADD
 UP.PLEASE CLARIFY. IS THIS A TYPO ERROR?
 4) SHT. A2.05 - THIS BUILDING HAS TWO FLAT ROOFS
 IDENTIFY RWL-1 & RWL-2 ON THE PLANS. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.2ND REQUEST.
 5) THE STORM DRAINAGE RISER SHOWS OVERFLOW DRAINS, NOT
 SCUPPERS, YET THERE ARE TABLES FOR SCUPPER SIZING. ARE
 THERE OR ARE THERE NOT ROOF SCUPPERS ON THIS BUILDING?
 IF SO, SHOW THE LOCATION OF ALL SCUPPERS AND SHOW THE
 LENGTH AND HEIGHT DIMENSIONS OF THE SCUPPERS AND THE
 DESIGN HEAD ( IN INCHES). SCUPPERS SHALL BE SIZED PER
 THE 2010 FBC-PLUMBING TABLE 1106.7. IF NOT, DELETE ANY
 REFERENCE/TABLE TO ROOF SCUPPERS.
 6) SUBMIT GUTTER CALCULATIONS FOR THE ROOF GUTTERS AND
 DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & 1106.7.
 2ND REQUEST.
 7) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS ( IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 8) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS (IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS. COMPLY
 WITH 2010 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1)
 THROUGH 1106.2 (2), 1106.3,1106.7.
 9) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF DRAIN
 CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. SUBMIT
 ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND SHOW
 THE LOCATION OF THE SCUPPERS ( IF APPLICABLE ) AND
 PROVIDE SCUPPER CALCULATIONS.COMPLY WITH 2010
 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) THROUGH
 1106.2 (2), 1106.3,1106.7.
 10) SHT. P1.00 - SHOWS A 2 INCH WATER SERVICE TO
 BUILDING #2 AND SHT. WS-1 SHOWS A 4 INCH WATER SERVICE.
 CLARIFY. 2ND REQUEST. THE CIVIL PLANS STILL SHOW A 4
 INCH WATER LINE. WHICH IS IT? THE PLANS SHALL
 CORRELATE.
 11) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2ND REQUEST. THE RESPONSE STATED THEY WILL BE PROVIDED.
 WHEN?
 12) SHT. P4.00 - SHOW THE TONNAGE OF THE AIR
 CONDITIONING EQUIPMENT ON THE CONDENSATE RISER. COMPLY
 W/ TABLE 314.2.2. OF 2010 FPC. THE PLAN WAS ONLY
 CORRECTED FOR BUILDING #1. CORRECT THE PLAN FOR THE
 OTHER BUILDINGS. 2ND REQUEST.
 13) SUBMIT THE MANUFACTURER SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1. I CANNOT DETERMINE IF
 THE VENT LOCATIONS ARE APPROVED AND TO CODE WITHOUT THE
 INSTALLATION MANUAL THAT SHOWS THE REQUIREMENTS. MY
 CONCERNS ARE THAT THIS IS A DIRECT VENT APPLIANCE AND
 THE CLOSE PROXIMITY TO AN EXHAUST DUCT MAY CREATE A
 CODE ISSUE.2010 FBC-FUEL GAS CODE SEC.503.2.3.
 14) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 SUBMIT A DETAIL THAT SHOWS ALL THE PIPING. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1. 2ND REQUEST.
 15) IDENTIFY THE OVERFLOW DRAINS ON ALL THE ROOF PLANS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P1.00 - CLEARLY SHOW WHERE THE WATER SERVICE
 ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 17) THE AREA OF THE SLOPED ROOFS THAT ARE DRAINING ONTO
 THE LOWER ROOFS SHALL BE INCLUDED IN THE ROOF DRAINAGE
 CALCULATIONS. THIS WAS OVERLOOKED IN FIRST REVIEW.2010
 FBC -PLUMBING SECS.1106.2 & 1106.3.
 18) THE PLUMBING DRAWINGS REFER TO THE ARCHITECTURAL
 PLANS FOR DOWNSPOUT DETAILS. I COULD NOT FIND ANY
 DOWNSPOUT DETAILS IN THE ARCHITECTURAL PLANS. CLARIFY.
 19) NOTE #14 ON THE ENLARGED ARCHITECTURAL FLOOR PLANS
 REFER TO THE ARCHITECTURAL AND PLUMBING DRAWINGS FOR
 DETAILS FOR THE GUTTERS AND DOWNSPOUTS. I COULD NOT
 FIND ANY DETAILS ON ANY OF THESE PLANS. CLARIFY.
 20) AS UPLOADED, ALL THE PLUMBING DRAWINGS ARE LABELED
 AS "P' DRAWINGS. THERE IS NO WAY TO DISCERN WHICH
 DRAWINGS ARE FOR BUILDING #1, #2 OR #3. PLEASE SUBMIT
 ONLY THE DRAWINGS THAT ARE APPLICABLE TO THIS PERMIT
 AND THIS BUILDING. THIS APPLIES TO ALL THE DRAWINGS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 21) SEVERAL RESPONSES ON THE PLAN REVIEW COMMENT STATE
 "REFER TO REVISED ROOF PLAN" OR "SEE ARCHITECTURAL
 DRAWINGS." THESE RESPONSES ARE VAGUE AND INCONCLUSIVE.
 PLEASE PROVIDE THE SPECIFIC DRAWING NUMBER WHEN
 REFERENCING PLAN SHEETS.. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-28 Cont ID  
Sent By tklarge Date 2015-06-28 Time 08:24 Rev Time 0.00
Received By tklarge Date 2015-06-27 Time 03:03 Sent To  
Notes
2015-06-27 12:04:051) THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5.
 2) RAINWATER DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF
 ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL PER 2010 FBC
 1503.7.
 3) THE ROOF DRAINAGE CALCULATIONS FOR THE DESIGN OF THE
 STORMWATER SYSTEM SHALL INCLUDE ONE-HALF OF THE AREA OF
 ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 PER THE 2010 FPC SEC.1106.4. SHOW THAT THIS HAS BEEN
 DONE WITH THE SIZING OF THE STORM DRAINAGE SYSTEM.
 4) SHT. A2.05 - SCUPPER CALCULATION - SEE ROOF SQ.FT.
 W/PARAPET.- THE SQUARE FOOTAGE CANNOT BE READ. CLARIFY.
 5) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL
 PROJECTED ROOF AREA -1008 SQ. FT." PLEASE CLARIFY. IS
 THIS A DISCREPANCY?
 6) SHT. A2.05 - SHOW THE LOCATION OF THE SCUPPERS ON
 THE PLAN AND THE LOCATION OF RWL-1 & RWL-2. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SUBMIT GUTTER CALCULATIONS FOR THE GABLE END GUTTERS
 AND DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 &
 1106.7.
 8) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 9) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 10) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF
 DRAIN CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY.
 SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND
 SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE SCUPPER
 CALCULATIONS.
 11) SHT. P1.00 - SHOWS A 2" WATER SERVICE TO BUILDING
 #2 AND SHT. WS-1 SHOWS A 4? WATER SERVICE. CLARIFY.
 12) SHT. P1.00 - SHOW THE TERMINATION POINTS OF THE
 STORM AND CONDENSATE DRAINS ON THE PLANS. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 13) SHT. P2.00 - PLANS REFER TO THE CIVIL DRAWINGS FOR
 THE CONTINUATION OF THE STORM AND CONDENSATE DRAINS.
 THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS.
 CLARIFY.
 14) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 15) AIR CHAMBERS ARE NOT PERMITTED FOR WATER HAMMER.
 DELETE ALL REFERENCE ON THE PLUMBING PLANS TO AIR
 CHAMBERS. A WATER HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK - CLOSING VALVES ARE UTILIZED. FPC
 SEC.604.9.
 16) SHT. P4.00 - SHOW THE TONNAGE OF THE EQUIPMENT ON
 THE CONDENSATE RISER. COMPLY W/ TABLE 314.2.2. OF 2010
 FPC
 17) SUBMIT THE MANUFACTURER SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 18) SHOW THE LOCATION OF ALL THE GAS VENTS FROM THE
 TANKLESS WATER HEATERS.
 19) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By jwitmer Date 2015-10-06 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2015-10-06 Time 05:34 Sent To  
Notes
2015-10-06 07:35:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK
 CONTACT: JORGE COSTAS
 TEL: (305)665-1146
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. OCT.06/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 5 STORY/BLDG TYPE: I-B/ R2
  
 ACTION: PROVISO
  
  
 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF
 TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By jwitmer Date 2015-08-18 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2015-08-17 Time 06:31 Sent To  
Notes
2015-08-18 16:53:02ROOFING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. AUG. 18/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 1A) NO PRODUCT APPROVALS FOR ROOFING, NOR
 PRE-ENGINEERED A/C STANDS, OR ROOF CURBS WERE SUBMITTED
 UNDER THE 1ST REVIEW.
 COMPONENTS & CLADDING
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 1B) ROOFING PRODUCT APPROVALS, IDENTIFY (CIRCLE) THE
 SUB-SYSTEM THAT WILL BE INSTALLED, IDENTIFY THE PSI AND
 LIMITATIONS SET FOR THE SUB-SYSTEM. IF THE LIMITATIONS
 ALLOWS FOR ENHANCED FASTENING BY A DESIGN PROFESSIONAL,
 USE RAS 117 CALCULATIONS, SIGNED AND SEALED
 CALCULATIONS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2015-06-07 Time 07:34 Sent To  
Notes
2015-06-08 06:20:36ROOFING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JUNE 07/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 1A) NO PRODUCT APPROVALS FOR ROOFING, NOR
 PRE-ENGINEERED A/C STANDS, OR ROOF CURBS WERE SUBMITTED
 UNDER THE 1ST REVIEW.
 COMPONENTS & CLADDING
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 1B) ROOFING PRODUCT APPROVALS, IDENTIFY (CIRCLE) THE
 SUB-SYSTEM THAT WILL BE INSTALLED, IDENTIFY THE PSI AND
 LIMITATIONS SET FOR THE SUB-SYSTEM. IF THE LIMITATIONS
 ALLOWS FOR ENHANCED FASTENING BY A DESIGN PROFESSIONAL,
 USE RAS 117 CALCULATIONS, SIGNED AND SEALED
 CALCULATIONS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-10-27 Cont ID  
Sent By cpuell Date 2015-10-27 Time 11:16 Rev Time 0.00
Received By cpuell Date 2015-10-27 Time 11:16 Sent To  
Notes
2015-10-27 11:16:42OK PER SKENNEDY
2015-05-13 16:33:01RECEIVED HARDCOPY SIGNED & SEALED ARDAMAN & ASSOCIATES
 SOILS REPORTS (WITH APPLICATION).

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-09 Cont ID  
Sent By jroach Date 2015-10-09 Time 09:32 Rev Time 0.00
Received By jroach Date 2015-10-09 Time 09:32 Sent To  
Notes
2015-10-09 09:36:55ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.09.2015
 PERMIT NO.: 15050261
 ADDRESS: 838 ADAMS STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT
 HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO.
 72-15.
  
 2. SEPARATE PERMITS SHALL BE OBTAINED FOR THE
 FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III)
 IRRIGATION.
  
 3. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE
 LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC
 LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT
 THE PROPERTY LINE.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE PROPERTY SHALL BE RE-PLATTED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-08-24 Cont ID  
Sent By jroach Date 2015-08-24 Time 15:52 Rev Time 0.00
Received By jroach Date 2015-08-24 Time 14:07 Sent To  
Notes
2015-08-24 16:02:36ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.24.2015
 PERMIT NO.: 15050261, 15050262, 15050263
 ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807
 DIVISION AVENUE
 CONTRACTOR/CONTACT: ???
 TELEPHONE NO.: ???
 SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT
 HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO.
 72-15, AS WELL AS THE FOLLOWING WHICH WERE CONDITIONS
 OF APPROVAL:
  
  I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS
 WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE
 (IN ALIGNMENT WITH 17TH STREET).
  
  II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF
 THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3.
  
 2. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED.
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED
 COST ESTIMATE (MATERIAL + LABOR).
  
 3. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED
 INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING
 THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX.
  
 4. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED
 THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE
 DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE
 NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.).
  
 5. ON SHEET A1.01, DETAIL 3 DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS WITH REGARD TO SIZE, AND DOESN'T MATCH WHAT
 IS SHOWN ON THE PLANS.
  
 6. THE SITE LIGHTING SHOWN ON SHEET E-1.00 AND E-1.10
 DO NOT MATCH. AND PHOTOMETRIC LEVELS SHALL BE SHOWN AT
 THE PROPERTY LINE, NOT EXCEEDING 0.5 FOOTCANDLES.
  
 7. IN AN EMAIL TO JON SCHMIDT & ASSOCIATES ON
 8/24/2015, SEVERAL AREAS OF CONCERN WERE IDENTIFIED
 WHERE IT APPEARS THAT THE LOCATION OF UTILITIES, SIGHT
 LIGHTING, ETC. HAVE CREATED DEFICIENCES OR CONFLICTS
 WITH LANDSCAPING. THESE AREAS SHOULD BE EVALUATED AND
 ADJUSTED ACCORDINGLY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  
 5/19/15

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-05 Cont ID  
Sent By jroach Date 2015-06-05 Time 16:01 Rev Time 0.00
Received By jroach Date 2015-06-05 Time 16:01 Sent To  
Notes
2015-06-05 16:02:01ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.04.2015
 PERMIT NO.: 15050261, 15050262, 15050263
 ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807
 DIVISION AVENUE
 CONTRACTOR/CONTACT: ???
 TELEPHONE NO.: ???
 SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL
 DEVELOPMENT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 72-15, PRIOR TO THE
 ISSUANCE OF A PERMIT:
  
 A. A MINOR AMENDMENT SHALL BE SUBMITTED TO THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION FOR
 THE FOLLOWING:
  
  I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS
 WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE
 (IN ALIGNMENT WITH 17TH STREET).
  
  II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF
 THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3.
  
 2. REMINDER - PRIOR TO THE ISSUANCE OF ANY CERTIFICATE
 OF OCCUPANCY, THE PROPERTY SHALL BE RE-PLATTED IN
 ACCORDANCE WITH ALL APPLICABLE STATUTES, REGULATIONS,
 AND THE CITY'S POLICIES AND PROCEDURES.
  
 3. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED.
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED
 COST ESTIMATE (MATERIAL + LABOR).
  
 4. REMINDER - ALL UTILITIES WITHIN THE RPD SHALL BE
 LOCATED UNDERGROUND.
  
 5. THE EAST-WEST ROADWAY EXTENDING WEST FROM DIVISION
 AVENUE (IN LINE WITH ADAMS STREET), SHALL BE
 INCORPORATED INTO ALL PERMIT MATERIALS FOR THIS PROJECT
 AS IT IS REQUIRED TO BE COMPLETED IN ASSOCIATION WITH
 SILVER PALM PLACE.
  
 6. PLEASE CONFIRM THAT THE PROPOSED DESIGN, RADIUS,
 MATERIALS, LOAD, ETC. FOR THE ROUNDABOUT WILL BE
 ACCEPTABLE TO THE CITY'S FIRE-RESCUE DEPARTMENT; OR ARE
 THEY ACCEPTABLE OF DRIVING THROUGH THE PARKING AREA?
 SIGNAGE MAY BE REQUIRED.
  
 7. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED
 INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING
 THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX.
  
 8. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED
 THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE
 DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE
 NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.).
  
 9. PLEASE CONSULT WITH THE CITY'S TRAFFIC ENGINEER AS
 TO WHETHER OR NOT THE EAST-WEST ROADWAYS SHOULD BE
 SIGNED AS "ADAMS STREET" AND "17TH STREET". THESE WILL
 NOT BE DEDICATED ROADWAYS. ADDITIONALLY, I DON'T IF THE
 PROPER ADDRESSES HAVE BEEN ASSIGNED BECAUSE OF THIS.
  
 10. THE UTILITIES SHOWN ON THE WATER & SEWER PLANS DO
 NOT MATCH WHAT WAS SHOWN ON THE LANDSCAPE PLANS. PLEASE
 ENSURE THAT THE PLANS ARE CONSISTENT AND THAT THERE ARE
 NO CONFLICTS. ADDITIONALLY, THE LANDSCAPE PLANS SHALL
 ENSURE THAT ALL MECHANICAL EQUIPMENT, METERS, BACKFLOW
 PREVENTERS, ETC. ARE SCREENED AS REQUIRED.
  
 11. THERE IS AN FDC CONNECTION SHOWN IN A LANDSCAPE
 ISLAND NEAR BUILDING #2 THAT APPEARS TO CONFLICT WITH A
 PROPOSED SHADE TREE. THE FDC MAY NEED TO BE RELOCATED.
  
 12. PLEASE ENSURE THAT THERE IS NO CONFLICT BETWEEN THE
 LANDSCAPING AND THE PROPOSED FIRE HYDRANT LOCATED IN
 THE PARKING LOT ISLAND BETWEEN BUILDINGS #2 AND #1
 (SOUTH OF THE ROUNDABOUT).
  
 13. ON SHEET A1.01, DETAIL 1 SHOULD SHOW A MINIMUM OF 5
 FEET OF LANDSCAPING ISLAND FROM THE INSIDES OF THE
 CURBING.
  
 14. ON SHEET A1.01, DETAILS 3 AND 3.1 DO NOT MEET THE
 MINIMUM REQUIREMENTS OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS WITH REGARD TO SIZE, STRIPING,
 ETC.
  
 15. ON SHEET A1.01, DETAIL 9, THE LANDSCAPING IS ON THE
 WRONG SIDE OF THE CONCRETE PAD, AND THE BIKE RACKS MAY
 BE ORIENTED IN THE WRONG DIRECTION ON THE SITE PLAN.
 THE BIKE RACK SHOULD BE ORIENTED SUCH THAT TWO (2)
 BIKES CAN BE EASILY PUSHED INTO PLACE ON EITHER SIDE OF
 THE RACK.
  
 16. ON SHEET A1.00, NOTES #9 AND #10 ARE REVERSED.
  
 17. ON SHEET A-1.02, THE STAIR FLOOR PLANS REFER TO THE
 INCORRECT SHEET FOR THE CROSS SECTIONS.
  
 18. IN LOOKING AT THE BUILDING PERMITS, THE ARCHITECT'S
 PLANS ARE SHOWING THAT THE FIRST FLOOR OF THE UNITS ON
 DIVISION AVENUE IS 4-5 FEET (OR MORE IN SOME AREAS)
 ABOVE GRADE. THIS LEAVES A LARGE AREA UNDERNEATH THE
 FIRST LEVEL OF WINDOWS. ALL THAT'S PROPOSED ON THE
 LANDSCAPE PLAN IS SOD WITH A 24 INCH HIGH ROW OF
 "SEMINOLE PINK HIBISCUS". ADDITIONAL PLANTINGS SHALL BE
 PROVIDED TO ADDRESS THE SCALE OF THE BASE OF THE
 BUILDING.
  
 19. LANDSCAPE SCREENING SHALL BE PROVIDED AROUND THE
 PROPOSED FPL TRANSFORMERS (UNLESS OTHERWISE PROHIBITED
 BY FPL).
  
 20. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN
 THE PROPOSED SITE LIGHTING AND THE LANDSCAPING.
  
 21. LANDSCAPE SCREENING AND FENCING SHALL BE PROVIDED
 FOR THE POOL EQUIPMENT.
  
 22. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN
 THE PROPOSED FPL TRANSFORMERS AND THE LANDSCAPING.
  
 23. PLEASE PROVIDE CROSS SECTIONS AT THE LOCATIONS OF
 THE ROOF-TOP MECHANICAL EQUIPMENT TO INDICATE THAT ALL
 EQUIPMENT WILL BE ADEQUATE SCREENED WITH THE PROPOSED
 PARAPETS, ETC. PLEASE SHOW THE MECHANICAL EQUIPMENT
 (ACCURATELY SIZED) IN THE CROSS SECTION.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 WWW.WPB.ORG
  
2015-05-19 11:22:175/19/15