Plan Review Details - Permit 15050261
| Plan Review Stops For Permit 15050261 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-06 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-06 |
Time |
05:32 |
Sent To |
|
|
| Notes |
| 2015-10-06 07:33:13 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: LANDMARK | | | CONTACT: JORGE COSTAS | | | TEL: (305)665-1146 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS | | | ADOPTED APRIL 25/2013. | | | | | | 3RD REVIEW | | | DATE: TUES. OCT.06/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 5 STORY/BLDG TYPE: I-B/ R2 | | | | | | ACTION: PROVISO | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE | | | ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING, | | | SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY | | | AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION | | | OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL | | | NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH | | | ASSOCIATED COST. | | | | | | 1) PROVISO: NOTICE! ART IN PUBLIC PLACES | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | | | | 2A-B) COMPLIED. | | | | | | | | | 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING | | | FLORIDA S. S. 553.71(7) | | | ?THRESHOLD BUILDING" . | | | | | | 3E) 3RD REQUEST!!! NOTE TO DATE NO PERMIT APPLICATION | | | WHERE THE OWNER HAS SIGNED AND THEIR SIGNATURES | | | NOTARIZED. AHOLD WILL BE PUT ON THE PERMIT NOT TO ISSUE | | | UNTIL THE OWNERS SIGNATURE IS ON THE PERMIT | | | APPLICATION. | | | | | | 3F)NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS. | | | | | | 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM | | | BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) PROVISO: CALCULATED FEES ENTERED INTO FEE SCHEDULE. | | | 10/06/2015 | | | CALCULATED VALUE: | | | BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00 | | | BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00 | | | | | | | | | 5-9) COMPLIED | | | | | | 10) SHEET A-200A: | | | 10A) COMPLIED. | | | | | | 10B) REVISION REQUIRED. 3RD REQUEST. BETWEEN DWELLING | | | UNITS AND DWELLING UNITS AND COMMON AREAS WALL TYPE W5 | | | HAS BEEN INDICATED A 6 INCH CONCRETE REINFORCED WALL | | | WITH NO INSULATION. PLEASE PROVIDE DOCUMENTATION THAT | | | COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN ACHIEVED. | | | | | | RESPONSE: WALL SOUND INSULATION THAT HAS ALREADY BEEN | | | TESTED, IS FOUND ON SHEET A9.04 ALSO WALL TYPE SHEET | | | A-8.01. NOTE THESE ARE SALES BROCHURES; THEY ARE NOT | | | THE ACTUAL TEST. PROVIDE TEST REPORTS. | | | | | | | | | | | | 11-19) COMPLIED. | | | | | | 20)(A)REVISION REQUIRED: 3RD REQUEST. SHEET A4.02 | | | INDICATES 6 INCH CONCRETE SLAB. SHEET A-9.04 INDICATES | | | THE USE OF (2) FLOOR INSULATION PRODUCTS, DB-4LOORING | | | INSULATION, AND QT SCU 4002 PLEASE SUBMIT THE REPORTS | | | FOR COMPLIANCE WITH 20A-20C, MISSING FLAME SPREAD. | | | | | | 20)(B) REVISION REQUIRED: 3RD REQUEST. SHEET A-9.04 | | | ALSO SHOWS A WALL INSULATION TYPE DB-3, THIS IS A SALES | | | BROCHURE PLEASE SUBMIT TEST INFORMATION, WALL | | | INSULATION WILL NEED TO COMPLY WITH 1207.2 THE SALES | | | BROCHURE SUBMITTED IS FOR WOOD AND METAL STUDS, NEVER | | | TESTED ON A 6 INCH CONCRETE WALL. WALL INSULATION WILL | | | NEED TO MEET 1207.2 ASTM E 90 AND SECTION 2010 FBC-B | | | 719.2 CONCEALED INSULATION FLAME SPREAD INDEX OF NOT | | | MORE THAN 25 AND A SMOKE DEVELOPMENT OF 450. | | | | | | | | | 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 21-22) COMPLIED. | | | | | | 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS. | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW | | | THEM AND FORWARD THEM TO THE | | | BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 23A) )PROVISO: FOR GLAZED PRODUCT APPROVALS, IDENTIFY | | | THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, | | | IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE | | | INSTALLED, PRESSURES, AND FASTENERS. | | | | | | 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF. | | | HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE | | | PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117 | | | CALCULATIONS, AND SIGNED & SEALED CALCULATIONS. | | | | | | 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF | | | TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF | | | FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED | | | PRESSURES. | | | | | | 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE | | | CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE | | | PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE | | | PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN | | | DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE | | | DEFERRED SUBMITTALS. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | | APPROVED BY THE BUILDING OFFICIAL. | | | | | | 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. | | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-08-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-18 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-17 |
Time |
06:30 |
Sent To |
|
|
| Notes |
| 2015-08-18 16:51:05 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: TBD/ TO BE DETERMINED | | | CONTACT: ALBERT OVIEDO | | | TEL: (??????? | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: TUES. AUGUST 18/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 4 STORY/ R2 | | | | | | ACTION: DENIED | | | | | | THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE | | | ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING, | | | SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY | | | AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION | | | OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL | | | NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH | | | ASSOCIATED COST. | | | | | | 1) NOTICE! ART IN PUBLIC PLACES | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | | | | 2A-B) COMPLIED. | | | | | | 2C) THE ELECTRONIC PLANS SUBMITTED 368 PAGES ARE PLANS | | | SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS | | | HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS. | | | THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO | | | BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE | | | COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS | | | SHOULD HAVE PULLED THE SHEETS THAT DID NOT PERTAIN TO | | | THAT BUILDING AND DETAIL SHEETS, DETAILS NOT PERTAINING | | | TO THAT BUILDING STRUCK THROUGH. 107.2.1.4 QUALITY OF | | | BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS | | | AND SPECIFICATIONS, IN ORDER TO PROVIDE UNIFORMITY TO | | | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE | | | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, | | | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. | | | ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE | | | REQUIREMENTS OF FLORIDA STATUTES. THIS CODE SECTION IS | | | FOR RECORD RETENTION BUT THE REALITY OF THIS IS, THE | | | WAY THESE PLANS WERE SUBMITTED, IT IS VERY DIFFICULT TO | | | FIND WHERE TO LOOK FOR CODE COMPLIANCE!!!!!!! | | | | | | 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING | | | FLORIDA S. S. 553.71(7) | | | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. | | | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 3A) 2ND REQUEST, THE RESPONSE INDICATES THE WRITTEN | | | THRESHOLD INSPECTION PLAN WAS SUBMITTED PLEASE INDICATE | | | WHERE IT CAN BE LOCATED? | | | THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 3B) COMPLIED. THRESHOLD INSPECTOR: WPB AMENDMENT | | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE | | | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT | | | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO | | | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT | | | ISSUANCE WILL TAKE PLACE. CONTACT KEN CONRAD MANAGER OF | | | THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR | | | FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO | | | E-MAIL ADDRESS: [email protected] | | | FORMS SENT AT SUN. JUNE 07/2015 08:51 AM. | | | | | | 3C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE | | | A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. | | | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 3E) NOTE TO DATE NO CONTRACTOR HAS SUBMITTED A PERMIT | | | APPLICATION WHERE THE OWNER AND QUALIFIER HAVE SIGNED | | | AND THEIR SIGNATURES NOTARIZED. | | | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO | | | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] | | | | | | 3F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS. | | | | | | 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM | | | BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN | | | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING | | | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT | | | THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING | | | PENETRATIONS, FOR WALLS AND CEILINGS. | | | | | | 4) THE PERMIT VALUE OF $11,712,570.25 IS LOW. THERE IS | | | A DISCREPANCY IN THE BUILDING TYPE FOR BUILDING # 1, SO | | | THE VALUATION IS FIGURED FOR BOTH BUILDING TYPES. | | | CALCULATED VALUE: | | | BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00 | | | BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00 | | | | | | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 5)2ND REQUEST. SAFEGUARDS DURING CONSTRUCTION; | | | 5A) 2010 FBC-B 3306.2 WALKWAYS | | | 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES | | | 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN | | | HEIGHT. | | | 5D) 2010 FBC-B 3306.5 BARRIERS | | | 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS | | | 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY | | | 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE | | | EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR | | | OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED | | | DECKING OR FLOORING. | | | | | | 6) 2ND REQUEST. THE PERMIT APPLICATION CAME IN AS A | | | TBD, TO BE DETERMINED. A HOLD WILL BE PUT ON THE | | | ISSUANCE OF THIS PERMIT TO VERIFY LICENSURE | | | REQUIREMENTS THAT THE CONTRACTOR HOLDS THE APPROPRIATE | | | LICENSURE FOR A 5 STORY BUILDING. FLORIDA S. S. | | | 489.113. | | | | | | 7) SHEET A-0.01: | | | 7A)2ND REQUEST. THE CONSTRUCTION TYPE IS LISTED FOR | | | BLDG # 1 AS II-B BUILDING, WHEREAS UNDER THE HEADING OF | | | FIRE RESISTANCE RATING THE BUILDING IS LISTED AS | | | CONSTRUCTION TYPE I-B. THIS DISCREPANCY IN THE PLANS | | | WILL AFFECT THE REQUIREMENTS IN TABLE 601. 107.2.1.3, | | | ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THAT | | | FIRE RESISTANCE RATINGS AND ALLOWABLE HEIGHT AND AREA | | | ARE FOR A CONSTRUCTION BLDG. TYPE I-B. FOR THE PURPOSE | | | OF THIS REVIEW A BLDG. TYPE I-B WILL BE ASSUMED. | | | | | | 7B) 2ND REQUEST. UNDER THE HEADING CONSTRUCTION TYPE IS | | | FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR | | | SINCE THERE ARE BLDGS. 2 & 3 ON THE SAME LINE AS | | | BUILDING # 1. | | | | | | THE REAL QUESTION IS WILL THERE BE (2) TYPES OF FIRE | | | SPRINKLERS, FOR BUILDING # 1 WILL REQUIRE THE NFPA 13 | | | FIRE SPRINKLER IN COMPLIANCE WITH FBC-B 903.3.1.1 AND | | | WILL BUILDINGS 2 & 3 HAVE THE SAME TYPE OF FIRE | | | SPRINKLERS OR WILL THEY HAVE A NFPA 13-R INCOMPLIANCE | | | WITH FBC-B 903.3.1.2. IF BOTH SYSTEMS ARE GOING TO BE | | | INSTALLED PLEASE LIST THEM IN THE BUILDING MATRIX FOR | | | EACH BUILDING TYPE. | | | | | | 8-9) COMPLIED. | | | | | | 10) SHEET A-200A: | | | 10A) THIS COMMENT WILL BE FOR THE 1ST FLOOR LS-1.01 | | | UNIT B NEXT TO STAIR # 2. THE FRONT ENTRY DOORS DO NOT | | | INDICATE A DOOR IDENTIFICATION TAG, PLEASE PROVIDE | | | COMPLIANCE WITH 2010 FBC-B TABLE 715.4. | | | | | | 10B) 2ND REQUEST. BETWEEN DWELLING UNITS AND DWELLING | | | UNITS AND COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED | | | A 6 INCH CONCRETE REINFORCED WALL WITH NO INSULATION. | | | PLEASE PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 | | | FBC-B 1207.2 HAS BEEN ACHIEVED. | | | | | | | | | | | | 11-19) COMPLIED. | | | | | | 20)2ND REQUEST. SHEET A-9.04 INDICATES THE USE OF (2) | | | FLOOR INSULATION PRODUCTS, EASY MAT AND KNAUF | | | INSULATION, PLEASE SUBMIT THE REPORTS FOR COMPLIANCE | | | WITH 20A-20C. | | | | | | PLEASE NOTE WITH THE DESIGNER OF RECORD SPECING OUT THE | | | USE OF EASY MAT WE CANNOT APPROVE THESE CODE SECTIONS. | | | TO DATE NO CONTRACTOR, SUPPLIER OR MANUFACTURER HAS | | | BEEN ABLE TO PROVIDE TESTING REPORTS FOR THE SOUND | | | REQUIREMENTS OF ASTM E 492 AND ASTM E 90. WE DO HAVE A | | | FLAME SPREAD TEST THAT WILL PASS A BUILDING TYPE I OR | | | II BUT NOT THE MORE RESTRICTIVE REQUIREMENT FOUND FOR | | | BUILDING TYPE IIIB. SEE 719.2 CONCEALED INSTALLATION. | | | | | | 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 21-22) COMPLIED. | | | | | | 23)2ND REQUEST. EITHER THE DESIGNER OF RECORD OR THE | | | CONTRACTOR CAN ELECT TO SUBMIT THE PRODUCT APPROVALS | | | AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL UNDER | | | 107.3.4.2, THIS IS A WRITTEN REQUEST, OTHERWISE WE WILL | | | NEED THE PRODUCT APPROVALS TO REVIEW FOR CODE | | | COMPLIANCE. PLEASE NOTE TO IDENTIFY, OPENING SIZES, | | | TYPE OF GLAZING, PRESSURES, TYPE OF FASTENERS, MULLIONS | | | ETC. | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 23A) 2ND REQUEST. FOR GLAZED PRODUCT APPROVALS, | | | IDENTIFY THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED | | | OPENING, IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE | | | INSTALLED, PRESSURES, AND FASTENERS. | | | | | | 23B)2ND REQUEST. FOR ROOFING APPROVALS: FLAT ROOF. | | | HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE | | | PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117 | | | CALCULATIONS, AND SIGNED & SEALED CALCULATIONS. | | | | | | 23C)2ND REQUEST. FOR THE SLOPED ROOF: PROVIDE THE TYPE | | | OF TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF | | | FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED | | | PRESSURES. | | | | | | 23D) 2ND REQUEST. EITHER THE DESIGN PROFESSIONAL OR THE | | | CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE | | | PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE | | | PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN | | | DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE | | | DEFERRED SUBMITTALS. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | | APPROVED BY THE BUILDING OFFICIAL. | | | | | | 24) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. | | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-08 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-07 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2015-06-08 13:04:50 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: TBD/ TO BE DETERMINED | | | CONTACT: ALBERT OVIEDO | | | TEL: (??????? | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SUN. JUNE 07/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 4 STORY/ R2 | | | | | | ACTION: DENIED | | | | | | THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE | | | ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING, | | | SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY | | | AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION | | | OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL | | | NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH | | | ASSOCIATED COST. | | | | | | 1) NOTICE! ART IN PUBLIC PLACES | | | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | | | | 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH AMENDMENTS | | | TO THE FLORIDA BUILDING CODE, CHAPTER 1, 107.2.1. | | | INFORMATION ON CONSTRUCTION DOCUMENTS. ELECTRONIC MEDIA | | | DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE | | | BUILDING OFFICIAL. THERE IS NO INDEX SHEET IN THE SET | | | OF PLANS. THERE IS 386 PAGES OF PLANS, WITHOUT AN INDEX | | | SHEET TO BE ABLE TO IDENTIFY THE TYPE OF DRAWING IT | | | WILL TAKE A LONGER TIME TO COMPLETE REVIEWS AND SUBJECT | | | TO NEW COMMENTS BECAUSE OF NOT BEING ABLE TO IDENTIFY | | | WHERE TO FIND INFORMATION. | | | THIS PLAN SHOULD HAVE BEEN KICKED BACK AT PERMIT | | | SUBMISSION. | | | | | | 2B) 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN | | | APPROVED BY THE BUILDING OFFICIAL. THIS PLAN DOES NOT | | | FOLLOW THE NAMING CONVENTION FOR EACH PAGE WITHIN THE | | | SET OF PLANS AND SHOULD HAVE BEEN DENIED AT TIME OF | | | ELECTRONIC SUBMISSION. THE ARCHITECTURAL SHEETS ARE NOT | | | IN ORDER BECAUSE OF THE NAMING CONVENTION WAS NOT | | | FOLLOWED, THE A1. SHEETS JUMP TO A-10 SERIES TO A-11 | | | SERIES THEN TO A-2SERIES. THE PLANS DO NOT MEET THE | | | CITY STANDARD FOR ELECTRONIC MEDIA REQUIRED BY THE | | | ELECTRONIC PLAN REVIEW LIBERIAN, CAROLINE PUELL. PLEASE | | | CONTACT MS. PUELL AT 805-6659 FOR FURTHER INSTRUCTIONS | | | AND CLARIFICATIONS. | | | | | | 2C) THE ELECTRONIC PLANS SUBMITTED 368 PAGES ARE PLANS | | | SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS | | | HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS. | | | THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO | | | BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE | | | COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS | | | SHOULD HAVE PULLED THE SHEETS THAT DID NOT PERTAIN TO | | | THAT BUILDING AND DETAIL SHEETS, DETAILS NOT PERTAINING | | | TO THAT BUILDING STRUCK THROUGH. 107.2.1.4 QUALITY OF | | | BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS | | | AND SPECIFICATIONS, IN ORDER TO PROVIDE UNIFORMITY TO | | | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE | | | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, | | | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. | | | ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE | | | REQUIREMENTS OF FLORIDA STATUTES. THIS CODE SECTION IS | | | FOR RECORD RETENTION BUT THE REALITY OF THIS IS, THE | | | WAY THESE PLANS WERE SUBMITTED, IT IS VERY DIFFICULT TO | | | FIND WHERE TO LOOK FOR CODE COMPLIANCE!!!!!!! | | | | | | 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING | | | FLORIDA S. S. 553.71(7) | | | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. | | | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 3A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO | | | E-MAIL ADDRESS: [email protected] | | | FORMS SENT AT SUN. JUNE 07/2015 08:51 AM. | | | | | | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE | | | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: | | | [email protected] | | | | | | 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | 4) THE PERMIT VALUE OF $11,712,570.25 IS LOW. THERE IS | | | A DISCREPANCY IN THE BUILDING TYPE FOR BUILDING # 1, SO | | | THE VALUATION IS FIGURED FOR BOTH BUILDING TYPES. | | | CALCULATED VALUE: | | | BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00 | | | BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00 | | | | | | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3* BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 5) SAFEGUARDS DURING CONSTRUCTION; | | | 5A) 2010 FBC-B 3306.2 WALKWAYS | | | 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES | | | 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN | | | HEIGHT. | | | 5D) 2010 FBC-B 3306.5 BARRIERS | | | 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS | | | 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY | | | 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE | | | EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR | | | OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED | | | DECKING OR FLOORING. | | | | | | 6) THE PERMIT APPLICATION CAME IN AS A TBD, TO BE | | | DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF THIS | | | PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE | | | CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 5 | | | STORY BUILDING. FLORIDA S. S. 489.113. | | | | | | 7) SHEET A-0.01: | | | 7A) THE CONSTRUCTION TYPE IS LISTED AS II-B BUILDING, | | | WHEREAS UNDER THE HEADING THE BUILDING IS LISTED AS | | | CONSTRUCTION TYPE I-B. THIS DISCREPANCY IN THE PLANS | | | WILL AFFECT THE REQUIREMENTS IN TABLE 601. 107.2.1.3, | | | ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THAT | | | FIRE RESISTANCE RATINGS AND ALLOWABLE HEIGHT AND AREA | | | ARE FOR A CONSTRUCTION BLDG. TYPE I-B. FOR THE PURPOSE | | | OF THIS REVIEW A BLDG. TYPE I-B WILL BE ASSUMED. | | | | | | 7B) UNDER THE HEADING CONSTRUCTION TYPE IS FOUND A BOX | | | CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR SINCE THERE | | | ARE BLDGS. 2 & 3 ON THE SAME LINE AS BUILDING # 1. THE | | | REAL QUESTION IS WILL THERE BE (2) TYPES OF FIRE | | | SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN COMPLIANCE | | | WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 & 3 HAVE THE | | | SAME TYPE OF FIRE SPRINKLERS OR WILL THEY HAVE A NFPA | | | 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF BOTH SYSTEMS | | | ARE GOING TO BE INSTALLED PLEASE LIST THEM IN THE | | | BUILDING MATRIX AS SUCH. | | | | | | 8) SHEET A-1.01; | | | 8A) DETAILS 3 AND 3.1 THE ACCESSIBLE & STANDARD PARKING | | | DETAILS AND PARALLEL PARKING STRIPPING DETAILS ARE | | | GOING TO NEED TO COMPLY WITH 2010 FBC-ACCESSIBILITY | | | CODE ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF | | | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY | | | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. SEE | | | WEST PALM BEACH MUNI-CODE SECTION 94-485 STALL PAINTING | | | DETAIL. | | | | | | 8B) DETAIL # 10. THE FENCE DESIGN IS INDICATED TO MEET | | | THE FBC-B 2010 ASCE 7-05. PLEASE NOTE THE ASCE -05 WAS | | | IN THE 2007 FBC-B. THE 2010 FBC-B SECTION 1609. 1.1 THE | | | DETERMINATION OF WIND USES THE ASCE 7-10. | | | | | | 9) SHEET A-8.01 IDENTIFIES TYPE OF WALLS WITH WALL TAG | | | ALPHA- NUMERICAL WALL TAGS FOR FIRE RESISTANCE RATINGS | | | HOW DOES SHEET A-11.00 SERIES OF DRAWINGS RELATE TO | | | SHEET A-8.01. SHEET A-8.01 DOES NOT HAVE BLOCK TYPE | | | INFORMATION STATING THEY ARE A T012 OR T007 TYPE BLOCK? | | | | | | 10) SHEET A-200A: | | | 10A) THIS COMMENT WILL STAND FOR ALL DOORS ON ALL | | | FLOORS. THE FRONT ENTRY DOORS DO NOT INDICATE A DOOR | | | IDENTIFICATION TAG, PLEASE PROVIDE COMPLIANCE WITH 2010 | | | FBC-B TABLE 715.4. | | | | | | 10B) BETWEEN DWELLING UNITS AND DWELLING UNITS AND | | | COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED A 6 INCH | | | CONCRETE REINFORCED WALL WITH NO INSULATION. PLEASE | | | PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 FBC-B | | | 1207.2 HAS BEEN ACHIEVED. | | | | | | | | | | | | 11) SHEET A-2.01B THE AREA ON THE 2ND FLOOR OVER THE | | | COMMON AREAS OF THE 1ST FLOOR, THERE ARE WALLS SHOWN ON | | | THIS AREA OF THE 2ND STORY BUT NO DOORWAYS TO GAIN | | | ENTRY, IS THIS AREA A CLEAR STORY TO THE 1ST FLOOR? | | | WHAT IS THE USAGE IF NOT? 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | | | | 12) PLEASE NOTE CONCERN IN STAIRWELL 2 & 3 THE 1ST, 2ND | | | & 3RD FLOORS SHOW A 6 INCH POURED CONCRETE WALL AND ON | | | THE 4TH AND 5TH FLOOR THE SAME WALL BECOMES A 8 INCH | | | BLOCK WALL WITH REINFORCING. THIS SAME WALL IN THE | | | PLUMBING SHEETS P2.04 SHOWS A 4 INCH RAIN WATER LETTER | | | AND A 4 INCH OVERFLOW RAIN WATER LETTER WITHIN THE SAME | | | WALL. THE RAIN WATER LETTERS CAN NOT BE WITHIN THE | | | STAIR WELL IN BOTH STAIRS FBC-B 1022.4 PENETRATIONS. IF | | | SHEET A-8.03 DETAIL #8 & 9 IS REFLECT A BUILD-OUT INTO | | | THE STAIRWELL, PLEASE SHOW IN THE STAIRWELL WHERE THIS | | | IS TO OCCUR, AND THE PILASTER WILL NEED TO BE A 2 HR. | | | RATED SHAFT. | | | | | | FOR THE POURED CONCRETE SECTION OF WALL FBC-B 1906.3 | | | PIPES AND SLEEVES CAN NOT BE EMBEDDED IN CONCRETE | | | UNLESS WITH THE APPROVAL OF THE DESIGN PROFESSIONAL. | | | PLEASE SHOW WITH THE 2 HOUR FIRE RATING OF THE | | | STAIRWELL ENCLOSURE WILL BE MAINTAINED WHEN OVER 4 ? | | | INCHES OF PIPE WILL BE IN A 6 INCH WALL PLUS THE REBAR. | | | | | | FOR THE MASONRY BLOCK WALL AND TIE BEAMS , THE OUTSIDE | | | DIAMETER OF A 4 INCH PIPE BEING 4 ? INCHES THIS TAKES | | | OVER 60 PERCENT OF THE VOLUME AWAY IN A 7 ? INCH WALL | | | AND BEAM THERE WOULD BE ONLY A 1 ? INCHES LEFT ON BOTH | | | SIDES OF THE PIPE. FBC-B 2108 .2 ACI 530. CHAPTER 4 | | | EMBEDDED ITEMS 4.1.1.2 DESIGN SHALL CONSIDER THE | | | STRUCTURAL EFFECTS RESULTING FROM THE REMOVAL OF | | | MASONRY TO ALLOW FOR THE PLACEMENT OF PIPES OR | | | CONDUITS. | | | | | | 13) SHEET A-7-06 TRASH CHUTE; | | | 13A) DETAIL # 1 PLEASE PROVIDE DETAIL OF THE 2ND FLOOR | | | BOTTOM OF SHAFT ENCLOSURE FIRE PROOFING OF HORIZONTAL | | | ASSEMBLY. FBC-B 713.4.1.1 THROUGH PENETRATIONS. | | | | | | 13 B) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS ON | | | THE HORIZONTAL DAMPER THAT CLOSES OFF THE TRASH CHUTE | | | FROM THE REMAINDER OF THE TERMINATION ROOM. FBC-B | | | 708.13.1. THIS MAY BE A HEAT ACTIVATED CLOSING DEVICE | | | SHALL BE PERMITTED BETWEEN THE SHAFT AND THE | | | TERMINATION ROOM. | | | | | | 13C) DETAIL C DOES INDICATE A FIRE SPRINKLER RISER | | | WITHIN THE SHAFT BUT NO COMPLIANCE WITH FBC-B | | | 903.2.11.2. CHUTES EXTENDING 3 OR MORE FLOORS SHALL | | | HAVE ADDITIONAL SPRINKLER HEADS AT ALTERNATING FLOORS | | | AND AT THE TOP OF THE SHAFT. | | | | | | 14) SHEET A-7.00 DETAIL # 1 STAIRWELL 1 & 4, THE 1ST | | | FLOOR INDICATES A VOID SPACE UNDER THE STAIRS, PLEASE | | | SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE | | | VERTICAL CLEARANCE 307.4 AND FIGURE 307.4. | | | | | | 15) SHEET A-7.01 DETAIL # 1 STAIRWELL 2 & 3, THE 1ST | | | FLOOR INDICATES A VOID SPACE UNDER THE STAIRS, PLEASE | | | SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE | | | VERTICAL CLEARANCE 307.4 AND FIGURE 307.4. | | | | | | 16) SHEET A-2.05; | | | 16A) THE HIPPED ROOFS SHOW SOFFIT VENTS BUT THERE IS NO | | | NOTATION OF CODE COMPLIANCE FOR 2010 FBC-B 1203.2 WITH | | | 50% OF THE REQUIRED VENTILATING AREA PROVIDED BY | | | VENTILATORS LOCATED IN THE UPPER PORTION OF THE SPACE | | | TO BE VENTILATED AT LEAST 3 FEET ABOVE THE EAVE OR | | | CORNICE VENTS, WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY THE EAVE VENTS. | | | | | | 16B) PLEASE SHOW HOW COMPLIANCE WITH 1209.2 WILL BE | | | ACHIEVED 20 INCH X 30 INCH ATTIC ACCESS. | | | | | | 16C) PLEASE SEE HIPPED ROOF SECTION A, ON BOTH SIDES OF | | | THIS ROOF THERE ARE FLAT ROOFS THAT DO NOT SHOW HOW THE | | | WATER IS GOING TO BE REMOVED FROM THESE ROOF TOPS? | | | FBC-B 1503.4. | | | | | | 17) SHEET A-6.04 AT THE BOTTOM OF THE SHEET THE PLANS | | | INDICATE BACKING REQUIREMENTS FOR TUB AND SHOWERS. THE | | | HEIGHT DIMENSION IS PROVIDED TO THE TOP OF THE BACKING | | | OF 38 INCHES AND THE VERTICAL DIMENSION OF THE BACKING | | | FOR THE BACK WALL OF THE TUB. WHAT IS MISSING IS THE | | | END WALL OF THE TUB AND SHOWER, WHAT IS THE MINIMUM | | | VERTICAL DISTANCE FOR THE BACKING. THE OTHER ISSUE IT | | | APPEARS FOR THE BACKING THE SHOWER BACK WALL WAS | | | MISLABELED TUB. 2010 FBC- ACCESSIBILITY/ FAIR HOUSING | | | SEE FIGURE # 5. | | | | | | 18) SHEET A-9.00 DETAILS 1 & 3 BOTH SHOW THE USE OF | | | ROOF SHEATHING, THICKNESS NOR SPAN OF PLYWOOD NOT | | | PROVIDED. FBC-B TABLE 2304.7(5). | | | | | | 19) SHEET A-9.00 DETAILS 1 & 3 BOTH SHOW THE USE OF | | | PLYWOOD ROOF SHEATHING AND WOOD TRUSSES. PLEASE SEE | | | FBC-B 603.1.1.3. | | | | | | 20) SHEET A-9.04 INDICATES THE USE OF (2) FLOOR | | | INSULATION PRODUCTS, EASY MAT AND KNAUF INSULATION, | | | PLEASE SUBMIT THE REPORTS FOR COMPLIANCE WITH: | | | | | | 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 21) SHEET S-3.02 UNDER THE HEADING WINDLOAD PRESSURES | | | FOR WINDOWS AND DOORS, THE PLANS DO NOT INDICATE THE | | | MEAN ROOF HEIGHT THESE PRESSURE WERE TAKEN FOR, | | | BUILDING 1 IS A (5) STORY WHEREAS BUILDINGS 2 & 3 ARE | | | BOTH 4 STORY BUILDINGS. DEFINITIONS, CHAPTER 2. MEAN | | | ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT AND | | | THE HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE, | | | EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF ANGLE OF | | | LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD). | | | | | | 22) SHEET S-3.02 COMPONENTS AND CLADDING THE ROOF | | | PRESSURES FOR ROOF ZONES 1,2 & 3 WERE NOT PROVIDED FOR | | | 10 SQ. FT. PLEASE ALSO NOTE THERE ARE 2 MEAN ROOF | | | HEIGHTS TO CONSIDER, THE 5 STORY AND 4 STORY. THE OTHER | | | ISSUE IS THE PRESSURES FOR THE FLAT ROOFS AS WELL AS | | | FOR THE SLOPED ROOF. FBC-B 1609.1.5 & 1609.1.2.3.1. | | | | | | 23) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 23A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF | | | GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS | | | ARE USED, CIRCLE THE MULLION TO BE INSTALLED, | | | PRESSURES, AND FASTENERS. | | | | | | 23B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE | | | SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY | | | REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND | | | SIGNED & SEALED CALCULATIONS. | | | | | | 23C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO | | | BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED, | | | IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES. | | | | | | 23D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR | | | CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT | | | APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR | | | THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING | | | FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | | APPROVED BY THE BUILDING OFFICIAL. | | | | | | 24) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-06 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-06 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2015-10-06 19:47:27 | ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN | | | SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-09-04 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-04 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-02 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2015-09-04 11:42:55 | MOST OF THE PREVIOUSLY MENTIONED ITEMS HAVE BEEN | | | ADDRESSED. I CONTACTED SERGIO MARTINEZ OF JMM | | | CONSULTING WITH THE LIST OF THE REMAINING ITEMS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-06-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-09 |
Time |
20:01 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-03 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2015-06-09 17:18:48 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE | | | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH | | | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN | | | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE | | | DIGITAL PLANS. | | | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR A SECOND REVIEW: | | | | | | PG. E-1.00 ELECTRICAL SITE PLAN | | | 1. BEING THAT THE PROPOSED POOL WILL BE UNDER A | | | SEPARATE PERMIT. A NOTE AS TO THE NEC 680.10 | | | REQUIREMENT FOR NO UNDERGROUND RACEWAYS WITHIN 5? OF | | | THE WATER?S EDGE SHOULD BE MADE TO KEEP THE AREA CLEAR | | | OF NON-POOL RELATED CONDUIT. | | | | | | PG. E1.10 PHOTOMETRIC PLAN | | | 1. AN AMENDMENT TO NOTE 4 IN IRRIGATION PUMP SYSTEMS TO | | | INCLUDE THE CODE REQUIREMENT THAT THE DEVICES ALSO BE | | | RATED ?WR? WEATHER RESISTANT. | | | | | | PG. E2.02A, E2.02B, E2.03A, E2.03B, E2.04A, E2.04B, | | | E2.08, E2.09, E.2.13 & E2.14 | | | 1. THE ABOVE PAGES ARE MISSING AN EXIT LIGHT IN THE | | | CORNER WHERE THE TWO CORRIDORS INTERSECT. THIS/THESE | | | LIGHTS SHALL BE VISIBLE FROM BOTH SIDES. | | | 2. IN ADDITION TO THE ABOVE, PGS. E2.04A, E2.09 & E2.14 | | | HAVE ACCESS TO THE ROOF. THERE SHALL BE AN EXIT LIGHT | | | ON THE ROOF SIDE OF EACH OF THESE DOORS. | | | 3. THE SAME APPLIES TO PG. E2.04B. THE DOOR ON THE | | | MATCH LINE HAS BEEN CLOUDED ON BOTH A & B. | | | | | | PG. E2.07A, E2.08A, E2.09A, E2.12A, E2.13A & E2.14A | | | 1. ON THESE PAGES YOU SHOW THE EMERGENCY EGRESS | | | LIGHTING, AND THOUGH THE STAIRS ARE SHOWN ON THE | | | INDIVIDUAL FLOOR PLANS, THEY ARE A PART OF THE | | | EMERGENCY EGRESS AND THEREFORE REFLECTED AS SUCH. | | | | | | | | | | | | PG. E3.00, UNITS NOTES & LEGEND | | | THIS IS PRIMARILY A NOTES PAGE AND HAS TWO ITEMS | | | NEEDING CORRECTION. THESE SAME NOTES ARE TYPICAL | | | THROUGHOUT THE DRAWINGS. | | | 1. NOTE 17 OF THE APARTMENT UNIT NOTES SHOULD BE | | | AMENDED TO INCLUDE THE NEC 314.27 REQUIREMENT THAT THE | | | CEILING BOXES BE RATED TO SUPPORT 50#. THIS NOTE HAS | | | BEEN NOTED ELSEWHERE ON THE PLANS. | | | 2. I NOTICED THAT YOUR DESIGN INCLUDES CEILING FANS AND | | | THEREFORE, APARTMENT SINGLE STATION SMOKE DETECTORS, | | | NOTE 4 SHALL BE AMENDED TO INCLUDE 36? FROM THE TIP OF | | | A CEILING FAN BLADE. | | | | | | PGS. E3.01, E3.02 & E3.03 | | | THE NOTES ON ALL OF THE SHEETS ARE THE SAME; THEREFORE | | | THE FIRST THREE COMMENTS APPLY TO ALL. | | | 1. UNIT CODED NOTES, #4 SHALL INCLUDE THE TIP OF A | | | CEILING FAN. (THE REGULATION INVOLVING THE KITCHEN IS | | | ONLY THAT IF THE UNIT IS WITHIN 10? OF THE RANGE IT HAS | | | TO BE SILENCEABLE). | | | 2. ADDITIONAL NOTES, #7 IS A REPEAT OF #4 ABOVE, & #2 | | | SHOULD BE AMENDED TO READ?AND BE RATED WEATHER | | | RESISTANT ?WR? AS PER NEC 406.8. | | | THE FOLLOWING ITEMS ARE ISSUES THAT WERE CLOUDED | | | THROUGHOUT ALL THREE MODEL UNITS. THESE CLOUDS CAN BE | | | SEEN BY VIEWING THE CHANGE MARK LAYERS. | | | 3. NEC 210.52 (A)(1) RECEPTACLES SHALL BE INSTALLED | | | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE | | | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A | | | RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE | | | EDGE OF THE WALL. | | | 4. NEC 210.52 (A)(2) ANY WALL SPACE 2 FT. OR MORE IN | | | WIDTH SHALL HAVE AN OUTLET | | | 5. NEC 210.52(C)(1) A RECEPTACLE OUTLET SHALL BE | | | INSTALLED AT EACH WALL COUNTERTOP SPACE THAT IS 12 IN. | | | OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT | | | NO POINT ALONG THE WALL LINE IS MORE THAN 24 IN. | | | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT | | | SPACE. | | | 6. NEC 210.52(C)(3) AT LEAST ONE RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT EACH PENINSULAR COUNTERTOP. | | | 7. NEC 210.520(D) IN DWELLING UNITS, AT LEAST ONE | | | RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS | | | WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. | | | 8. NEC 210.70(A)(3) AT LEAST ONE LIGHTING OUTLET | | | CONTAINING A SWITCH OR CONTROLLED BY A WALL SWITCH | | | SHALL BE INSTALLED WHERE THESE SPACES ARE USED FOR | | | STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE | | | LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE | | | EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH SMC | | | BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING. | | | | | | PG. E4.00A | | | 1. SOUND SYSTEM NOTES BOX SHALL HAVE AN ADDITIONAL LINE | | | ITEM STATING THAT THE AUDIO SYSTEM SHALL BE MUTED VIA | | | THE FACP IN THE EVENT OF AN ALARM CONDITION. | | | | | | PG. E4.00B | | | 1. ILLUMINATION ELECTRICAL NOTES #3, SEE CORRECTION TO | | | NEC 700.12(F) | | | | | | PG. E4.01, E4.03, E4.05, E4.06, MAIN ELECTRICAL ROOM | | | ?A?, ?B? & ?C? | | | 1. SEE CLOUDED AREA IN ELECTRICAL ROOM NOTES WHICH HAS | | | TO BE CLARIFIED. | | | | | | PG. E4.02 & E4.09 MACHINE ROOMS | | | 1. ELEVATOR ELECTRICAL NOTES BOX, NOTRE #1 SHALL BE | | | CORRECTED TO READ AS FOLLOWS: NEC 620.51. | | | | | | PG. E4.07, E4.08 ENLARGED TRASH ROOMS | | | 1. BOTH, TRASH ROOM A, B, C & D, HAVE THE SAME COMMENT | | | AS FOLLOWS: CHECK FOR PROPER WORKING CLEARANCE AS PER | | | NEC 110.26. THERE DOES NOT APPEAR TO BE SUFFICIENT | | | CLEARANCE BETWEEN THE ELECTRICAL OUTLETS AND WHATEVER | | | IS IN FRONT OF THEM. | | | | | | PG. E5.06 | | | 1. CORRECT INCORRECTLY QUOTED NEC SECTION TO READ | | | (410.130(G)) | | | 2. CLARIFY YOUR INTENT AT THE OUTLET STUB UP DETAIL | | | | | | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 | | | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE | | | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA | | | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND | | | FLORIDA BUILDING CODE ENERGY CONSERVATION. | | | | | 2015-06-09 15:45:43 | SEE ATTACHMENTS FOR DERTAILS OF ELECTRICAL PLAN REVIEW | | | RESULTS. | | | FIRE ALARM REVIEW TO FOLLOW |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2015-08-25 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2015-08-25 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2015-08-25 |
Time |
|
Sent To |
ENG |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2015-05-21 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-05-21 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-05-21 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2015-05-21 10:10:47 | ON SHEET LP-1, SHOW THE VISIBILITY TRIANGLE AT THE | | | INTERSECTION OF ADAMS AND DIVISION. | | | | | | KELLY CRANFORD, PE | | | LAND DEVELOPMENT ENGINEERING | | | (561)494-1098 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-10-07 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-10-07 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-10-07 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-08-13 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-08-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2015-08-13 08:41:41 | PERMIT #15050261 - 838 ADAMS STREET (66 UNITS) | | | PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS) | | | PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS) | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER | | | HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS | | | LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR | | | THE 2ND REVIEW. | | | ORIGINAL COMMENT - THE FIRE DEPARTMENT REQUIRES PLANS | | | AND PERMITS FOR ALL CONSTRUCTION RELATED TRAILERS AND | | | MODULAR BUILDINGS. ADDITIONALLY PER NFPA 241- STANDARD | | | FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND | | | DEMOLITION OPERATIONS, SECTION 4.2: TEMPORARY OFFICES, | | | TRAILERS, AND OTHER FACILITIES OF COMBUSTIBLE | | | CONSTRUCTION OR HOUSING COMBUSTIBLE CONTENTS SHALL BE | | | SEPARATED FROM ADJACENT BUILDINGS, TRAILERS OR | | | STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. PER TABLE | | | 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER | | | HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS | | | LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR | | | THE 2ND REVIEW. | | | ORIGINAL COMMENT - PER NFPA 241 SECTION 4.2.2: | | | DETACHMENT BETWEEN TEMPORARY STRUCTURES, ADEQUATE | | | TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND PORTABLE | | | EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | | | | RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED; | | | REVISED PLANS NOT SUBMITTED. | | | ORIGINAL COMMENT - SHEET PM-1: PER SECTION 18.2.3.5.3 | | | (NFPA 1), FIRE LANES SHALL BE MARKED WITH FREESTANDING | | | SIGNS READING, "FIRE LANE - NO PARKING BY ORDER OF THE | | | FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE | | | BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF | | | SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS | | | SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED | | | A MAXIMUM OF 60 FEET APART. FIRE DEPARTMENT ACCESS | | | ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE | | | APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL | | | HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND | | | AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 | | | FEET 6 INCHES. | | | | | | RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED; | | | REVISED PLANS NOT SUBMITTED. | | | ORIGINAL COMMENT - SHEET WS-1: FIRE MAINS SUPPLYING TWO | | | OR MORE FIRE HYDRANTS WILL NEED TO BE LOOPED AND WILL | | | NOT BE PERMITTED TO TERMINATE AT A DEAD END BLOWOFF | | | CAP. | | | | | | RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED; | | | REVISED PLANS NOT SUBMITTED. | | | ORIGINAL COMMENT - SHEET WS-1: THE FIRELINE BACKFLOW | | | PREVENTERS SHALL COMPLY WITH NFPA 24 SECTION 6.2.1, ALL | | | CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE | | | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH | | | ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: | | | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 | | | FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST | | | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED | | | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE | | | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST | | | INDICATOR VALVE. | | | (2) A WALL POST INDICATOR VALVE | | | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN | | | ACCORDANCE WITH SECTION 6.4 | | | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A | | | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE | | | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET | | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | | THE WALL FACING THE BACKFLOW PREVENTER. | | | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM | | | ACCESSIBLE FROM THE EXTERIOR | | | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE | | | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE | | | AUTHORITY HAVING JURISDICTION | | | | | | RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL | | | SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO | | | TWO SEPARATE EXITS. | | | ORIGINAL COMMENT - SHEET E2.01A & SHEET E2.01B: PROVIDE | | | TWO ADDITIONAL EXIT SIGNS IN THE EXIT ACCESS CORRIDOR | | | NEAR COLUMN INTERSECTION B.1/1.2. TYPICAL ALL LEVELS. | | | | | | RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL | | | SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO | | | TWO SEPARATE EXITS. | | | ORIGINAL COMMENT - SHEET E2.07: PROVIDE TWO ADDITIONAL | | | EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN | | | INTERSECTION A.4/8.1. TYPICAL ALL LEVELS. | | | | | | RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED; | | | REVISED PLANS NOT SUBMITTED. | | | ORIGINAL COMMENT - SHEET E2.12: PROVIDE TWO ADDITIONAL | | | EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN | | | INTERSECTION A.4/8.1. TYPICAL ALL LEVELS. | | | | | | RESPONSE COMMENT: SHEET FP2.04 NOW INCLUDES A STATEMENT | | | THAT SPRINKLERS ARE BEING REQUIRED BY THE LOCAL | | | JURISDICTION. THIS IS AN INCORRECT STATEMENT; | | | COMBUSTIBLE CONCEALED ROOF SPRINKLER PROTECTION IS | | | REQUIRED BY NFPA 13 SECTION 8.15. SHEET FP2.05 HAS NOT | | | BEEN CORRECTED AT ALL. | | | ORIGINAL COMMENT - SHEET FP2.04 & FP2.05: PLAN | | | INDICATES NO SPRINKLER PROTECTION FOR THE | | | NON-ACCESSIBLE TRUSS SPACE; CONTRARY TO NFPA 13 SECTION | | | 8.15. INDICATE A CODE REFERENCE PERMITTING THIS | | | COMBUSTIBLE CONCEALED SPACE FROM BEING PROTECTED BY | | | FIRE SPRINKLERS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-05-22 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-05-22 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-05-15 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2015-05-15 14:20:00 | PERMIT #15050261 - 838 ADAMS STREET (66 UNITS) | | | PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS) | | | PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS) | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE FIRE DEPARTMENT REQUIRES PLANS AND PERMITS FOR ALL | | | CONSTRUCTION RELATED TRAILERS AND MODULAR BUILDINGS. | | | ADDITIONALLY PER NFPA 241- STANDARD FOR SAFEGUARDING | | | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, | | | SECTION 4.2: TEMPORARY OFFICES, TRAILERS, AND OTHER | | | FACILITIES OF COMBUSTIBLE CONSTRUCTION OR HOUSING | | | COMBUSTIBLE CONTENTS SHALL BE SEPARATED FROM ADJACENT | | | BUILDINGS, TRAILERS OR STRUCTURES IN ACCORDANCE WITH | | | TABLE 4.2.1. PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN | | | TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE | | | PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE | | | PROVIDED AS REQUIRED BY THE AUTHORITY HAVING | | | JURISDICTION. | | | | | | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | | | | PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER | | | MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE | | | INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL | | | CONSTRUCTION WORK. | | | | | | SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE | | | UNDERGROUND FIRE LINE AND FIRE HYDRANTS. | | | | | | SHEET PM-1: PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES | | | SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE | | | LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT." | | | SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND | | | RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN | | | HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN | | | SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 | | | FEET APART. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A | | | SURFACE DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING | | | AT LEAST 36 TONS. ACCESS ROADS SHALL HAVE AN | | | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN | | | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 | | | FEET 6 INCHES. | | | | | | SHEET WS-1: FIRE MAINS SUPPLYING TWO OR MORE FIRE | | | HYDRANTS WILL NEED TO BE LOOPED AND WILL NOT BE | | | PERMITTED TO TERMINATE AT A DEAD END BLOWOFF CAP. | | | | | | SHEET WS-1: THE FIRELINE BACKFLOW PREVENTERS SHALL | | | COMPLY WITH NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO | | | PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS | | | SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE | | | FOLLOWING SO THAT THEY CAN BE ISOLATED: | | | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 | | | FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST | | | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED | | | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE | | | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST | | | INDICATOR VALVE. | | | (2) A WALL POST INDICATOR VALVE | | | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN | | | ACCORDANCE WITH SECTION 6.4 | | | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. | | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A | | | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE | | | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET | | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | | THE WALL FACING THE BACKFLOW PREVENTER. | | | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM | | | ACCESSIBLE FROM THE EXTERIOR | | | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE | | | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE | | | AUTHORITY HAVING JURISDICTION | | | | | | COULD NOT LOCATE A DRAWING INDEX. | | | | | | COULD NOT LOCATE ANY LIFE SAFETY PLANS FOR THE PROPOSED | | | POOL AREA AND CHILDRENS' PLAYGROUND AREA. | | | | | | SHEET A7.00: STAIRWAY IDENTIFICATION: 7.2.2.5.4.1 NEW | | | ENCLOSED STAIRS SERVING THREE OR MORE STORIES SHALL | | | COMPLY WITH 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(L). | | | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE | | | WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. | | | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. | | | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP | | | AND BOTTOM OF THE STAIR ENCLOSURE. | | | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF | | | THE STAIR ENCLOSURE. | | | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND | | | THE DIRECTION TO, EXIT DISCHARGE. | | | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE | | | APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A | | | POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN | | | OR CLOSED POSITION. | | | (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. | | | (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE | | | WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE | | | WALL. | | | (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED | | | AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH | | | LETTERING. | | | (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED | | | UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL | | | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. | | | LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. | | | (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE | | | MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. | | | MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER | | | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR | | | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B" | | | OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING | | | THE FLOOR LEVEL NUMBER. | | | (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF | | | THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN | | | IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. | | | | | | SHEET E2.01A & SHEET E2.01B: PROVIDE TWO ADDITIONAL | | | EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN | | | INTERSECTION B.1/1.2. TYPICAL ALL LEVELS. | | | | | | SHEET E2.07: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE | | | EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1. | | | TYPICAL ALL LEVELS. | | | | | | SHEET E2.12: PROVIDE TWO ADDITIONAL EXIT SIGNS IN THE | | | EXIT ACCESS CORRIDOR NEAR COLUMN INTERSECTION A.4/8/1. | | | TYPICAL ALL LEVELS. | | | | | | SHEET FA1.00: COULD NOT LOCATE REMOTE ANNUNCIATOR | | | PANEL. TYPICAL ALL 3 BUILDINGS. | | | | | | SHEET FA2.00: FIRE ALARM SYSTEM SHALL BE FULLY | | | ADDRESSABLE. | | | | | | SHEET FP1.00: SEVERAL NOTES INDICATE THE 2007 EDITION | | | OF NFPA 13. THE STATE OF FLORIDA HAS ADOPTED AND | | | ENFORCES THE 2010 EDITION. | | | | | | SHEET FP2.00: THE NON-RESIDENTIAL PUBLIC SPACES ARE | | | INDICATE THE SPRINKLERS ARE BEING FED FROM THE SECOND | | | FLOOR SPRINKLER SYSTEM. PROVIDE A DEDICATED FLOW SWITCH | | | FOR THIS AREA OR SUPPLY THIS AREA FROM THE FIRST FLOOR | | | SPRINKLER SYSTEM TO ELIMINATE CONFUSION THAT THE FIRE | | | EVENT IS LOCATED ON THE SECOND FLOOR. | | | | | | SHEET FP2.04 & FP2.05: PLAN INDICATES NO SPRINKLER | | | PROTECTION FOR THE NON-ACCESSIBLE TRUSS SPACE; CONTRARY | | | TO NFPA 13 SECTION 8.15. INDICATE A CODE REFERENCE | | | PERMITTING THIS COMBUSTIBLE CONCEALED SPACE FROM BEING | | | PROTECTED BY FIRE SPRINKLERS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-03 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-03 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-10-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-10-09 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-09-30 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-09-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-09-09 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-07-23 |
Time |
18:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-06-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-28 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-05-13 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2015-12-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2015-12-01 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2015-12-01 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-06 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-06 |
Time |
05:36 |
Sent To |
|
|
| Notes |
| 2015-10-06 07:17:31 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2015-08-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-18 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-17 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2015-08-18 16:51:51 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-08 |
Time |
06:21 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-06-07 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2015-06-08 06:21:26 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: TBD/ TO BE DETERMINED | | | CONTACT: ALBERT OVIEDO | | | TEL: (??????? | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SUN. JUNE 07/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 4 STORY/ R2 | | | | | | ACTION: DENIED | | | | | | 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2015-10-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-05 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-05 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-09-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-08-06 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-08-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2015-08-06 14:20:59 | 2ND REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15050261 | | | 8/6/15 | | | . | | | 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR | | | THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR | | | THE ACCA/ASHRAE STANDARD 183- SECTION 503.2.1 FBC-10 | | | ENERGY CONSERVATION. | | | 2) SHEET M2.02: CLARIFY HOW THE DUCT SMOKE DETECTOR IN | | | AHU-10 WILL BE SUPERVISED: PROVIDE A SEQUENCE OF | | | OPERATION FOR FAN SHUT DOWN. | | | 3) SHEET M3.0: REVISE THE HVAC DESIGN TABLE TO INCLUDE | | | THE FIRE DAMPERS IN THE "YES" COLUMN. | | | 4) PROVIDE INSTALLATION DETAILS FOR THE FIRE DAMPERS | | | AND DUCT SMOKE DETECTORS. | | | 5) M3.0: THE 80 CFM TOILET EXHAUST FANS ARE UNDERSIZED | | | PER TABLE 403.3 FBC-10 MECHANICAL- MINIMUM 100 CFM | | | REQUIRED IN THE TOILET AREAS OF THE BATHROOMS. | | | 6) SHEET M3.01: WIND LOAD DESIGN PRESSURE CALCULATIONS | | | AND TIE-DOWN ENGINEERING ARE REQUIRED FOR ANCHORING THE | | | CONDENSER STANDS AND CONDENSER UNITS TO THE ROOF | | | STRUCTURE- SECTION 301.12 FMC-10, AND SECTION 1609 | | | FBC-10 BUILDING. PLEASE REVISE THE DETAIL ACCORDINGLY | | | AND CORRECT THE 150 MPH WIND LOAD SPECIFICATION. | | | 7) REMOVE SHEET A-10.08 SHOWING THE HILTI FIRESTOPPING | | | DETAILS, THE ENGINEER OF RECORD HAS INDICATED IN HIS | | | NARRATIVE RESPONSE TO BUILIDNGS 2 & 3 THAT HE HAS | | | APPROVED THE TREMCO SYSTEM. | | | 8) 13) PROVIDE A SUBMITTAL PACKAGE WITH ALL DOCUMENTS | | | REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF | | | RECORD. PLEASE INCLUDE NOA'S, PRODUCT APPROVALS, AND | | | MANUFACTURER'S SPECIFICATIONS FOR THE CONDENSER STANDS, | | | THE EXHAUST AND O/A INTAKE FANS, THE O/A MOTORIZED | | | DAMPERS, THE EXHAUST AND INTAKE WALL LOUVERS, THE | | | ELEVATOR SHAFT MOTORIZED DAMPER, THE AC SYSTEMS, THE | | | RINNAI GAS WATER HEATER AND VENT SYSTEM, THE FIRE | | | DAMPERS, THE DUCT SMOKE DETECTORS, AND THE REFRIGERANT | | | PIPE INSULATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-06-16 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-06-16 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2015-06-16 14:15:51 | PLAN DENIED | | | | | | 1) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST OUTLETS | | | # 2 AND 501.2.1.1 EXHAUST DISCHARGE 2010 FBC (M) | | | 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | | INCLUDING A/C CLOSET DOORS 2010 FBC (M) | | | 3) CITY OF WEST PALM BEACH FIRE RESCUE WILL NOT PERMIT | | | DRYER BOOSTER FANS IN DRYER DUCT . | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-10-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-03 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-03 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-08-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-08-06 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-08-06 |
Time |
04:33 |
Sent To |
|
|
| Notes |
| 2015-08-05 08:23:15 | 1)THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR | | | BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE | | | DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE | | | PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. 2ND | | | REQUEST. | | | 2) THE OVERFLOW RAINWATER DOWNSPOUTS SHALL DISCHARGE A | | | MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL | | | PER 2010 FBC 1503.7. PLACE A NOTE ON THE PLANS.THIS | | | COMMENTS REFERS TO THE DOWNSPOUTS FROM THE GUTTERS. | | | THEY ARE NOT UNDERGROUND. | | | 3) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ. | | | FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND | | | ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL | | | PROJECTED ROOF AREA" -1008 SQ. FT.- THIS DOES NOT ADD | | | UP.PLEASE CLARIFY. IS THIS A TYPO ERROR? | | | 4) SHT. A2.05 - THIS BUILDING HAS TWO FLAT ROOFS | | | IDENTIFY RWL-1 & RWL-2 ON THE PLANS. WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1.2ND REQUEST. | | | 5) THE STORM DRAINAGE RISER SHOWS OVERFLOW DRAINS, NOT | | | SCUPPERS, YET THERE ARE TABLES FOR SCUPPER SIZING. ARE | | | THERE OR ARE THERE NOT ROOF SCUPPERS ON THIS BUILDING? | | | IF SO, SHOW THE LOCATION OF ALL SCUPPERS AND SHOW THE | | | LENGTH AND HEIGHT DIMENSIONS OF THE SCUPPERS AND THE | | | DESIGN HEAD ( IN INCHES). SCUPPERS SHALL BE SIZED PER | | | THE 2010 FBC-PLUMBING TABLE 1106.7. IF NOT, DELETE ANY | | | REFERENCE/TABLE TO ROOF SCUPPERS. | | | 6) SUBMIT GUTTER CALCULATIONS FOR THE ROOF GUTTERS AND | | | DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & 1106.7. | | | 2ND REQUEST. | | | 7) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT | | | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. | | | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER | | | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS ( IF | | | APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 8) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT | | | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. | | | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER | | | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS (IF | | | APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS. COMPLY | | | WITH 2010 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) | | | THROUGH 1106.2 (2), 1106.3,1106.7. | | | 9) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF DRAIN | | | CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. SUBMIT | | | ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND SHOW | | | THE LOCATION OF THE SCUPPERS ( IF APPLICABLE ) AND | | | PROVIDE SCUPPER CALCULATIONS.COMPLY WITH 2010 | | | FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) THROUGH | | | 1106.2 (2), 1106.3,1106.7. | | | 10) SHT. P1.00 - SHOWS A 2 INCH WATER SERVICE TO | | | BUILDING #2 AND SHT. WS-1 SHOWS A 4 INCH WATER SERVICE. | | | CLARIFY. 2ND REQUEST. THE CIVIL PLANS STILL SHOW A 4 | | | INCH WATER LINE. WHICH IS IT? THE PLANS SHALL | | | CORRELATE. | | | 11) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL | | | SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2ND REQUEST. THE RESPONSE STATED THEY WILL BE PROVIDED. | | | WHEN? | | | 12) SHT. P4.00 - SHOW THE TONNAGE OF THE AIR | | | CONDITIONING EQUIPMENT ON THE CONDENSATE RISER. COMPLY | | | W/ TABLE 314.2.2. OF 2010 FPC. THE PLAN WAS ONLY | | | CORRECTED FOR BUILDING #1. CORRECT THE PLAN FOR THE | | | OTHER BUILDINGS. 2ND REQUEST. | | | 13) SUBMIT THE MANUFACTURER SPECIFICATIONS & | | | INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. I CANNOT DETERMINE IF | | | THE VENT LOCATIONS ARE APPROVED AND TO CODE WITHOUT THE | | | INSTALLATION MANUAL THAT SHOWS THE REQUIREMENTS. MY | | | CONCERNS ARE THAT THIS IS A DIRECT VENT APPLIANCE AND | | | THE CLOSE PROXIMITY TO AN EXHAUST DUCT MAY CREATE A | | | CODE ISSUE.2010 FBC-FUEL GAS CODE SEC.503.2.3. | | | 14) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE. | | | SUBMIT A DETAIL THAT SHOWS ALL THE PIPING. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. 2ND REQUEST. | | | 15) IDENTIFY THE OVERFLOW DRAINS ON ALL THE ROOF PLANS. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 16) SHT. P1.00 - CLEARLY SHOW WHERE THE WATER SERVICE | | | ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 17) THE AREA OF THE SLOPED ROOFS THAT ARE DRAINING ONTO | | | THE LOWER ROOFS SHALL BE INCLUDED IN THE ROOF DRAINAGE | | | CALCULATIONS. THIS WAS OVERLOOKED IN FIRST REVIEW.2010 | | | FBC -PLUMBING SECS.1106.2 & 1106.3. | | | 18) THE PLUMBING DRAWINGS REFER TO THE ARCHITECTURAL | | | PLANS FOR DOWNSPOUT DETAILS. I COULD NOT FIND ANY | | | DOWNSPOUT DETAILS IN THE ARCHITECTURAL PLANS. CLARIFY. | | | 19) NOTE #14 ON THE ENLARGED ARCHITECTURAL FLOOR PLANS | | | REFER TO THE ARCHITECTURAL AND PLUMBING DRAWINGS FOR | | | DETAILS FOR THE GUTTERS AND DOWNSPOUTS. I COULD NOT | | | FIND ANY DETAILS ON ANY OF THESE PLANS. CLARIFY. | | | 20) AS UPLOADED, ALL THE PLUMBING DRAWINGS ARE LABELED | | | AS "P' DRAWINGS. THERE IS NO WAY TO DISCERN WHICH | | | DRAWINGS ARE FOR BUILDING #1, #2 OR #3. PLEASE SUBMIT | | | ONLY THE DRAWINGS THAT ARE APPLICABLE TO THIS PERMIT | | | AND THIS BUILDING. THIS APPLIES TO ALL THE DRAWINGS. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 21) SEVERAL RESPONSES ON THE PLAN REVIEW COMMENT STATE | | | "REFER TO REVISED ROOF PLAN" OR "SEE ARCHITECTURAL | | | DRAWINGS." THESE RESPONSES ARE VAGUE AND INCONCLUSIVE. | | | PLEASE PROVIDE THE SPECIFIC DRAWING NUMBER WHEN | | | REFERENCING PLAN SHEETS.. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-28 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-27 |
Time |
03:03 |
Sent To |
|
|
| Notes |
| 2015-06-27 12:04:05 | 1) THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR | | | BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE | | | DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE | | | PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. | | | 2) RAINWATER DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF | | | ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL PER 2010 FBC | | | 1503.7. | | | 3) THE ROOF DRAINAGE CALCULATIONS FOR THE DESIGN OF THE | | | STORMWATER SYSTEM SHALL INCLUDE ONE-HALF OF THE AREA OF | | | ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF | | | PER THE 2010 FPC SEC.1106.4. SHOW THAT THIS HAS BEEN | | | DONE WITH THE SIZING OF THE STORM DRAINAGE SYSTEM. | | | 4) SHT. A2.05 - SCUPPER CALCULATION - SEE ROOF SQ.FT. | | | W/PARAPET.- THE SQUARE FOOTAGE CANNOT BE READ. CLARIFY. | | | 5) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ. | | | FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND | | | ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL | | | PROJECTED ROOF AREA -1008 SQ. FT." PLEASE CLARIFY. IS | | | THIS A DISCREPANCY? | | | 6) SHT. A2.05 - SHOW THE LOCATION OF THE SCUPPERS ON | | | THE PLAN AND THE LOCATION OF RWL-1 & RWL-2. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | 7) SUBMIT GUTTER CALCULATIONS FOR THE GABLE END GUTTERS | | | AND DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & | | | 1106.7. | | | 8) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT | | | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. | | | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER | | | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE | | | SCUPPER CALCULATIONS. | | | 9) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT | | | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. | | | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER | | | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE | | | SCUPPER CALCULATIONS. | | | 10) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF | | | DRAIN CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. | | | SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND | | | SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE SCUPPER | | | CALCULATIONS. | | | 11) SHT. P1.00 - SHOWS A 2" WATER SERVICE TO BUILDING | | | #2 AND SHT. WS-1 SHOWS A 4? WATER SERVICE. CLARIFY. | | | 12) SHT. P1.00 - SHOW THE TERMINATION POINTS OF THE | | | STORM AND CONDENSATE DRAINS ON THE PLANS. WPB AMEND. TO | | | 2010 FBC SEC.107.2.1. | | | 13) SHT. P2.00 - PLANS REFER TO THE CIVIL DRAWINGS FOR | | | THE CONTINUATION OF THE STORM AND CONDENSATE DRAINS. | | | THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. | | | CLARIFY. | | | 14) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL | | | SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 15) AIR CHAMBERS ARE NOT PERMITTED FOR WATER HAMMER. | | | DELETE ALL REFERENCE ON THE PLUMBING PLANS TO AIR | | | CHAMBERS. A WATER HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK - CLOSING VALVES ARE UTILIZED. FPC | | | SEC.604.9. | | | 16) SHT. P4.00 - SHOW THE TONNAGE OF THE EQUIPMENT ON | | | THE CONDENSATE RISER. COMPLY W/ TABLE 314.2.2. OF 2010 | | | FPC | | | 17) SUBMIT THE MANUFACTURER SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 18) SHOW THE LOCATION OF ALL THE GAS VENTS FROM THE | | | TANKLESS WATER HEATERS. | | | 19) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-06 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-06 |
Time |
05:34 |
Sent To |
|
|
| Notes |
| 2015-10-06 07:35:00 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: LANDMARK | | | CONTACT: JORGE COSTAS | | | TEL: (305)665-1146 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS | | | ADOPTED APRIL 25/2013. | | | | | | 3RD REVIEW | | | DATE: TUES. OCT.06/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 5 STORY/BLDG TYPE: I-B/ R2 | | | | | | ACTION: PROVISO | | | | | | | | | 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS. | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF. | | | HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE | | | PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117 | | | CALCULATIONS, AND SIGNED & SEALED CALCULATIONS. | | | | | | 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF | | | TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF | | | FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED | | | PRESSURES. | | | | | | 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE | | | CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE | | | PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE | | | PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN | | | DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE | | | DEFERRED SUBMITTALS. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | | APPROVED BY THE BUILDING OFFICIAL. | | | | | | 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. | | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-08-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-18 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-17 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2015-08-18 16:53:02 | ROOFING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: TBD/ TO BE DETERMINED | | | CONTACT: ALBERT OVIEDO | | | TEL: (??????? | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: TUES. AUG. 18/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 4 STORY/ R2 | | | | | | ACTION: DENIED | | | | | | 1A) NO PRODUCT APPROVALS FOR ROOFING, NOR | | | PRE-ENGINEERED A/C STANDS, OR ROOF CURBS WERE SUBMITTED | | | UNDER THE 1ST REVIEW. | | | COMPONENTS & CLADDING | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 1B) ROOFING PRODUCT APPROVALS, IDENTIFY (CIRCLE) THE | | | SUB-SYSTEM THAT WILL BE INSTALLED, IDENTIFY THE PSI AND | | | LIMITATIONS SET FOR THE SUB-SYSTEM. IF THE LIMITATIONS | | | ALLOWS FOR ENHANCED FASTENING BY A DESIGN PROFESSIONAL, | | | USE RAS 117 CALCULATIONS, SIGNED AND SEALED | | | CALCULATIONS. | | | | | | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER CBO |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-08 |
Time |
06:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-07 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2015-06-08 06:20:36 | ROOFING PLAN REVIEW | | | W. P. B. PERMIT: 15050261 | | | ADD: 838 ADAMS ST. | | | CONT: TBD/ TO BE DETERMINED | | | CONTACT: ALBERT OVIEDO | | | TEL: (??????? | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SUN. JUNE 07/2015 | | | SILVER PALM PLACE | | | BLDG # 1/ 66 UNITS/ 4 STORY/ R2 | | | | | | ACTION: DENIED | | | | | | 1A) NO PRODUCT APPROVALS FOR ROOFING, NOR | | | PRE-ENGINEERED A/C STANDS, OR ROOF CURBS WERE SUBMITTED | | | UNDER THE 1ST REVIEW. | | | COMPONENTS & CLADDING | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 1B) ROOFING PRODUCT APPROVALS, IDENTIFY (CIRCLE) THE | | | SUB-SYSTEM THAT WILL BE INSTALLED, IDENTIFY THE PSI AND | | | LIMITATIONS SET FOR THE SUB-SYSTEM. IF THE LIMITATIONS | | | ALLOWS FOR ENHANCED FASTENING BY A DESIGN PROFESSIONAL, | | | USE RAS 117 CALCULATIONS, SIGNED AND SEALED | | | CALCULATIONS. | | | | | | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-10-27 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-10-27 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2015-10-27 11:16:42 | OK PER SKENNEDY | | 2015-05-13 16:33:01 | RECEIVED HARDCOPY SIGNED & SEALED ARDAMAN & ASSOCIATES | | | SOILS REPORTS (WITH APPLICATION). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2015-10-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-10-09 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-10-09 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2015-10-09 09:36:55 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.09.2015 | | | PERMIT NO.: 15050261 | | | ADDRESS: 838 ADAMS STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY DEVELOPMENT. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE | | | SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT - | | | PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT | | | HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO. | | | 72-15. | | | | | | 2. SEPARATE PERMITS SHALL BE OBTAINED FOR THE | | | FOLLOWING: I) FENCING/WALLS, II) LANDSCAPING, AND III) | | | IRRIGATION. | | | | | | 3. PRIOR TO THE INSTALLATION OF ANY SITE LIGHTING, THE | | | LIGHTING PLAN SHALL BE REVISED TO REFLECT PHOTOMETRIC | | | LEVELS NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT | | | THE PROPERTY LINE. | | | | | | 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | THE PROPERTY SHALL BE RE-PLATTED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-08-24 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-08-24 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-08-24 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2015-08-24 16:02:36 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.24.2015 | | | PERMIT NO.: 15050261, 15050262, 15050263 | | | ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807 | | | DIVISION AVENUE | | | CONTRACTOR/CONTACT: ??? | | | TELEPHONE NO.: ??? | | | SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL | | | DEVELOPMENT. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. A MINOR AMENDMENT WILL EVENTUALLY NEED TO BE | | | SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT - | | | PLANNING DIVISION TO REFLECT ALL OF THE REVISIONS THAT | | | HAVE OCCURRED SINCE THE APPROVAL OF RESOLUTION NO. | | | 72-15, AS WELL AS THE FOLLOWING WHICH WERE CONDITIONS | | | OF APPROVAL: | | | | | | I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS | | | WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE | | | (IN ALIGNMENT WITH 17TH STREET). | | | | | | II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF | | | THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3. | | | | | | 2. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED. | | | APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF | | | SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED | | | COST ESTIMATE (MATERIAL + LABOR). | | | | | | 3. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED | | | INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING | | | THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX. | | | | | | 4. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED | | | THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE | | | DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE | | | NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.). | | | | | | 5. ON SHEET A1.01, DETAIL 3 DOES NOT MEET THE MINIMUM | | | REQUIREMENTS OF THE CITY'S ZONING AND LAND DEVELOPMENT | | | REGULATIONS WITH REGARD TO SIZE, AND DOESN'T MATCH WHAT | | | IS SHOWN ON THE PLANS. | | | | | | 6. THE SITE LIGHTING SHOWN ON SHEET E-1.00 AND E-1.10 | | | DO NOT MATCH. AND PHOTOMETRIC LEVELS SHALL BE SHOWN AT | | | THE PROPERTY LINE, NOT EXCEEDING 0.5 FOOTCANDLES. | | | | | | 7. IN AN EMAIL TO JON SCHMIDT & ASSOCIATES ON | | | 8/24/2015, SEVERAL AREAS OF CONCERN WERE IDENTIFIED | | | WHERE IT APPEARS THAT THE LOCATION OF UTILITIES, SIGHT | | | LIGHTING, ETC. HAVE CREATED DEFICIENCES OR CONFLICTS | | | WITH LANDSCAPING. THESE AREAS SHOULD BE EVALUATED AND | | | ADJUSTED ACCORDINGLY. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 5/19/15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-05 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-06-05 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-06-05 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2015-06-05 16:02:01 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 06.04.2015 | | | PERMIT NO.: 15050261, 15050262, 15050263 | | | ADDRESS: 838 ADAMS STREET, 1851 DIVISION AVENUE, 1807 | | | DIVISION AVENUE | | | CONTRACTOR/CONTACT: ??? | | | TELEPHONE NO.: ??? | | | SCOPE OF REVIEW: NEW MULTIFAMILY RESIDENTIAL | | | DEVELOPMENT. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PURSUANT TO RESOLUTION NO. 72-15, PRIOR TO THE | | | ISSUANCE OF A PERMIT: | | | | | | A. A MINOR AMENDMENT SHALL BE SUBMITTED TO THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION FOR | | | THE FOLLOWING: | | | | | | I. INCLUDE SHADE/FLOWERING TREES IN THE BULB-OUTS | | | WITHIN THE EAST-WEST ACCESS DRIVE FROM DIVISION AVENUE | | | (IN ALIGNMENT WITH 17TH STREET). | | | | | | II. REMOVAL OF THE PRIVACY WALL FROM THE WEST SIDE OF | | | THE SIDEWALK THAT CONNECTS BETWEEN BUILDINGS #2 AND #3. | | | | | | 2. REMINDER - PRIOR TO THE ISSUANCE OF ANY CERTIFICATE | | | OF OCCUPANCY, THE PROPERTY SHALL BE RE-PLATTED IN | | | ACCORDANCE WITH ALL APPLICABLE STATUTES, REGULATIONS, | | | AND THE CITY'S POLICIES AND PROCEDURES. | | | | | | 3. LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED. | | | APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF | | | SIGNED/SEALED LANDSCAPE PLANS, ALONG WITH A CERTIFIED | | | COST ESTIMATE (MATERIAL + LABOR). | | | | | | 4. REMINDER - ALL UTILITIES WITHIN THE RPD SHALL BE | | | LOCATED UNDERGROUND. | | | | | | 5. THE EAST-WEST ROADWAY EXTENDING WEST FROM DIVISION | | | AVENUE (IN LINE WITH ADAMS STREET), SHALL BE | | | INCORPORATED INTO ALL PERMIT MATERIALS FOR THIS PROJECT | | | AS IT IS REQUIRED TO BE COMPLETED IN ASSOCIATION WITH | | | SILVER PALM PLACE. | | | | | | 6. PLEASE CONFIRM THAT THE PROPOSED DESIGN, RADIUS, | | | MATERIALS, LOAD, ETC. FOR THE ROUNDABOUT WILL BE | | | ACCEPTABLE TO THE CITY'S FIRE-RESCUE DEPARTMENT; OR ARE | | | THEY ACCEPTABLE OF DRIVING THROUGH THE PARKING AREA? | | | SIGNAGE MAY BE REQUIRED. | | | | | | 7. SECTION I-I AND J-J ON SHEET PD-3 IS LABELED | | | INCORRECTLY; IT INDICATES THE ADJACENT PROJECT AS BEING | | | THE PAUL LAWRENCE DUNBAR SENIOR COMPLEX. | | | | | | 8. ADDITIONAL STRIPING AND/OR SIGNAGE MAY BE REQUIRED | | | THROUGHOUT THE SITE (I.E. AT THE ROUNDABOUT TO INDICATE | | | DIRECTION OF TRAVEL, AT THE INTERSECTION OF THE | | | NORTH-SOUTH DRIVE AND THE PARKING AREAS, ETC.). | | | | | | 9. PLEASE CONSULT WITH THE CITY'S TRAFFIC ENGINEER AS | | | TO WHETHER OR NOT THE EAST-WEST ROADWAYS SHOULD BE | | | SIGNED AS "ADAMS STREET" AND "17TH STREET". THESE WILL | | | NOT BE DEDICATED ROADWAYS. ADDITIONALLY, I DON'T IF THE | | | PROPER ADDRESSES HAVE BEEN ASSIGNED BECAUSE OF THIS. | | | | | | 10. THE UTILITIES SHOWN ON THE WATER & SEWER PLANS DO | | | NOT MATCH WHAT WAS SHOWN ON THE LANDSCAPE PLANS. PLEASE | | | ENSURE THAT THE PLANS ARE CONSISTENT AND THAT THERE ARE | | | NO CONFLICTS. ADDITIONALLY, THE LANDSCAPE PLANS SHALL | | | ENSURE THAT ALL MECHANICAL EQUIPMENT, METERS, BACKFLOW | | | PREVENTERS, ETC. ARE SCREENED AS REQUIRED. | | | | | | 11. THERE IS AN FDC CONNECTION SHOWN IN A LANDSCAPE | | | ISLAND NEAR BUILDING #2 THAT APPEARS TO CONFLICT WITH A | | | PROPOSED SHADE TREE. THE FDC MAY NEED TO BE RELOCATED. | | | | | | 12. PLEASE ENSURE THAT THERE IS NO CONFLICT BETWEEN THE | | | LANDSCAPING AND THE PROPOSED FIRE HYDRANT LOCATED IN | | | THE PARKING LOT ISLAND BETWEEN BUILDINGS #2 AND #1 | | | (SOUTH OF THE ROUNDABOUT). | | | | | | 13. ON SHEET A1.01, DETAIL 1 SHOULD SHOW A MINIMUM OF 5 | | | FEET OF LANDSCAPING ISLAND FROM THE INSIDES OF THE | | | CURBING. | | | | | | 14. ON SHEET A1.01, DETAILS 3 AND 3.1 DO NOT MEET THE | | | MINIMUM REQUIREMENTS OF THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS WITH REGARD TO SIZE, STRIPING, | | | ETC. | | | | | | 15. ON SHEET A1.01, DETAIL 9, THE LANDSCAPING IS ON THE | | | WRONG SIDE OF THE CONCRETE PAD, AND THE BIKE RACKS MAY | | | BE ORIENTED IN THE WRONG DIRECTION ON THE SITE PLAN. | | | THE BIKE RACK SHOULD BE ORIENTED SUCH THAT TWO (2) | | | BIKES CAN BE EASILY PUSHED INTO PLACE ON EITHER SIDE OF | | | THE RACK. | | | | | | 16. ON SHEET A1.00, NOTES #9 AND #10 ARE REVERSED. | | | | | | 17. ON SHEET A-1.02, THE STAIR FLOOR PLANS REFER TO THE | | | INCORRECT SHEET FOR THE CROSS SECTIONS. | | | | | | 18. IN LOOKING AT THE BUILDING PERMITS, THE ARCHITECT'S | | | PLANS ARE SHOWING THAT THE FIRST FLOOR OF THE UNITS ON | | | DIVISION AVENUE IS 4-5 FEET (OR MORE IN SOME AREAS) | | | ABOVE GRADE. THIS LEAVES A LARGE AREA UNDERNEATH THE | | | FIRST LEVEL OF WINDOWS. ALL THAT'S PROPOSED ON THE | | | LANDSCAPE PLAN IS SOD WITH A 24 INCH HIGH ROW OF | | | "SEMINOLE PINK HIBISCUS". ADDITIONAL PLANTINGS SHALL BE | | | PROVIDED TO ADDRESS THE SCALE OF THE BASE OF THE | | | BUILDING. | | | | | | 19. LANDSCAPE SCREENING SHALL BE PROVIDED AROUND THE | | | PROPOSED FPL TRANSFORMERS (UNLESS OTHERWISE PROHIBITED | | | BY FPL). | | | | | | 20. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN | | | THE PROPOSED SITE LIGHTING AND THE LANDSCAPING. | | | | | | 21. LANDSCAPE SCREENING AND FENCING SHALL BE PROVIDED | | | FOR THE POOL EQUIPMENT. | | | | | | 22. ELECTRICAL PLANS SHOW MULTIPLE CONFLICTS BETWEEN | | | THE PROPOSED FPL TRANSFORMERS AND THE LANDSCAPING. | | | | | | 23. PLEASE PROVIDE CROSS SECTIONS AT THE LOCATIONS OF | | | THE ROOF-TOP MECHANICAL EQUIPMENT TO INDICATE THAT ALL | | | EQUIPMENT WILL BE ADEQUATE SCREENED WITH THE PROPOSED | | | PARAPETS, ETC. PLEASE SHOW THE MECHANICAL EQUIPMENT | | | (ACCURATELY SIZED) IN THE CROSS SECTION. | | | | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | 2015-05-19 11:22:17 | 5/19/15 |
|
|
|