Plan Review Details - Permit 15050152
Plan Review Stops For Permit 15050152
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-15 Cont ID  
Sent By ccole Date 2015-07-15 Time 15:10 Rev Time 0.00
Received By ccole Date 2015-07-14 Time 10:26 Sent To  
Notes
2015-07-15 10:26:44RESUB ON CCOLE DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-07-15 Cont ID  
Sent By ccole Date 2015-07-15 Time 11:12 Rev Time 0.00
Received By ccole Date 2015-07-15 Time 11:12 Sent To  
Notes
2015-07-15 15:10:35MECHANICAL PROVISOS:
  
 1) WELDER'S CERTIFICATE MUST BE ON-SITE AT TIME OF
 INSPECTION.
 2) SEPARATE PERMIT REQUIRED FOR INSTALLATION OF THE
 TOWER GUARDRAIL AND LADDER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By ccole Date 2015-05-12 Time 11:10 Rev Time 0.00
Received By ccole Date 2015-05-12 Time 11:10 Sent To  
Notes
2015-07-15 11:12:131ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050152
  
 1) PROVIDE PLANS AND SPECIFICATIONS FOR INSTALLATION OF
 THE NEW COOLING TOWER INDICATING COMPLIANCE WITH ALL
 APPLICABLE SECTIONS OF NFPA 214, AND SECTION 908 FBC-10
 MECHANICAL.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  